[22]
Setting
:
300~900(RPM)
Default
:
480
Description
:
Disconnect starter motor when RPM reaches setting
5.
RPM Disp. Source
Setting
:
Alternator / Frequency
Default
:
Freq.
Description
:
Converts the RPM from frequency or alternator speed.
6.
O.S. Detection
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates over speed protection.
7.
O.S. set point
Setting
:
1350~2100(RPM)
Default
:
1980
Description
:
If e
ngine speed is higher than setting, controller shuts down the engine only if
over speed is enabled
8.
Over speed delay
Setting
:
1~10(Second)
Default
:
1
Description
:
When over speed occurres, timer starts before activating protection
12.
.......................................................................................................................
Sensors
1.
LFL Value Alarm
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates low fuel warning
2.
LFL set point
Setting
:
6~55(%)
Default
:
45
Default
:
When fuel level is below setting, controller displays warning message.
3.
HFL set point
Setting
:
35~99(%)
Default
:
95
Description
:
When fuel level is above setting, controller displays warning message
4.
LOP value alarm
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates low oil pressure warning
Summary of Contents for GTR-610