H*42DF Indoor Gas Fireplace

XG0148 - 151123

Maintenance

Section: 

Maintenance

Lighting Instructions

See pages 32 to 34.

    CAUTION!

„

  Fireplace gas control must be in the “OFF” position and pilot 

and main burners extinguished when cleaning appliance 

with a vacuum. 

„

  Doors can get very hot. Handle only when cool.

General

„

  Have the fireplace and installation inspected yearly. The inspection 

must include, but is not limited to, the following: 

•   A visual check of the entire vent system and termination.

•  An  inspection  of    the  explosion  relief  flappers  and  the  door  

gaskets to ensure a proper seal.  

•  An inspection of the burner, vent run, and primary air openings.

•   An inspection of the gas valve, gas components, and pilot flame.  

For your convenience a 1/8" manifold pressure tap is supplied on 

the gas valve for a test gauge connection.

•  Ensure proper log placement as per this manual.
•  Inspection of all optional equipment; fans, thermostats, etc.
•  Inspection of glass doors and screen for damage and proper 

installation.

„

  For Natural Gas this appliance requires a minimum inlet pressure of 

5.5" W.C. and a manifold pressure of 3.5" W.C.

„

  For Propane Gas this appliance requires a minimum inlet pressure of  

11" W.C. and a manifold pressure of 10" W.C.

„

  Always keep the fireplace area clear and free of combustible materials, 

as well as gasoline and other flammable vapors and liquids. 

„

  Do not use this appliance if 

any part has been under water

Immediately call a qualified service technician to inspect the appliance 

and to replace any part of the control system and any gas control which 

has been under water.

Cleaning

When the fireplace is first activated, there may be some smoking and a 

visible film may be left on the glass. This is a normal condition, and is 

the result of burning of protective coatings on new metal.

„

  Glass must be cleaned periodically to remove any film (which is a 

normal by-product of combustion) which may be visible. Film can easily 

be removed by removing the door, as shown on Page 25. Handle the 

door carefully, and clean it with non-abrasive glass cleaners. One of 

the most effective products is Kel Kem.

„

  Silicone seals on inner door during initial firing will "off gas", leaving 

a visual deposit of a white substance on combustion chamber walls. 

This can easily be removed from the chamber walls using normal 

household products.

„

  Use a vacuum cleaner or whisk broom to keep the control compartment, 

burner, and firebox free from dust and lint.

„

  Logs may be cleaned periodically with a vacuum to remove soot or 

other contaminates.

Hi-Lo Burner Adjustment: (SIT Nova 820).
The H*42DF* is equipped with an adjustable burner, allowing you 

to raise or lower the flames. To adjust the flames, locate the black 

knob marked 'Hi-Lo', in the centre of the gas control valve (See 

Figure 31). 

„

   To raise the flame height, turn the black knob (located behind 

the lower control compartment) counter-clockwise.

„

   To lower the flame height, turn clockwise.

Figure 49. 

'Hi-Lo' Adjustment  on  the  SIT  Nova  820    gas 

valve, 

Hi-Lo Burner Adjustment: (SIT Proflame 2).

The H*42DFI is equipped with an adjustable burner, allowing you 

to raise or lower the flames. To adjust the flames, locate the black 

knob marked 'Hi-Lo', in the centre of the gas control valve (See 

Figure 32). 

„

   To raise the flame height, turn the black knob (located behind 

the lower control compartment) counter-clockwise.

„

   To lower the flame height, turn clockwise.

Figure 50. 

'Hi-Lo' Adjustment  on  the  SIT  Proflame  2  gas 

valve. 

Manifold Pressure
Test Connection

Pilot Adjustment Screw

Hi Lo Adjustment

Inlet Pressure
Test Connection

Pilot Burner Adjustment.
1.  Locate Pilot Adjustment Screw. 

(See

 figure 31 or 32.

)

2.  Adjust pilot screw to provide properly sized flame as shown.

3.  After installing or servicing, leak test with a soap solution with 

main burner on. Coat pipe and tubing joints, gasket etc. with soap 

solution. Bubbles indicate leaks. Tighten any areas where the 

bubbles appear until the bubbling 

stops completely.

Manifold Pressure

Test Connection

Wall Switch

Power 

Generator

Pilot Adjustment Screw

Inlet Pressure

'Hi-Lo' Adjustment Knob

Gas Control Knob (Shown in “Pilot” position)

Summary of Contents for H42-DF

Page 1: ...igh voltage Toxic Flammable materials Corrosive Fork lift trucks Danger overhead crane Explosion risk Oxidising Danger of death Biohazard Laser Radiation Danger of entrapment Hot surface General Warni...

Page 2: ...tallation only available for SIT Electronic Ignition Systems 21 Section 5 1 FUEL CONVERSION 22 Section 5 2 GAS PRESSURE 22 Section 5 3 GAS CONNECTION 22 Section 6 Finishing 23 Section 7 Screen Install...

Page 3: ...he following table Refer to your rating plate to verify included options Throughout this manual instructions are applicable to all models designated as H 42DF unless otherwise noted Warranty Informati...

Page 4: ...A C22 1 1 Installations in the USA must conform to the local codes or in the absence of local codes to the current version of National Fuel Gas Code ANSI Z223 1 NFPA 54 Electrical Installations must c...

Page 5: ...ion Section Rating Plate Sample LB1223 V5 1 SIT IPI with screen DEC06 2014 Teklynx LabelView Demo Figure A Rating Plate for IPI eletronic ignition Figure B Rating Plate for standing pilot SIT LBL1205...

Page 6: ...nces to air conditioning ducts electrical wiring and plumbing Safety as well as efficiency of operation should be consideredwhenselectingthefireplacelocation Selectalocation that does not interfere wi...

Page 7: ...oor opening 3 Rear Vent Ceiling level Floor Top Vent 18 max Min 1 Non Combustible Header Non Combustible materials Alcove over fireplace 33 Exterior Wall Non Combustible Nailing Flange supplied figure...

Page 8: ...ler to discuss power venting options NOTES FOR PLANNING VENTING Venting originates from the unit through the top or through the rear Venting can terminate through the roof or through an exterior wall...

Page 9: ...shing around the fireplace MODEL Top Rear Vent Top Top Vent Back Sides Floor Mantel 6 Figure 7 Installing the Nailing Flange Extension Installing The Standoffs To avoid elevated mantel temperatures al...

Page 10: ...mamechanical air inlet Foramoredetaileddiagramofallowedterminationlocations see Appendix A A maximum of two offsets each offset is made up of 2 90 bends may be made for vertical vent runs Firestops mu...

Page 11: ...Section Figure 10c Rear vent Roof mounted venting 1 90 bend Support ring Support plate 32 max PVTK1 Termination 18 Max Note Images are shown without screens for clarity purposes However your fireplace...

Page 12: ...on Selection of components and details of venting layout should adhere to the following guidelines Vent terminations must not be recessed in walls or siding For Heat Shield requirements see Section 3...

Page 13: ...ame the BSR opening to 12 x 12 2 Secure the BSR Frame to the exterior sheathing of the structure 3 Fasten the termination to the BSR Frame using a minimum of 4 screws 1 Frame the MOSR opening to 12 x...

Page 14: ...120 Max Figure13c Top Vented wall mounted Retracted Multi elbow installation See Venting Graph for Top vent wall mounted terminations Figure 13 Note Images are shown without screens for clarity purpo...

Page 15: ...ch to the termination 45 or less Corner Installation Use an PTO 3 termination and an PFL 1 or PFL 2 PFL 2 12 or 24 compressed length and a frame if appropriate Flex may be turned to obtain desired deg...

Page 16: ...flange of the vent termination is 96 this would NOT be an acceptable installation Example C Unacceptable Installation If the vertical dimension from the floor of the fireplace is 72 andthehorizontalru...

Page 17: ...to consult your Building Envelope Engineer or Waterproofing Consultant for further recommendations Section 3 3 2 Venting Components The following components and associated Montigo part num bers for in...

Page 18: ...1 Min 1 Min Combustible Framing RHS8 Heat Shield 36 Min 60 Min Termination Drywall sheetrock RHS101 Heat Shield inner Section RHS101 Heat Shield Outer Section Combustible framing Termination Drywall...

Page 19: ...d Screw Wall Switch Fan Plug Receptacle Manifold Pressure Test Connection Wall Switch Power Generator Pilot Adjustment Screw Inlet Pressure Hi Lo Adjustment Knob Gas Control Knob Shown in Pilot positi...

Page 20: ...nside the fireplace depending on the model of the unit Use only low voltage wire and DO NOT connect any external power to the remote switch Refer to Figure 18 19 or 20 for wiring requirements NOTE The...

Page 21: ...a second or third time depending on prevailing temperatures or altitude When in CPI mode the pilot also keeps the system warm During a cold start condensation will normally form on the inner glass sur...

Page 22: ...ve and valve train under normal operating pressure with a commercially available leak check solution DO NOT USEAFLAME OFANYKIND TO TEST FOR LEAKS Section 5 1 FUEL CONVERSION Verify that your fireplace...

Page 23: ...lace may be hot to touch We recommend careful consideration be given to the effects of elevated mantel temperatures which may be in excess of product design for example candles plastic or pictures Thi...

Page 24: ...en Tab Receptacles in the lower section of the fireplace Makesurethetabsandscreensareloweredallthewaydown intotheScreenTabReceptaclesonthefireplace Then push each Upper Screen Stud on the top corners...

Page 25: ...e tool is firmly in the lower end of the slot as shown Then pull toward you Caution hold the tool securely 3 Step 6 Pull hard if necessary to release the spring ten sion Caution The latch springs back...

Page 26: ...Door Step 8 GrasptheDooroneitherside usuallymidwayandliftupward liftthedoorcarefullyupandawayfromthefrontofthefireplace See Figure 26g Place the Door aside in a safe place whilemaintenanceand orclean...

Page 27: ...gs using the predetermined alignment holes cast into the underside of the logs as shown above figure 27c Step 2 Place the bottom Rear log as shown in figure 27 Figure 27 Placing Bottom Rear Log Step 1...

Page 28: ...ed Rocks The HL42DF has the option of installing the cultured rocks which mimic real stone These may be spaced at random or in a visual pattern of your preference in the burner pan See the Montigo web...

Page 29: ...Rock Guard should line up between the air inlets of the burner Figure 29d Pushing the Rock Guard down into place Rock Tray Front Cover Figure 29f Completed Placement of Rock Guards Installing the Des...

Page 30: ...nt 3 faux ceramic rock E as shown 6 Place 11 eleven faux rocks F as shown below Figure 30g Placement 11 faux ceramic rock F as shown Figure 30h Completed Placement Note You may have to adjust the Faux...

Page 31: ...shown in figure 30c Place Log C knot hole as shown Figure 31d Place log D and then E note placement of Knot on log Log E 4 Place the Long front Left log Log D as shown in figure 30d Angle log with kn...

Page 32: ...remote switch to ignite fire NOTE Gas control knob cannot be turned from PILOT to OFF unless knob is pushed in slightly Do not force with American Flame Electronic Ignition For Your Safety READ BEFORE...

Page 33: ...s go to the next step 6 Turn fireplace ON using wall switch or remote control 7 If the Fireplace does not light the System will cycle through two trials one minute audible clicking thirty seconds of s...

Page 34: ...the safety information above on this label If you don t smell gas go to the next step 5 Turn switch on the gas control to ON NOTE This unit is equipped with an ignition system that lights the pilot b...

Page 35: ...e Key is provided to index between the features and a Thermostat Key is used to turn On Off or index through Thermostat functions see Figure 32 Additionally a Key Lock feature is provided The Proflame...

Page 36: ...ook at the LCD screen on the Remote Control to verify that a C or F is visible to the right of the Room Temperature display Turn On the Fireplace With the system Off turn the master override switch to...

Page 37: ...the remote control will change to show that the room thermostat is On and the set temperature is now displayed To adjust the set temperature press the Up or Down Arrow Keys until the desired set temp...

Page 38: ...his function use the Mode Key see Figure 32 to index to the accent light icon see Figure 45 Pressing the Up Arrow Key will turn the light on at the lowest setting Continue pressing up to get brighter...

Page 39: ...eys at the same time see Figure 47 To de activate this function press the Mode and Up Keys at the same time Remote Control When the Remote Control batteries are low a Battery Icon will appear on the L...

Page 40: ...he door as shown on Page 25 Handle the door carefully and clean it with non abrasive glass cleaners One of the most effective products is Kel Kem Silicone seals on inner door during initial firing wil...

Page 41: ...will not Light 1 Check and verify all wiring connections as per the wiring diagram 2 Verify the inlet and Manifold Pressurearewithinacceptablelimits Pilot lights but Main burner will not Light and ig...

Page 42: ...RPG001 Piezo Ignitor PIEZO Pilot Tubing RPTA03 Door RDTH42 Replacement Screen RSCH42 SIT IPI Proflame 2 Replacement Parts List HR42DF H42DF HL42DF Log Set N A RLGSH42 N A NG Gas Valve Hi Low RGC3044 L...

Page 43: ...iance 100 000 BTU H 30 KW 12 inches 12 inches M clearance to forced air supply inlet 6 feet 3 feet above air inlet N clearance above paved sidewalk or paved driveway located on public property 7 feet...

Page 44: ...e must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance...

Page 45: ...eight of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than o...

Page 46: ...XG0148 151123 H42DF Residential Gas Fireplace...

Reviews: