13
Installation
XG0228 - 021419
Figure 8.b
H34DFN Top Vent Venting Graph for wall mounted terminations
Figure 8.
Top Vented, wall mounted installation with 1 elbow (1 one 90° bend). The vent run
must comply with Venting Graph for Top vent, wall mounted terminations
Selection of components and details of venting layout should adhere
to the following guidelines:
• Vent terminations must not be recessed in walls or siding.
• For Heat Shield requirements see Section 3-3.
• Once the proposed venting layout has been determined refer to
graph to ensure the layout is acceptable.
Notes Wall Mounted Terminations: TOP VENT
• All measurements for vertical or horizontal runs are measured from
center of the vent pipe.
• Venting runs must fall within the limits set by the venting graph.
H34 Top Venting Graph
Measure the vertical height from the fireplace hearth to the centre of
the termination and the horizontal run from the fireplace flue collar to
the wall flange of the termination. Plot on the Venting Graph with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Wall mounted Terminations:
The following details are some possible configurations for Wall mounted
terminations. See below.
H34DFN VENT RUN
Figure 8.d
Top Vented, wall mounted Multi-elbow installation. The vent run must comply with
Venting Graph for Top vent, wall mounted terminations,
Exterior
Wall
Hearth
Termination
Heat Shield
0
HEARTH
12
12
0
60
36
84
120
24
72
108
48
96
132
Vertical Height (In.)
Horizontal Run (In.)
36
60
84
108
132
156
24
48
72
96
120
144
168 180
Acceptable vent run
within non-shaded area.
Unacceptable vent run
within shaded area.
Section 3-3-1: Venting Layout: Wall Mounted Termination
41½" Min. (NG)
72" Max. for minimum vertical
72"
41½"
Exterior
Wall
Rigid
Section
Flex
Section
Termination
Heat Shield
8½’ Min at Max.
Horizontal
15' Max.
for minimum
vertical