background image

Page 12

L-Series DF Gas Fireplace

Part No. XG0180

f i r e   f e a t u r e

Installation

B. Multi-Elbow Installations

For more difficult installation situations, the L-Series DF Rear Vent may 

be installed with two - 90° elbows and up to 15' of horizontal run. If using 

this installation option, you must adhere to the following guidelines:

  the first 90° elbow must be placed directly on the flue collar

  you must have a minimum vertical lift of 50" (measured from the 

hearth)

  your vent run must fall within the limits set by Figure 22

Before you install any venting, you must determine whether the venting 

run will be acceptable. Unacceptable venting can affect the fireplace's 

combustion.

The Venting Graph

Measure the vertical height from the fireplace hearth to the centre of 

the termination and the horizontal run from the from the fireplace flue 

collar to the wall flange of the termination. Plot on the Venting Graph 

(Fig. 22) with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the 

installation is acceptable.

L38DF

Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 84" and the horizontal 

run to the wall flange of the vent termination is 36", this would be 

an acceptable installation.

Example B: (Acceptable Installation)

If the vertical dimension from the hearth is 94" and the horizontal 

run to the wall flange of the vent termination is 126", this would be 

an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 78" and 

the horizontal run to the wall flange of the vent termination is 108", 

this would NOT be an  acceptable installation.

Figure 22.

 L38DF Multi-Elbow Venting Graph.

L38DF

L42DF

Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 84" and the horizontal 

run to the wall flange of the vent termination is 36", this would be 

an acceptable installation.

Example B: (Acceptable Installation)

If the vertical dimension from the hearth is 90" and the horizontal 

run to the wall flange of the vent termination is 126", this would be 

an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 78" and 

the horizontal run to the wall flange of the vent termination is 108", 

this would NOT be an  acceptable installation.

L52DF

Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 84" and the horizontal 

run to the wall flange of the vent termination is 36", this would be 

an acceptable installation.

Example B: (Acceptable Installation)

If the vertical dimension from the hearth is 108" and the horizontal 

run to the wall flange of the vent termination is 120", this would be 

an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 72" and 

the horizontal run to the wall flange of the vent termination is 84", 

this would NOT be an  acceptable installation.

L42DF

Figure 22b.

 L42DF Multi-Elbow Venting Graph. 

0

12 24 36 48 60 72 84 96 108

132

120

144 156 168 180

Horizontal Run (in.)

Hearth

0

12

24

36

48

60

72

84

96

108

L52DF

Summary of Contents for L38DF series

Page 1: ...phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department For Your Safety Do not store or use gasolineorotherflammable vapors and liquids in the vicin...

Page 2: ...or glass doors Use of any component part not manufactured or approved by Montigo in combination with this Montigo fireplace system Installation other than as instructed in this manual Consult your lo...

Page 3: ...t be installed on a metal or wood panel extending the full width and depth of the appliance Top View Front View Side View Unprotected combustible walls which are perpendicular to the fireplace opening...

Page 4: ...C a manifold pressure of 3 5 W C Propane Gas requires a minimum inlet gas supply pressure of 11 W C a manifold pressure of 10 W C Provision must also be made for a 1 8 N P T plugged tapping and be ac...

Page 5: ...termination where temperatures are highest 2 Attach to the faceplate of the termination using four sheet metal screws Installing Heat Guards over Terminations Installing The Remote Switch The L Serie...

Page 6: ...d fireplace Figure 7b Flue collar installation for Top Vented fireplace Figure 8a Flue cap installation for Rear Vented fireplace Figure 8b Flue collar installation for Rear Vented fireplace L Series...

Page 7: ...acceptable installation Figure 9a L38DF Top Vent Venting Graph L42DF Example A Acceptable Installation If the vertical dimension from the hearth is 84 and the horizontal run to the wall flange of the...

Page 8: ...installation Thesolidsectionscanbeusedin variouscombinationstoobtainthedesiredventrun Thevent run must fall within the limits set by the venting graph Figure 12 Extended Installation using a combinati...

Page 9: ...wo offsets each offset has two 90 bends may be made and shall not exceed total length of 25 of the vertical vent height when measured center to center of piping Example Typical vent installation 20 ve...

Page 10: ...ith 1 offset 1 offset two 90 bends Figure 18 Reducing Vertical Vent from 5 8 to 4 7 Reduced Vertical Installation It is possible to reduce vertical vent runs from 5 8 venting to 4 7 venting Reducedver...

Page 11: ...hield Heat Shield The heat shield RHS101 must be used on all installations straight through the wall at the point where the vent pipe connects to the termination With the heat shield proper vent clear...

Page 12: ...tallation If the vertical dimension from the floor of the fireplace is 78 and the horizontal run to the wall flange of the vent termination is 108 this would not be an acceptable installation Figure 2...

Page 13: ...MTO 3F 3 Length PTO 3 3 Length PTO 3F 3 Length B Stucco Kits MSR Stucco Frame BSR 4 4 Brick Frame BSR 6 6 Brick Frame MOSR Stucco Can MSR Stucco Frame BSR 4 4 Brick Frame BSR 6 6 Brick Frame MOSR Stuc...

Page 14: ...cing materials may be subject to temperatures in excess of 250 F This should be considered when selecting facing materials We recommend careful consideration be given to the effects of elevated mantel...

Page 15: ...d with the same type or its equivalent Figure 27b Wiring schematic for optional fans Figure 27a Wiring for optional fans Removing and Installing the Door Removing the door The door is held in place by...

Page 16: ...ff Gas To Appliance Operation Model L Series DF 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower trim 1 Turn off remote switch 2 Flip down the lower trim...

Page 17: ...try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1...

Page 18: ...ting Instructions To Turn Off Gas To Appliance 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 If the switch on the control module is set to Continuous Pilot Off t...

Page 19: ...ll a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operation Lighting Instructions See pages 16 17...

Page 20: ...r until the bubbling stops completely Figure 34 Pilot Burner Troubleshooting The following is a troubleshooting chart of possible problems PROBLEM CORRECTIVE ACTION Noisy Pilot Flame Locate pilot adju...

Page 21: ...jected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce...

Page 22: ...t minimum in the United States 6 feet 1 8 m minimum in Canada L clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum for...

Page 23: ...Spare Parts L SeriesDF L38DF L42DF NG Gas Valve RGC1006 RGC1006 LP Gas Valve RGC1005 RGC1005 NG Pilot RPA020 RPA020 LP Pilot RPA021 RPA021 Burner NG RBL3801 RBL4201 Burner LPG RBH3802 RBL4202 ROR1151...

Page 24: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0180 033007...

Reviews: