6

RS485 (5.3)

SD Card (6.1)

DIP Switches (6.2)

Reset Button (6.4)

Real-time Clock/Backup Battery (6.3)

BACnet (5.4)

The general RS485 connector (J1) is a 4-way terminal that provides 24V DC 

power and RS485 differential signals to an external device that communicates 

over RS485. This is for future functionality and is not yet implemented in 

firmware or in the iNVent Configurator.

iNVent 2 has an SD card socket which is used to data-log the system 

operation. 2 types of file are created on the SD card, a data-log of the system 

status and an event log of notable events. This data can be used to analyse 

the operation of an iNVent 2 system and associated products to provide case 

study analysis of how the system is performing  and allows Monodraught 

The DIP switches on iNVent 2 provide some alternative functions /operational 

modes. 

At the moment these are only used for testing purposes.

They must all be set to “OFF” to ensure normal operation.

If the panel needs to be reset for some reason, instead of cycling the power, 

the micro-controller can be reset using the reset button (S3).

The iNVent 2 panel has a built-in real-time clock which it uses for various 

functions such as time-stamping data logs, calculating the current 

season and providing out of hours closure of automated windows. 

 

It uses a CR2032 battery in order to maintain the time and date when the 

power is off to the panel. The battery should last 5 years with no power to the 

panel. When the panel is powered, the battery is not used.

In order to satisfy different markets, iNVent 2 is provided with UTC, Coordinated 

Universal Time, and Local Time. iNVent 2 will display the local time to the user 

and for data logging purposes it saves the data in UTC in order to simplify the 

analysis of the data, especially when daylight savings is enabled.

The BACnet module socket (A1) allows the optional BACnet module from 

Cimetrics to be installed into the iNVent 2 panel in order to make system 

status information available on a BACnet network, if desired by the customer.

Only BACnet/IP is supported and requires an Ethernet connection and a 

static IP address. Please see the iNVent 2 - Optional BACnet module product 

card for further information.

SYSTEM

SPECIFICATIONS

This section describes extra features of the iNVent 2 panel not covered by 

other categories.

engineers to analyse the data in order to improve on the system performance.  

2GB cards have been tested, but larger capacities should also be supported.

General Features

Summary of Contents for INVENT 2

Page 1: ...INVENT 2 Operational Manual...

Page 2: ...inal J3 Master Controls BMS I O General Features Damper Louvre Connection USB Fault Output Optional Night time cooling LEDs Smoke Vent Input Optional Control Strategy RS485 Competition Key Switch Inpu...

Page 3: ...SENSOR 2 RS485 DMP LVR DAMPER LOUVRE 0V 24V DMP LVR WALL ACTUATOR 0V 24V Zone 0V 24V 0V 24V SENSOR 1 SENSOR 2 RS485 DMP LVR DAMPER LOUVRE 0V 24V DMP DMP LVR WALL ACTUATOR 0V 24V Zone 0V 24V 0V 24V SE...

Page 4: ...Jack J2 is used to connect power to the panel from the external power supply and is centre positive The Power Terminal J3 is for future use when the power supply will be integrated within a new desig...

Page 5: ...panel in order to see the status and configuration of the panel via the iNVent Configurator software This enables the iNVent 2 panel to be reconfigured to operate in more advanced and custom configura...

Page 6: ...t uses for various functions such as time stamping data logs calculating the current season and providing out of hours closure of automated windows It uses a CR2032 battery in order to maintain the ti...

Page 7: ...y24VDC connected to J34 One such suitable sensor is the Titan Products part ref TPVOS This should be located out of direct sunlight and away from any heat sources that could affect the air temperature...

Page 8: ...se contact is closed all dampers louvres wall louvres and windows will close If both the Open and Close inputs are activated at the same time by an external system then the Close setting will take pri...

Page 9: ...contact rated at 24V 1A maximum The iNVent 2 panel has four solid state relays Upper terminals of J15 J18 J22 J26 for controlling a cooling system per zone This is not currently supported but will be...

Page 10: ...e set to close when the internal temperature is at least 25 C and the external temperature is at least 5 C above the internal temperature This feature is designed to prevent a space from heating up du...

Page 11: ...e level drops below 1300 ppm Note If the dampers are already at 100 they do not open any further Input Priority 1 Fire Key Switch Highest 2 Fire Alarm 3 Competition Switch 4 Override Open 5 Override C...