9
MAIN MENU
SUB MENU 1
SUB MENU 2 SUB MENU 3
COMMENTS
RS485
PROTOCOL
Modbus RTU
Modbus Ascii
SiloPatrol (default)
Select for generic Modbus RTU protocol.
Select for generic Modbus Ascii.
Select for proprietary SiloPatrol protocol.
RS485
SETTINGS
Modbus RTU
9600,8,E,1
9600,8,N,1
9600,8,N,2
9600,8,O,1
19200,8,E,1
19200,8,N,1
19200,8,N,2
19200,8,O,1
Modbus ASCii
9600,7,E,1
9600,7,N,2
9600,7,O,1
9600,8,E,1
9600,8,N,1
9600,8,N,2
9600,8,O,1
19200,7,E,1
19200,7,N,2
19200,7,O,1
19200,8,E,1
19200,8,N,1
19200,8,N,2
19200,8,O,1
SiloPatrol
9600,8,N,1
baud rate, # bit, parity, # stop bit
Options available are dependent on the
protocol selected.
(default protocol: SiloPatrol)
9600,8,N,1
For SiloTrack Cloud select:
Modbus RTU 9600,8,N,1
DEVICE
ADDRESS *
Modbus RTU
#1 - 247
Modbus Ascii
#1 - 247
SiloPatrol
#
1
- 16
Acceptable addresses are dependent on the
protocol selected.
(default address: #1)
RELAY
SETTINGS
RELAY ACTION *
FORCE RELAY
RELAY THRESHOLD
OFF
CYCLE
OPERATE
ERROR
LOW
THRESHOLD
HIGH
THRESHOLD
NOT ACT (on)
ACT (off)
###.#
No relay action, energized whenever power is
applied.
Relay relaxed while SMU is sounding, ener-
gized when bob idle.
(default: CYCLE OPERATE)
Relay relaxed when error is detected,
energized when error dismissed.
When distance => thres, relay relaxed
When distance < thres, relay energized
Use distance from latest measure, only
update on "good" cycles, relaxed if Genesis.
When distance > thres, relay energized
When distance <= thres, relay relaxed
Use distance from latest measure, only
update on "good" cycles, relaxed if Genesis.
Relay temporarily not activated (on) regardless of status.
Relay temporarily activated (off) regardless of status.
Distance threshold
range: 0 ~ 200ft / 0 ~ 61.0m
(default: 200ft)
Menu Selection for ConfigureSensor App - RS-485
(Factory Defaults are Shown in Bold)
* Denotes that parameter can also be adjusted with Modbus communications.
Figure 11