Page 11
L-Series DF Gas Fireplace
Part No. XG0180
f i r e f e a t u r e
Installation
Important: Corner Installation is available only for
Top Vent Units.
Figure 20.
Corner installation.
Figure 21.
Flex installation.
(NG Models Only)
2. 45° Corner Installation.
Attach an PEL-90 (90° elbow) directly onto the flue collar, and attach
it to the PEL-45 (45° elbow). Cut the PXT-18 to suit and insert it into
the PEL-45. Slide the fireplace into position, and then connect it to
the exterior termination.
3. Corner Installation — 45° or less.
Use an PTO-3 termination and an PFL-1 or PFL-2 (12" or 24"
compressed length) and a frame, if appropriate.
Flex may be turned to
obtain desired degree of angle required but must not exceed 45°.
Figure 19a.
Extended installation.
PXT-12
PXT-18
PEL-45 Elbow
PEL-90 Elbow
Rear Vent Venting Runs
The L-Series DF Rear Vent
has three possible installations which do
not require vertical lift, all of these installations require that you install
the RHS101 heat shield.
Heat Shield
The heat shield (RHS101) must be used on
all installations straight
through the wall
, at the point where the vent pipe connects to the
termination. With the heat shield, proper vent clearances can be
maintained.
The heat shield is not included with the fireplace.
To install the heat shield, slide one section over the vent pipe on the inside
of the wall opening, with the circular portion
inside the wall cavity
. Screw
the shield in place over the wall opening. Install the second section on
the outside of the wall opening sliding the circular portion into the wall
opening. Refer to Figure 19.
Figure 19.
Heat Shield. Install by sliding over the vent pipe where it
passes through combustible construction.
1. Straight Installation.
The height from the hearth to the center of the termination is 21
3/4". For straight installations use a 12" extension pipe (PXT-12)
with female/female connections. For shorter installations, cut the
PXT-12 to the desired length. Refer to figure 19a.
Ensure that the RHS101 heat shield is installed before attaching
the pipe to the termination.
Note:
For Rear Vent models, maximum horizontal run with no
vertical lift must never exceed 12".