Page 20
L52DF* Indoor Gas Fireplace
XG0185 - 100511.1
Installation
Installations in the USA
which employ the fans must be grounded in
accordance with local codes or, in the absence of local codes, with the
National Electrical Code,
AnSI/nFPA 70.
For more information see the
Fan Kit Installation guide
included with
the fan kit.
nOTE:
If any of the original wire supplied with the appliance is replaced,
it must be replaced with the same type, or its equivalent.
Figure 20.
Wiring diagram for optional fans.
G
L2-WH
L1-BLK
p g
Quick Connect
lu to motor
Wiring for the
optional
Fan Kit
All
L52DF*
fireplaces may be equipped with optional fan kits for circulating
heat into the living space.
Installations in Canada
which employ the fans must be electrically
grounded in accordance with
CSA C22.1
Canadian Electrical Code
Part 1 and/or Local Codes.
Installing the remote On/Off Wall Switch
The
L52DF
* gas valve may be connected to a wall switch. Do
nOT
connect any external power to the remote switch. The valve will
generate its own power on a millivolt circuit or will draw its power from
an AC Connection inside the fireplace, depending on the model of the
unit. Use only low voltage wire, and
DO nOT
connect any external
power to the remote switch.
Refer to
Figure 18 or 19
for wiring requirements.
nOTE:
The switch location must not exceed 30' from the fireplace.