Page 9
L52DF* Indoor Gas Fireplace
XG0185 - 100511.1
Installation
Section 3: Venting
Figure 9.
Flue cover and collar removal, Top Vented fireplace.
Figure 9a.
Flue cover and collar installation, Rear Vented fireplace.
Section 3-1:
CONVERTING TO REAR VENT
Use the following instructions to convert an
L52DF*
for Rear Vent use:
1. Remove the Rear flue cover and gasket (5" and 8") on the flue
outlet, as shown in
Figure 9.
2. Next, Remove the Top flue collar's (5" and 8") on the flue outlet,
as shown in
Figure 9.
3. Install the (removed) Rear flue cover and gasket material, to the
Top vent outlet. Fasten the cover with included hardware, as
illustrated
Figure 9a
.
4. Install the (5" and 8") collars to the rear vent outlet using the
included hardware, as illustrated
Figure 9a
.
5” Inner Flue Collar
8” Outer Flue Collar
Flue Gasket
Flue Cover Plate
Flue Gasket
Flue Cover Plate
8” Outer Flue Collar
5” Inner Flue Collar
Montigo supplies a variety of direct venting and termination options.
The direct vent termination location MUST be selected such that
it is the highest point in the venting assembly.
It should also be
selected such that it provides the shortest vent run possible. Should
it be impossible to ensure that the termination is the highest point or
should it be impossible to meet the venting guidelines laid out below
please contact your Montigo dealer to discuss power venting options.
nOTES FOR PLAnnIng VEnTIng:
Venting can originate from the unit through the top or
through the rear.
Venting can terminate through the roof or through an
exterior wall
.
Refer to Appendix A - Termination Locations to ensure the
planned termination location is acceptable
.
Once the termination location has been established, refer
to the appropriate section for installation details.
All fireplaces shipped from the factory are
Top vent.