L-Series DF Gas Fireplace
Part No. XG0180
f i r e f e a t u r e
Installation
Figure 13.
Retracted Installation using a combination of solid and flex
venting. Use the vent graph to determine your allowable
run, then select appropriate components.
Figure 14.
Horizontal flex installation with MIN vertical rise.
B. Vertical (Through-The-Roof) Installations
5/8" with option for 4/7" (on applicable models)
Vertical rise >12' can be reduced (on applicable models).
Vertical Terminations must be installed:
•
minimum 2' (two feet) above the highest point where
vent passes through the roof.
•
minimum 6' (six feet) from a mechanical air inlet
•
minimum 18" (1 1/2 feet) from a parapet wall.
Maximum vent height is:
32 feet above fireplace.
35 feet above fireplace.
35 feet above fireplace.
Note: Flame characteristics will change if the maximum vent height
is used.
Minimum clearances 2" from vent to all combustible materials must
be maintained.
•
•
•
L38DF
L42DF
L52DF
A maximum of two offsets
(each offset has two 90° bends)
may be
made and shall not exceed total length of 25% of the vertical vent
height, when measured center to center of piping.
Example:
Typical vent installation.
20' vertical vent
2 - 2' offsets required
25% of 20' = 5' max. offset allowed
This venting configuration meets requirements.
4" / 7" Venting
5" / 8" Venting
A - Termination
MVTK-1
PVTK-1
B - Flex Sections
MFL-1 (12" Section)
MFL-2 (24" Section)
MFL-3 (36" Section)
MFL-4 (48" Section)
PFL-1 (12" Section)
PFL-2 (24" Section)
PFL-3 (36" Section)
PFL-4 (48" Section)
C - Rigid Sections MEXT-1 (12" m/f Section)
MEXT-2 (24" m/f Section)
MEXT-3 (36" m/f Section)
MEXT-4 (48" m/f Section)
PEXT-1 (12" m/f Section)
PEXT-2 (24" m/f Section)
PEXT-3 (36" m/f Section)
PEXT-4 (48" m/f Section)
D - Support Ring
& Plate
MSPXT-8
PSPXT-8
E - Firestop
FS-8
PS-8
F - Roof Flashing MRF-7 (1/12 - 7/12 pt.)
MRF-12 (7/12 - 12/12 pt.)
PRF-7 (1/12 - 7/12 pt.)
PRF-7 (7/12 - 12/12 pt.)
G - Adaptor / Vent
Reducer
PVA5487 (5"/8" to 4"/7")
Figure 15.
Straight, vertical venting
showing required PXT-10 adaptor
(supplied with the PVTK-1 termination).
MEXT/PEXT
MEXT/PEXT
MXT-10/PXT-10
*
For venting MIN 1" clearance to all vertical combustibles,
MIN 2" to all horizontal combustibles.