[11]
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Manual shutdown the Genset without cooling down the engine
3.
.........................................................................................................................
Hour Meters
1.
Acc.: Seconds/
Setting
:
0~59(Seconds)
Default
:
0
Description
:
Set the hour meter in seconds.
2.
Acc.: Minutes
Setting
:
0~59(Minutes)
Default
:
0
Description
:
Set the hour meter in minutes
3.
Acc.: Hour
Setting
:
0~99(Hour)
Default
:
0
Description
:
Set the hour meter in hours.
4.
Acc.: Hour * 100
Setting
:
0~99(*100)
Default
:
0
Description
:
Set the hour meter in 100 hours scale.
4.
.........................................................................................................................
Sensors Switches
1.
H.W.T. Detection
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates high water temperature protection
2.
H.T. Sw. Type
Setting
:
NC/NO
Default
:
Normal Open
Description
:
Setup the switch to normally close or normally open.
3.
H.W.T. Sw. Delay
Setting
:
1~9.5(Seconds)
Default
:
1.5
Description
:
When high water temperature occurres, timer starts before initiating shutdown.
4.
L.O.P. Detection
Setting
:
Disable/ Enable
Default
:
Enable
Summary of Contents for GTR-610