H*42DF Indoor Gas Fireplace
Page 16
XG0148 - 151123
Installation
Section:
Figure 15.
Rear Vent
Venting Graph for
wall mounted
terminations.
Notes Wall Mounted Terminations: REAR VENT
All dimension lengths for vertical or horizontal runs are
measured from center of the vent pipe.
Venting runs
must
fall within the limits set by the venting
graphs, see Figure 15.
Fireplace must be converted to Rear Vent configuration
prior to running vent, see Figure 9 and 9a.
The Venting Graph
Measure the vertical height from the fireplace hearth to the centre
of the termination and the horizontal run from the fireplace flue
collar to the wall flange of the termination. Plot on the Venting
Graph Figure 15 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the
horizontal run to the wall flange of the vent termination is
138", this would be an acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 48" and the horizontal
run to the wall flange of the vent termination is 96",this would
NOT be an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 72"
and the horizontal run to the wall flange of the vent termination
is 120", this would NOT be an acceptable installation.
Figure 15b.
Rear Vented, wall mounted
Multi-elbow termination
installation. Installation for
H*42DF*
must have a minimum vertical
rise of
52"
.The vent run must comply with the Venting Graph for
Rear vent, wall mounted
terminations,
Figure 15.
Figure 15a.
Straight run, Rear Vented
, wall mounted termination for
H*42DF*
,
Figure 15. N.G. (Natural Gas) equipped fireplaces ONLY. For
Propane
fireplaces, see
figure 15b
below.
NOTE: 18” MAX. horizontal run
with no vertical lift. N.G. (Natural
Gas) fireplaces ONLY.
PXT Extension
RHS101 Heat
Shield
Termination
Hearth
Exterior
Wall
18” MAX.
33"
6”
30” Max.
52” Min.
18”
Max.
Flex or Rigid
Section
19”
Min.
33”
6”
33”
18” NG Only
A
B
C
52”
48”
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
If your installation does not fall
within the venting graph parameters,
please contact a local Montigo
dealer for Power Venting options.
Note: Images are shown without screens for clarity purposes.