background image

www.monodraught.com

info@monodraught.com

9

RS485 Digital Interface (8.3)

BMS I/O (9.1)

General Purpose Inputs (9.2)

Heating Solid State Relays (9.3)

Cooling Solid State Relays (9.4)

Sensor 1/2 Input (8.4)

The RS485 Digital Interface is for future support of digital communication 

between Monodraught products. Currently there are no products that 

support this, but this section will be updated when they have been 

developed. Currently it provides 24V power and an RS485 connection over a 

RJ45 terminated CAT5 cable, but MUST NOT BE CONFUSED WITH ETHERNET.

The BMS I/O connections (J17) allow the iNVent 2 panel to send or receive 

signals to/from a BMS system for tighter control and integration. It provides 

The general purpose inputs (J21 & J25) provide four 0 - 10V inputs and 24V DC 

power to additional devices or sensors. These can be configured to operate 

with a wide variety of sensors through the iNVent 2 configurator software.

The iNVent 2 panel has four solid state relays (Lower terminals of J15, J18, 

J22, J26) for controlling a heating system per zone. This is not currently 

supported, but will be in a future release of firmware. It is a volt-free contact 

rated at 24V, 1A maximum.

The iNVent 2 panel has four solid state relays (Upper terminals of J15, J18, 

J22, J26) for controlling a cooling system per zone. This is not currently 

supported, but will be in a future release of firmware. It is a volt-free contact 

rated at 24V, 1A maximum.

The Sensor 1 and 2 inputs are used to connect to Monodraught sensors and 

wall controllers, as well as any other sensors that output a 0-10V signal. 

By default, Sensor 1 is configured as a Monodraught WINDCATCHER Wall 

Mounted Controller, and Sensor 2 is configured as an additional 0-50°C 

temperature sensor. This means that by default, iNVent 2 operates the same 

way as an iNVent 1 panel.

The terminals are wired as follows, from left to right:

1.

  0V DC

2.

  0 - 10V Input from Sensor

3.

  24V DC Power

SYSTEM

SPECIFICATIONS

four 0 - 10V outputs, and four 0 - 10V inputs which can be configured for a 

variety of purposes.

An example of this is getting the BMS system to send the room temperature 

that it reads and uses for the control of other systems, such as heating, to 

the iNVent  2 panel so that one common measurement is used to prevent 

cooling/heating system fighting or oscillation. It can also operate in reverse, 

so that the BMS uses the temperature measurements that the iNVent 2 panel 

measures to base the operation of other building systems on.

Additional I/O

Summary of Contents for INVENT 2

Page 1: ...INVENT 2 Operational Manual...

Page 2: ...inal J3 Master Controls BMS I O General Features Damper Louvre Connection USB Fault Output Optional Night time cooling LEDs Smoke Vent Input Optional Control Strategy RS485 Competition Key Switch Inpu...

Page 3: ...SENSOR 2 RS485 DMP LVR DAMPER LOUVRE 0V 24V DMP LVR WALL ACTUATOR 0V 24V Zone 0V 24V 0V 24V SENSOR 1 SENSOR 2 RS485 DMP LVR DAMPER LOUVRE 0V 24V DMP DMP LVR WALL ACTUATOR 0V 24V Zone 0V 24V 0V 24V SE...

Page 4: ...Jack J2 is used to connect power to the panel from the external power supply and is centre positive The Power Terminal J3 is for future use when the power supply will be integrated within a new desig...

Page 5: ...panel in order to see the status and configuration of the panel via the iNVent Configurator software This enables the iNVent 2 panel to be reconfigured to operate in more advanced and custom configura...

Page 6: ...t uses for various functions such as time stamping data logs calculating the current season and providing out of hours closure of automated windows It uses a CR2032 battery in order to maintain the ti...

Page 7: ...y24VDC connected to J34 One such suitable sensor is the Titan Products part ref TPVOS This should be located out of direct sunlight and away from any heat sources that could affect the air temperature...

Page 8: ...se contact is closed all dampers louvres wall louvres and windows will close If both the Open and Close inputs are activated at the same time by an external system then the Close setting will take pri...

Page 9: ...contact rated at 24V 1A maximum The iNVent 2 panel has four solid state relays Upper terminals of J15 J18 J22 J26 for controlling a cooling system per zone This is not currently supported but will be...

Page 10: ...e set to close when the internal temperature is at least 25 C and the external temperature is at least 5 C above the internal temperature This feature is designed to prevent a space from heating up du...

Page 11: ...e level drops below 1300 ppm Note If the dampers are already at 100 they do not open any further Input Priority 1 Fire Key Switch Highest 2 Fire Alarm 3 Competition Switch 4 Override Open 5 Override C...

Page 12: ...Halifax House High Wycombe Buckinghamshire HP12 3SE 44 0 1494 897700 www monodraught com info monodraught com Follow us on...

Reviews: