background image

XG0128

Page 12

M38ODV-ST Direct Vented Fireplace

Maintenance

General

„

Have the fireplace installation inspected yearly, including a visual
check of the vent system, the burner and the pilot flame. For your
convenience a 1/8" manifold pressure tap is supplied on the gas
valve for a test gauge connection. See Figure 16.

„

For 

Natural Gas

 this appliance requires a minimum inlet pressure

of 5.5" W.C. and a manifold pressure of 3.5" W.C.

„

For 

Propane Gas 

this appliance requires a minimum inlet pressure

of  11" W.C. and a manifold pressure of 10" W.C.

„

Always keep the fireplace area clear and free of combustible
materials, as well as gasoline and other flammable vapours and
liquids.

„

Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and any gas
control which has been under water.

CAUTION

Fireplace gas control must be in the “OFF” position and pilot
and main burners extinguished when cleaning appliance with
a vacuum.

Glass and logs can get very hot. Handle only when cool.

Cleaning

When the fireplace is first activated, there may be some smoking and a
visible film may be left on the glass. This is a normal condition, and is
the result of burningthe protective coatings on new metal.

„

Glass must be cleaned periodically to remove any film (a normal bi-
product of combustion) which may be visible. Film can easily be
removed by removing the door, as shown on page 9. Handle the
door carefully, and clean it with non-abrasive glass cleaners. One of
the most effective products is Kel Kem.

„

Silicone seals on inner door during initial firing will "off gas", leaving
a visual deposit of a white substance on combustion chamber walls.
This can easily be removed by following the steps described above.

„

Use a vacuum cleaner or whisk broom to keep the control compart-
ment, burner, and firebox free from dust and lint.

„

Logs may be cleaned periodically with a vacuum to remove soot.

WARNING:

Do not attempt to clean glass when hot.

Do not clean glass with abrasive materials as any glass
etching may cause premature glass failure.

Pilot  Burner Adjustment

1.

Locate Pilot Adjustment Screw. 

(See figure 16.)

2.

Turn Adjustment Screw until flame is proper size. 

(See figure 17).

3.

After installing or servicing, leak test with a soap solution with main
burner on. Coat pipe and tubing joints, gasket etc. with soap
solution. Bubbles indicate leaks. Tighten any areas where the
bubbles appear until the bubbling stops completely.

Gas Control Valve

Figure 16. 

Sit Nova 820 

gas valve for M38ODV-ST.

Manifold Pressure
Test Connection

Pilot Adjustment Screw

Inlet
Pressure

Power
Generator

Wall Switch

Figure 17. 

Pilot Burner.

Troubleshooting

Continuous Pilot System Troubleshooting

The following is a troubleshooting chart of possible problems:

PROBLEM

CORRECTIVE ACTION

Noisy Pilot Flame

Locate Pilot Adjustment Screw.  Flame
is decreased by turning adjustment
screw clockwise.

Pilot won’t ignite

Disconnect remote wires and try to
light pilot. If pilot now works, remote
connections are faulty. Check wiring
diagram 

figure 

16.

Main burner will

1. Check wiring 

(see figure 16)

not light

2. Check wall switch for proper
connection.

M38ODV-ST

Summary of Contents for M38ODV-ST

Page 1: ...l your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier For Your Safety ...

Page 2: ...unit employs the optional Fan Kit it must be grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 1987 A manufactured mobile home OEM installation in the United States must conform with the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 or when such a standard is not applicable the Standard for Manufactur...

Page 3: ...r any combustible material other than wood flooring it must be installed on a metal or wood panel extending the full width and depth of the appliance Figure 2a Framing dimensions 38 C C 17 1 8 Ø8 Ø5 For protection against freezing temperatures it is recommended that outer walls of the chase be insulated with a vapour barrier This will reduce the possibility of a cold air convection current on the ...

Page 4: ...alshutoffvalveduringanypressuretestingof the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Installation Vent Installation Thissectioncoverstheinstallationofdirectventingandterminations For a detailed diagram of allowed termination locations see Appendix B InstallationRequirements The M38ODV ST fireplace uses premium venting components with 5 inner dia 8 outer di...

Page 5: ... 12 12 MOSR 1 Frame the termination opening to 12 x 12 2 Fasten the MSR frame to the interior side of the studs using a minimum of 4 screws 3 Insert the termination into the MSR frame as shown here and attach by screwing through the four pilot holes in the termination PTKOG 1 Ensure that the two long mounting brackets are facing the bottom of the termination See inset This will provide more heat p...

Page 6: ...ableinstallation ExampleB AcceptableInstallation If the vertical dimension from the hearth is 66 and the horizontal run to the wall flange of the vent termination is 30 this would be anacceptableinstallation ExampleC UnacceptableInstallation If the vertical dimension from the floor of the fireplace is 48 and the horizontal run to the wall flange of the vent termination is 84 this would NOT be an a...

Page 7: ...llation 48 Hearth Flex Section Termination Exterior Wall 126 30 Max Solid Section w 90 Elbow Heat Shield Hearth Flex Section Solid Section w 90 Elbow Termination Exterior Wall 126 150 max Heat Shield Heat Shields Due to high flue temperatures heat shields are required on all M38ODV ST installations at the point where the venting passes through the wall to connect to the termination Using the heat ...

Page 8: ... effects of elevated mantel temperatures which may be in excess of product design forexample candles plasticorpictures Thiscancause melting deformation discoloration or premature failure of T V and radiocomponents Figure 11b Combustible surrounds Figure 11a Combustible mantles and facings Painting Special care is recommended by the Master Painters and Decorators Association whenpaintingthefireplac...

Page 9: ... slots in the bottom door rail See figure 14 Ensure that a good seal is maintained Figure 14 Installing Glass Door Glass door and frame Door surround Tab B Slot A Magnet Pull bottom of door surround outwards and upwards Machine Screws Door Rail Tabs Installation Figure 12b Completed Installation Figure 12a Log Installation Installing the Logs and Embers Bottom Logs The M38ODV ST is supplied with f...

Page 10: ...ent The M38ODV ST is equipped with an adjustable burner allowing you to raise or lower the flames To adjust the flames locate the black knob marked Hi Lo in the centre of the gas control valve See Figure 15 The front burners are not adjustable To raise the flame height turn the black knob located behind the lower trim counterclockwise To lower the flame height turn clockwise ...

Page 11: ...er s instructions To Turn Off Gas To Appliance Operation Model M38ODV ST 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Replace trim 1 Turn off remote switch 2 Removelowertrim 1 STOP Read the safety information above on this label 2 Removelowertrims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including ...

Page 12: ...fully and clean it with non abrasive glass cleaners One of the most effective products is Kel Kem Silicone seals on inner door during initial firing will off gas leaving a visual deposit of a white substance on combustion chamber walls This can easily be removed by following the steps described above Use a vacuum cleaner or whisk broom to keep the control compart ment burner and firebox free from ...

Page 13: ...Page 13 XG0128 M38ODV ST Direct Vented Fireplace Appendix A Spare Parts Accessories 2 3 ...

Page 14: ...liancesaredesignedtoburngasonly Burningconventionalfireplacefuelssuchaswood coaloranyothersolidfuelwillcausedamagetotheGasAppliance willproduceexcessivetemperaturesandwillresultinafirehazard Limitations On Liability ItisexpresslyagreedandunderstoodthatTheCompaniessoleobligation andpurchaser sexclusiveremedyunderthisWarranty underanyotherwarranty expressed orimplied orincontract tortorotherwise sha...

Page 15: ...Page 15 XG0128 M38ODV ST Direct Vented Fireplace Notes ...

Page 16: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0128 Rev 0102 2005 ...

Reviews: