H*42DF Indoor Gas Fireplace
Page 12
XG0148 - 151123
Installation
The Venting Graph: H*42DF*
Measure the vertical height from the fireplace hearth to the centre
of the termination and the horizontal run from the fireplace flue
collar to the wall flange of the termination. Plot on the Venting
Graph Figure 13 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 84" and the horizontal
run to the wall flange of the vent termination is 36", this would be an
acceptable installation.
Example B: (Acceptable Installation)
If the vertical dimension from the hearth is 72" and the horizontal
run to the wall flange of the vent termination is 66", this would be an
acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 72" and the
horizontal run to the wall flange of the vent termination is 108", this
would NOT be an acceptable installation.
Figure 13. H*42DF* Top Vent
Venting Graph for
wall mounted
terminations.
Section 3-3-1:
Venting Layout:
Wall mounted termination. Selection of components and details
of venting layout should adhere to the following guidelines:
Vent terminations must not be recessed in walls or siding.
For Heat Shield requirements see Section 3-3-3.
Once the proposed venting layout has been determined
refer to Figure 13 or 15 to ensure the layout is
acceptable.
Notes Wall Mounted Terminations: TOP VENT
All measurements for vertical or horizontal runs are
measured from center of the vent pipe.
Venting runs
must
fall within the limits set by the venting
graph, see Figure 13.
Wall mounted Terminations
The following details are some possible configurations for Wall
mounted terminations.
Figure 13a.
Top Vented,
wall mounted installation with one
90° bend.
The vent run must comply with Venting Graph for
Top vent, wall
mounted
terminations,
Figure 13.
Figure 13b.
Top Vented
, wall mounted Multi-elbow installation.
See
Venting Graph for
Top vent, wall mounted
terminations,
Figure 13.
42”
46”
B
C
A
Ve
rtical Run (in.)
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
If your installation does not fall
within the venting graph parameters,
please contact a local Montigo
dealer for Power Venting options.
Solid Section
Flex Section
Hearth
15’foot Max.
Heat
Shield
Termination
Exterior
Wall
Heat
Shield
Termination
Hearth
Exterior
Wall
46”Min.
42” Max.
Flex or Ridig
section