H36PVN Power Vent Indoor Gas Fireplace
Page 13
XG0649 - 031511
Installation
Venting Layout
Selection of components and details of venting lay out should adhere
to the following guidelines:
■ Ensure there is a minimum run of 2’ of straight pipe before
the power vent .
■ Ensure the maximum vent run does not exceed 100’ .
■ Ensure the number of 90° elbows does not exceed 6 .
■ Ensure the number of 45° elbows does not exceed 12 .
Figure 6. Typical Venting Installations.
Multi-Elbow Installations
Multi-elbow installations are possible up to a maximum of six
at 90° elbows .
Figure 6a. Multi-elbow Venting Installations.
Figure 6b. Downward Venting Installations.
Downward Vertical Venting
Note: The downward vent run must not exceed 6' of vent run .
Installing a Wall Mounted Vertical Exterior Power Vent
(EDVWSPV58)
This section applies to installations where the shortest possible vent
run is through an exterior wall . Refer to Appendix A - Power Vent
locations, to ensure the planned Power vent location is acceptable .
Once the vent location has been established, please refer to the
appropriate section below for installation details .
Once the vent location has been established, please refer to the
appropriate section below for installation details .
All venting material must be sealed with high heat
silicone sealant RV230. All venting material to be
Montigo flex pipe, with as few joints as possible.
All joints use MVA vent splice, sealed thoroughly
with silicone. Montigo will not be held responsible
for any water damage that may occur from not
installing the equipment as specified by this
document.
WARNING
XW2024
Venting Installation
V + H (Maximum Length)
Max. #
Elbows
80 Feet
6
Multi Elbow - Venting Installation
V1 + H1 + V2 + H2 + V3 = H3
(Maximum Length)
Max. #
Elbows
80 Feet
6
Multi Elbow - Venting Installation
V1 + H1 + D + H2
(Maximum Length)
Max. #
Elbows
40 Feet
6
H
V
Elbow 1
Elbow 2
Elbow 3
Elbow 5
Elbow 4
Elbow 6
H3
H2
H1
V1
V2
V3
H2
H1
V
D