Page 19
P38DF* Indoor Gas Fireplace
XG0193 -103111.1
Installation
Section 6: Finishing
Horizontal Run (in.)
Ve
rtical Height (in.)
Combustible construction
allowed in shaded area
Combustible facing material
Combustible header
Non-combustible header
Top of fireplace
Non-combustible facing
Figure 22.
Combustible mantels and facings.
WARNING!
When covering the upper metal portion of the fireplace, up to 4" (
as
shown,
Fig.22
) with a non-combustible material
Please note
: The
decorative facing materials may be subject to temperatures in excess
of 250° F. This should be considered when selecting facing materials.
Finishing Around the Fireplace
Non-combustible mantels and mouldings may be safely installed over
the top and on the front of the fireplace provided that they do not project
beyond shaded area shown in
Figure 22.
Fireplace Facing
When sizing the finish material for your fireplace, it is important to
remember the following: THE OPENING MUST NOT BE OBSTRUCTED
IN ANY WAY - to do so restricts the air supply for the control compartments
and heat exchanger it also prevents access for servicing controls.
The face of the fireplace may be painted to match the room decor,
provided you use a heat-resistant paint. Decorative facing must not
extend past the fireplace opening at all, because it will interfere with
the access to retainers for removal of glass door.
Glass doors on gas fireplaces are
extremely hot
while the fireplace is on and
remain hot even after the fireplace has been turned off. Safety screens are
available and can reduce the risks of severe burns. Please keep children away
from the fireplace at all times.
CAUTION
Do not use ammonia based or abrasive cleaners on the glass, they will permanently
etch the surface. Use an approved gas fireplace glass cleaner such as Kel-Kem or
White off.
NOTICE
4”Non-Combustible
Facing Material
Non-combustible Header
Drywall/Sheetrock
4”
3”
Figure 23.
Combustible surrounds.
We recommend careful consideration be given to the effects of elevated mantel
temperatures which may be in excess of product design, for example: candles, plastic
or pictures. This can cause melting, deformation, discoloration or premature failure of
T.V. radio, and other electronic components.
CAUTION
Mantels & Surrounds
nOTE:
National Canadian Gas Association mantel test requirements
are for fire hazard prevention to combustible materials.
New technology, to meet consumer and government demands for the
wise use of energy, has prompted us to manufacture many models of
fireplaces which are hot, fuel and energy efficient.
Please be aware; temperatures over the mantel will rise above normal
room temperature and walls above fireplace may be hot to touch.
Side wall clearances are 3". Combustible surrounds may be installed
with 3" clearance to the side of the fireplace as shown in
Figure 23
.