background image

Page 4

L-Series DF Gas Fireplace

Part No. XG0180

f i r e   f e a t u r e

Installation

Use only 

certified Montigo vent components.

 (Use of other parts will void the 

Montigo warranty, and may impede the operation of the fireplace.)
All joints must be secured with a minimum of two screws per joint
Vent terminations must not be recessed in walls or siding
Horizontal runs must be supported by a minimum of two supports per horizontal 
run. A minimum of one screw on each side of support is also required
Flex vent sections may be stretched up to 50% of their total length (eg. a 
24" section may be stretched to 36")
Maximum horizontal run with no vertical rise is 6 feet.
Flex vent sections over 6 feet must fall within the limits set by the venting 
graph and must have a minimum vertical rise of 3 inches per foot of flex.
Solid vent sections may be cut less than half way from the female end
Venting components can be used in any combination of solid/rigid pipe or flex 
pipe and in any orientation (Male connectors can face in any direction)

Vent Terminations

Selecting A Termination Location

Choosing your vent termination location will help to determine whether 

you need to use a top vent or rear vent fireplace. Figure 6a, below, shows 

typical fireplace locations and the venting options they provide.      
For a more detailed diagram of allowed termination locations, see

 Ap-

pendix A.

Cautions: 

Vent terminations can be very hot. If the termination is less 

than 7 feet above a public walkway, it should be fitted with 

a certified Montigo Heat Guard. (Part no. PTKOG).
Do not obstruct, or attempt to conceal, the vent termination.  

These actions will affect the operation of the fireplace, 

and may be hazardous.
In heavy snow areas, take extra care to prevent snow 

buildup from obstructing the vent termination.
Use  Montigo  VSS  Vinyl  Heat  Shield  when  using  on 

applications with vinyl siding to guard against possible 

damage.

Figure 6a.

  

Fireplace locations and vent terminations.

Installing The Gas Line

The gas line must be installed before finishing the L-Series DF Fireplace. 

Natural Gas

 requires a minimum  inlet gas supply  pressure of 5.5" W.C. 

& a manifold pressure of 3.5" W.C. 

Propane Gas

 requires a minimum 

inlet gas supply pressure of 11" W.C. & a manifold pressure of 10" W.C. 

Provision must also be made for a 1/8" N.P.T. plugged tapping and be 

accessible for test gauge connection immediately upstream of the gas 

supply  controls  to  the  appliance.  The  fireplace  gas  connection  and 

the main operating gas valve is located behind the removable trim at 

the bottom of the unit and need only be attached to the gas line  with 

an approved fitting, as required by the 

applicable installation codes.

To access the fireplace gas connection the main burner must be 

removed as shown below in figure 5a.

• Only use gas shut-off valves approved for use by the state, province, 

region, or governing body, in which the appliance is being installed, or 

as required by the applicable installation codes.
• Flexible gas connectors must not exceed 3 feet in length, unless it is 

allowable  within applicable installation codes.

Note:

  After gas line is connected, 

each 

appliance connection

,

 

valve and valve train

 must be checked while under normal 

operating  pressure  with  either  a  liquid  solution,  or  leak 
detection device, to locate any source of leak. Tighten any 
areas  where  bubbling  appears  or  leak  is  detected  until 
bubbling stops completely or leak is no longer detected. 

DO  NOT use a flame of any kind to test for leaks.

Figure 5a.  

Gas line access.

The appliance and its individual shut-off valve must be disconnected 

from the gas supply piping system during any pressure testing of that 

system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by 

closing its individual manual shut-off valve during any pressure testing 

of the gas supply piping system at test pressures equal to or less than 

1/2 psig (3.5 kPa).

Gasline Access
0.875” dia.

2” height
to center

7”

to center

Vent  Installation

This section covers the installation of direct venting and terminations. 

Installation Requirements

L-Series DF

 fireplaces are certified for use with Montigo Standard Series 

(5" / 8")

 venting components.

Minimum 

clearance to combustible construction around the vent pipe 

is 1" 

on all sides, except on horizontal venting where the 

top

 of the pipe 

must have a clearance of at least 2".

Summary of Contents for L38DF series

Page 1: ...phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department For Your Safety Do not store or use gasolineorotherflammable vapors and liquids in the vicin...

Page 2: ...or glass doors Use of any component part not manufactured or approved by Montigo in combination with this Montigo fireplace system Installation other than as instructed in this manual Consult your lo...

Page 3: ...t be installed on a metal or wood panel extending the full width and depth of the appliance Top View Front View Side View Unprotected combustible walls which are perpendicular to the fireplace opening...

Page 4: ...C a manifold pressure of 3 5 W C Propane Gas requires a minimum inlet gas supply pressure of 11 W C a manifold pressure of 10 W C Provision must also be made for a 1 8 N P T plugged tapping and be ac...

Page 5: ...termination where temperatures are highest 2 Attach to the faceplate of the termination using four sheet metal screws Installing Heat Guards over Terminations Installing The Remote Switch The L Serie...

Page 6: ...d fireplace Figure 7b Flue collar installation for Top Vented fireplace Figure 8a Flue cap installation for Rear Vented fireplace Figure 8b Flue collar installation for Rear Vented fireplace L Series...

Page 7: ...acceptable installation Figure 9a L38DF Top Vent Venting Graph L42DF Example A Acceptable Installation If the vertical dimension from the hearth is 84 and the horizontal run to the wall flange of the...

Page 8: ...installation Thesolidsectionscanbeusedin variouscombinationstoobtainthedesiredventrun Thevent run must fall within the limits set by the venting graph Figure 12 Extended Installation using a combinati...

Page 9: ...wo offsets each offset has two 90 bends may be made and shall not exceed total length of 25 of the vertical vent height when measured center to center of piping Example Typical vent installation 20 ve...

Page 10: ...ith 1 offset 1 offset two 90 bends Figure 18 Reducing Vertical Vent from 5 8 to 4 7 Reduced Vertical Installation It is possible to reduce vertical vent runs from 5 8 venting to 4 7 venting Reducedver...

Page 11: ...hield Heat Shield The heat shield RHS101 must be used on all installations straight through the wall at the point where the vent pipe connects to the termination With the heat shield proper vent clear...

Page 12: ...tallation If the vertical dimension from the floor of the fireplace is 78 and the horizontal run to the wall flange of the vent termination is 108 this would not be an acceptable installation Figure 2...

Page 13: ...MTO 3F 3 Length PTO 3 3 Length PTO 3F 3 Length B Stucco Kits MSR Stucco Frame BSR 4 4 Brick Frame BSR 6 6 Brick Frame MOSR Stucco Can MSR Stucco Frame BSR 4 4 Brick Frame BSR 6 6 Brick Frame MOSR Stuc...

Page 14: ...cing materials may be subject to temperatures in excess of 250 F This should be considered when selecting facing materials We recommend careful consideration be given to the effects of elevated mantel...

Page 15: ...d with the same type or its equivalent Figure 27b Wiring schematic for optional fans Figure 27a Wiring for optional fans Removing and Installing the Door Removing the door The door is held in place by...

Page 16: ...ff Gas To Appliance Operation Model L Series DF 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower trim 1 Turn off remote switch 2 Flip down the lower trim...

Page 17: ...try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1...

Page 18: ...ting Instructions To Turn Off Gas To Appliance 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 If the switch on the control module is set to Continuous Pilot Off t...

Page 19: ...ll a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operation Lighting Instructions See pages 16 17...

Page 20: ...r until the bubbling stops completely Figure 34 Pilot Burner Troubleshooting The following is a troubleshooting chart of possible problems PROBLEM CORRECTIVE ACTION Noisy Pilot Flame Locate pilot adju...

Page 21: ...jected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce...

Page 22: ...t minimum in the United States 6 feet 1 8 m minimum in Canada L clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum for...

Page 23: ...Spare Parts L SeriesDF L38DF L42DF NG Gas Valve RGC1006 RGC1006 LP Gas Valve RGC1005 RGC1005 NG Pilot RPA020 RPA020 LP Pilot RPA021 RPA021 Burner NG RBL3801 RBL4201 Burner LPG RBH3802 RBL4202 ROR1151...

Page 24: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0180 033007...

Reviews: