P52DF* Indoor Gas Fireplace
XG0196 - 150204.3
Installation
Section 3-5: Heat Shields
Installing a Wall Mounted RHS 102 Heat shield
The RHS102 Heat Shield (
Figure 16 and 16a
)
MUST
be
used in all cases where the venting passes through a wall.
To install the RHS 102, frame an opening in combustible
construction. Slide the Heat shield in place over the vent
pipe which attaches to the fireplace. After the fireplace and
vent pipe has been installed, clearances should match the
dimensions in
Figure 14
.
Figure 14.
RHS102 Installation.
Installing a Wall Mounted RHS 104 Heat shield.
The RHS104 Heat shield
MUST
be used in conjunction with
the RTO-4 Termination (
Figure 16 and 16a
).
To install the RHS104, Slide the Inner Section over the vent
pipe.
From the outside slide the RHS104 outer section on
(see
Figure 15a)
. To complete the installation fasten the Heat
Shield Outer Section & Termination frame to the structure.
Figure 16.
RHS 102 & RHS 104 Installation. (Minimum
requirements).
Combustible
framin
g
Termination
Drywall / sheetrock
Outer Section
Vent pip
e
RHS 104 Heat Shiel
d
RHS 104 Heat Shield
Inner Section
Figure 16a.
RHS 102 & RHS 104 Installation. (Minimum
requirements).
Figure 15a.
RHS104 Installation.
RHS104 Heat
Shield
27” Min.
RTO-4Terminati
on
36” Min
RHS 102
Heat
Sheild
60 Min”
5”/10”
Figure 14a.
RHS102 Installation.
RHS 104 Heat Shiel
d
RTO - 4 T
erminatio
n
27” Min
RHS 102
Heat Shiel
d
36” Min
60” Min
5”/10”
Figure 15.
RHS104 Installation.
Combustible
framin
g
Drywall / sheetrock
Outer Section
Vent pip
e
RHS 102 Heat Shiel
d
RHS 102 Heat Shield
Inner Section
Outer Shield 10 5/8”
1/4” Min. Both sides Typical
1/4” Min.
1/4” Min .
Combustible Framing
Inner Shield 11 1/2”
Outer Shield 10 5/8”
1 1/4”” Min. Both sides Typical
1 1/4” Min.
1 1/4” Min.
Combustible Framing
Inner Shield 11 1/2”
Note:
Images are shown without screens for clarity
purposes. However, your fireplace should not be operated
without proper installation of screens.