background image

P/N XG0206

Page 16

M40DV-CR/CL Corner Gas Fireplace

For Your Safety - READ BEFORE LIGHTING:

WARNING:

 

If you do not follow these instructions exactly, a fire or explosion 

may result causing property damage, personal injury or loss of life.

Department.

C.

 Use only your hand to push in or turn the gas control 

knob. Never use tools. If  the knob will not push in or 

turn by hand, don't try to repair it, call a qualified serv

-

ice technician. Force or attempt to repair may result in 

a fire or explosion.

D.

 Do not use this appliance if any part has been under 

water. Immediately call a qualified service technician 

to inspect the appliance and to replace any part of the 

control system, and any gas control which has been 

under water.

A. 

This appliance has a pilot which must be lighted by 

hand. When lighting the pilot, follow these instructions 

exactly.

B. BEFORE LIGHTING

 smell all around the appliance 

area for gas.  Be sure to smell next to the floor be

-

cause some gas is heavier than air and will settle on 

the floor.

 

What To Do If You Smell Gas:

  Do not try to light any appliance.

 

Do not touch any electrical switch; do not use any 

phone in your building.

  Immediately call your gas supplier from a neigh-

bour's phone. Follow the gas supplier's instruc-

tions.

  If you cannot reach your gas supplier, call the Fire 

To Turn Off Gas To Appliance:

Operation -  Model M40DV-CR/CL

3.  Push in gas control knob slightly and turn  

  

clockwise to "Off".  Do not force.

4.  Flip up the lower end louvres.

1.  Turn off remote switch.
2.  Flip down the lower end louvres.

1.

 

STOP!

 

 

Read the safety information above on this 

label.

2.

  Flip down the lower louvres on the end panel of the 

fireplace.

3.

  Push in gas control knob and turn clockwise 

  to 

"OFF."

4.

  Wait five (5) minutes to clear out any gas. Smell for 

gas, including near the floor. If you then smell gas, 

STOP!

 Follow "B" in the safety information above on 

this label. If you don't smell gas, go to the next step.

5.

  Locate pilot burner 

(See illustration at right.)

 and fol-

low steps below.

6.

  Turn knob on gas control counterclockwise  

  to 

"PILOT."

7.

  Push in gas control knob completely and hold. Light 

with Piezo Igniter button. Continue to hold the control 

knob in for about (1) minute after the pilot is lit. Re-

lease the knob and it will pop back up. Pilot should 

remain lit. If it goes out repeat steps 3 through 8.

 

If knob does not pop up when released. Stop and 

immediately call your service technician or gas 

supplier.

 

If the pilot will not stay lit after several tries, turn 

the gas control knob to "OFF" and call your service 

technician or gas supplier.

8.

  Push in gas control knob and turn counterclockwise  

  to "ON."

9.

  Flip up the lower louvres.

10.

Turn on remote switch to ignite fire.

Lighting  Instructions:

NOTE:

 Knob cannot be turned from 

"PILOT" to "OFF" unless knob is 

pushed in slightly.  Do not force.

with Continuous Pilot

Gas Control Knob

(Shown in "Pilot" postion.)

M40DV-CR/CL

Summary of Contents for M40DV-CR

Page 1: ...ead all instructions prior to installation C US Safety Notice Glass doors on gas fireplaces are extremely hot while the fireplaces is on and remain hot even after the fireplace has been turned off Safety screens are available and can reduce the risks of severe burns Please keep children away from the fireplace at all times WARNING Improper installation adjustment alteration service or maintenance ...

Page 2: ... Indicates a hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE Used to address practices not related to personal injury Important Used to address practices not ...

Page 3: ...ny responsibility for the following actions Modification of the fireplace and or components including Direct Vent assembly or glass doors Use of any component part not manufactured or approved by Montigo in combination with this Montigo fireplace system Installation other than as instructed in this manual Consult your local Gas Inspection Branch on installation require ments for factory built gas ...

Page 4: ...ed area shown in Figure 20b For protection against freezing temperatures it is recommended that outer walls of the chase be insulated with a vapour barrier This will reduce the possibility of a cold air convection current on the fireplace Figure 2a Framing dimensions Clearances The M40DV CR CL clearances to combustible materials are Top 8 Rear 1 Closed Side 1 Floor Combustible Mantle 6 Flue Cover ...

Page 5: ...ly piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Installation Vent Installation This section covers the installa...

Page 6: ...crews 12 12 MSR Figure 4b Installing a PT0 3 termination with the MSR frame Figure 4c Installing a PT0 3 termination with the MOSR frame 12 12 12 MOSR Installing Terminations with MOSR Frames 1 Frame the termination opening to 12 x 12 2 Fasten the MSR frame to the interior side of the studs using a minimum of 4 screws 3 Insert the termination into the MSR frame as shown here and attach by screwing...

Page 7: ...Acceptable Installation If the vertical dimension from the hearth is 72 and the horizontal run to the wall flange of the vent termination is 36 this would be an acceptable installation Example C Unacceptable Installation If the vertical dimension from the floor of the fireplace is 48 and the horizontal run to the wall flange of the vent termination is 108 this would not be an acceptable installati...

Page 8: ... Figure 7 Short horizontal installation Figure9 Extendedhorizontalinstallationusingacombinationofrigid and flex venting Figure8 HeatShieldforshorthorizontalinstallation Installbysliding overtheventpipewhereitconnectstothetermination Heat Shields Due to high flue temperatures the heat shield RHS101 must be used on all installations straight through the wall at the point where the vent pipe connects...

Page 9: ... a clearance of at least 2 2 Offset Vertical Installations Amaximumoftwooffsets eachoffsethastwo90 bends maybe made if the length of the offsets does not exceed 25 of the vertical vent height when measured center to center of piping Example Typical vent installation 30 vertical vent 2 2 offsets required 25 of 30 7 1 2 max offset allowed This venting configuration meets requirements Figure10b Verti...

Page 10: ...lange of the vent termination is 120 this would be an acceptable installation Example B Acceptable Installation If the vertical dimension from the hearth is 66 and the horizontal run to the wall flange of the vent termination is 30 this would be an acceptable installation Example C Unacceptable Installation If the vertical dimension from the floor of the fireplace is 48 and the horizontal run to t...

Page 11: ...ve foot chase allow for a maxi mum horizontal run of twelve and one half feet from the centre of the fireplace to outside wall and a minimum of 7 6 when retracted in opposite direction See Figure 14a and 14b D flex sections and E solid sections may be used in conjunction with one another to obtain different possible horizontal length instal lations NOTE Flex section must not exceed maximum horizon...

Page 12: ...e made if the length of the offsets does not exceed 25 of the vertical vent height when measured center to center of piping Example Typical vent installation 30 vertical vent 2 2 offsets required 25 of 30 7 1 2 max offset allowed This venting configuration meets requirements A Termination PVTK 1 B Flex sections PFL 1 12 section PFL 2 24 section PFL 3 36 section PFL 4 48 section C Solid sections PE...

Page 13: ...peratures over the mantel will rise above normal room temperature and walls above fireplace may be hot to touch We recommend careful consideration be given to the effects of elevated mantel temperatures which may be in excess of product design for example candles plastic or pictures This can cause melt ing deformation discoloration or premature failure of T V and radio components Painting Figure 2...

Page 14: ...ide panel by sliding it out and away from the back of the fireplace Refer to figure 22b Removing the Doors Figure 22a Removing the louvre assemblies Figure 22b Removing the side panel To remove the inner doors simply unscrew the eight 8 machine screws on the top and bottom of the door See figure 22c Door Installation To re install the doors align the door with the screw holes and re fasten with al...

Page 15: ...Place logs C and D into their mating positions on the large logs as shown in Figure 16a below Log E is mounted on top of logs C and D as shown in Figure 23b Warning If logs are not placed properly excessive sooting will result Installing the Ember Material The ember material is supplied in two packages Place the material evenly along both ember burner tubes next to logs A and B Refer to figure 23b...

Page 16: ...Operation Model M40DV CR CL 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower end louvres 1 Turn off remote switch 2 Flip down the lower end louvres 1 STOP Read the safety information above on this label 2 Flip down the lower louvres on the end panel of the fireplace 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out...

Page 17: ...oor because some gas is heavier than air and will settle on the floor What To Do If You Smell Gas Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Flip down the lower end louvres Gas Inlet Gas Control Switch Shown in...

Page 18: ...ou Smell Gas Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Flip down the lower trims 3 Turn the incoming gas control valve to Off 4 Flip UP the lower trims 1 STOP Read the safety information above on this label 2 ...

Page 19: ...ng the door as shown on page 9 Handle the door carefully and clean it with an approved glass cleaner One of the most effective products is Kel Kem Silicone seals on inner door during initial firing will off gas leaving a visual deposit of a white substance on combustion chamber walls This can easily be removed by following the steps described below Use a vacuum cleaner or soft bristle brush to kee...

Page 20: ...l valve Flame is decreased by turning adjustment screw clockwise Pilot won t ignite Disconnect remote wires and try to light pilot If pilot now works remote connections are faulty Check wiring diagram figure 17 Main burner will 1 Check wiring see figure 17 not light 2 Check wall switch for proper con nection 3 Check pilot burner If extinguished a Allow fireplace to cool then try to relight b If co...

Page 21: ...rious safety hazards may result in the denial of certification by recognized national safety agencies and could be in violation of local building codes This warranty does not cover any damages occurring from the use of any components not manufactured or supplied by The Companies 2 The Montigo Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning con...

Page 22: ...m in the United States 6 feet 1 8 m minimum in Canada L clearance to nonmechanical air supply inlet to building or the combus tion air inlet to any other appliance 16 inches 41 cm minimum for appliances 100 000 BTU H 30kW M clearance to mechanical air supply inlet 6 feet 1 8 m minimum N clearance above paved sidewalk or a paved driveway located on public property 7 feet 2 1 m minimum P clearance u...

Page 23: ... in a manufactured or mobile home ThestandardM40DV CR CLortheM40DV CR CL Iequippedwith HotSurfaceIgnition HSI arenotapprovedforuseinmobileor manufactured homes The M40DV CR CL MH is rated for Natural Gas at 30 000 BTU H 8 79 Kilowatts max input and 24 000 BTU H 7 03 Kilowatts min input Propane at 30 000 BTU H 8 79 Kilowatts max input and 24 000 BTU H 7 03 Kilowatts min input Conversion Kits The M4...

Page 24: ...y in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection...

Page 25: ...Page 25 P N XG0206 M40DV CR CL Corner Gas Fireplace Notes ...

Page 26: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0206 092508 ...

Reviews: