[12]
Description
:
Activates low oil pressure protection
5.
O.P. Sw. Type
Setting
:
NC/NO
Default
:
Norma close
Description
:
Setup the switch to normally close or normally open.
6.
L.O.P Sw. Delay
Setting
:
0.2~6.0(Seconds)
Default
:
1
Description
:
When low oil pressure occurres, timer starts before initiating shutdown.
5.
.........................................................................................................................
Auxiliary Input
1.
Auto input delay
Setting
:
0.2~5(seconds)
Default
:
1
Description
:
Time delay for ATS input before initiating crank procedure.
2.
Input0 Detect
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates Input 0 function
3.
Input 0 Name
Setting
:
1.Emergency Stop 2.User Define 3.Low battery Voltage 4. System fault 5.High fuel
level 6. System trip 7.Insulation Fail 8.Cooling failure 9.Malfunction warning 10.Charge
fail 11.Over load 12.Low water temperature 13.Preheat
Default
:
Preheat
Description
:
Define the function for input 0
4.
In0 Protection
Setting
:
1.Warning 2.Alarm 3.Trip 4.Stop)
Default
:
Stop.
Description
:
Setup the action when input 0 activates
5.
In0 Switch Type
Setting
:
NC/NO
Default
:
Normal Close
Description
:
Setup input 0 to normally close or normally open
6.
Input0 Delay
Setting
:
0.2~5.0(Seconds)
Default
:
0.2
Description
:
When input0 activates, timer starts before activating protection
7.
Input 1 Detect