background image

R324-STIO Indoor Outdoor Ventless Gas Fireplace

Page 11

XG0775 - 150204.1

Installation

Section 4: Installing the Gas Line 

Section 5: Electrical Connection 

Figure6.

Gas Inlet Supply location,

 

(left-hand side of fireplace facing indoor face).

Fuel Consumption

Verify that your fireplace is compatible with your available gas type.  (Natural Gas 

or Propane shown by "N" or "L" in your model number
If gas type is not compatible, contact your local Montigo representative to purchase 

a conversion kit.

Conversion kits must be installed by a qualified service technician.

Gas Pressure

Optimum appliance performance requires proper input pressures.
Gas line sizing requirements will be determined in ANSI 223.1 National Fuel Gas 

Code in the USA and CAN/CGA B149 in Canada.

Pressure requirements:

The manifold outlet pressure is set from the factory to the appropriate pressure but 

should be verified.
To check pressures, control valves have a provision to remove a 1/8” N.PT. plug to 

be fitted with a hose barb.
Montigo requires a service shut off valve be located in an accessible location to 

isolate the gas supply.

Only install gas shut-off valves approved for use by the state, province, or other 

governing body in which the fireplace is being installed.

GAS CONNECTION

The gas connection is located on the left side of the fireplace looking at the indoor 

face of the unit.
Connect this line to a service shut of valve as per local code.

Make sure that the gas line as well as the shut of valve will be rated for 75,000 BTU

Purge all air out of the gas line prior to start up.

Flexible gas connectors must not exceed 3 feet in length, unless allowable within 

local regulations.

Connect incoming gas line to the 1/2"or 3/8" gas inlet port.

Check appliance connection, valve and valve train under normal operating pressure 

with a commercially available leak check solution.

DONOTUSEAFLAMEOFANYKINDTOTESTFORLEAKS.

Pressure Requirements

Gas Pressure

Natural Gas

Propane

Minimum Inlet Pressure

5.5" W.C.

11" W.C.

Manifold Presure

3.5" W.C.

10" W.C.

After gas line is connected, each appliance connection, valve and valve train MUST 

be checked while under normal operating pressure with either a Liquid Solution, or 

Leak Detection Device, to locate any source of leak. Tighten any areas where 

bubbling appears or a leak is detected until bubbling stops completely or leak is no 

longer detected. DO  NOT use a flame of any kind to test for leaks. A fire or explosion 

will occur, causing serious injusy, property damage or death.

DANGER

When pressure testing the fireplace, Gas line, and input system follow the appropriate 

local codes or your area. DO NOT connect the fireplace to pressures in excess of 

1/2lb. This will damage the gas control valve.

NOTICE

We recommend careful consideration be given to the effects of elevated mantel 

temperatures which may be in excess of product design, for example: candles, plastic 

or pictures.  This can cause melting, deformation, discoloration or premature failure of 

T.V. radio, and other electronic components.

CAUTION

When covering the upper metal portion of the fireplace, (as shown, Fig.16) 

with a non-combustible material, Please 

Note:

 The decorative facing 

materials may be subject to temperatures in excess of 250° F.  This should 

be considered when selecting facing materials.

CAUTION

• 

  Connect 115 Volt 12 Amp power supply to the 

connection box located on the right side bottom corner of 

this fireplace.

• 

  There is 25 Feet of low voltage wire coiled up on the 

same side of this fireplace.

• 

  Run this low voltage wire to an on / off switch at a 

location of your choice.

• 

 If this wire is inadequate in length you may replace this 

wire with any Number 18 gage solid or stranded wire in 

any length.

• 

Do not splice these wires. Run a new wire directly from 

the control board to the switch location.

• 

Caution:  Do not apply any power to these two wires.

Summary of Contents for R324-ST

Page 1: ...zard Danger of suffocation High voltage Toxic Flammable materials Corrosive Fork lift trucks Danger overhead crane Explosion risk Oxidising Danger of death Biohazard Laser Radiation Danger of entrapment Hot surface General Warning Blank Gas bottles Watch for falling objects Electricity Danger for cutter Entrapment hazard Battery hazard Rotating parts Low temperature Strong magnetic field Optical r...

Page 2: ...on 2 Framing 7 Section 3 Finishing 8 Section 4 Installing the Gas Line 11 Section 5 Electrical Connection 11 Section 6 a Removing Installing the Interior Screen and Door 12 Removing the Screen and Door 12 Section 6 b Removing Installing the Outside Screen and Door 13 Section 7 Installing the Firestones 14 Firestones 14 Optional River Rocks 14 Section 8 Start up Sequence 15 Section 9 Cleaning and M...

Page 3: ...l installation and service work should be performed by a qualified or licensed installer plumber or gas fitter as certified by the state province region or governing body where the fireplace is being installed This installation operation and maintenance manual is applicable to the models described below Refer to your rating plate to verify included options Warranty and Installation Information See...

Page 4: ...rrier removed for servicing an appliance must be replaced prior to operating the appliance Pre Installation Checklist Determine the desired install location of your fireplace See Section 1 Dimensions on Page 5 and refer to the Framing Section 2 for details Theelectricalpanelislocatedonthelowerrightsidewhenfacingtheinterior side of the fireplace Montigosupplies20 oflowvoltagewire whichcanbesplicedt...

Page 5: ...STIO Indoor Outdoor Ventless Gas Fireplace Page 5 XG0775 150204 1 Installation Rating Plate Sample Figure A Rating Plate for R324 ST LBL1207D V5 0 R P VIEW_HSI_WITH SCREEN _DEC 11 2014 Teklynx LabelView Demo ...

Page 6: ...ration mustbeconsideredwhen selecting the fireplace location Try to select a location that does not interfere with room traffic has adequate ventilation and offers an accessible pathway for Power Vent installation The fireplace dimensions are shown below Figure 1 Unit Dimensions 48 1219 39 1 8 994 39 3 8 999 35 3 4 906 23 3 8 594 23 1 4 590 25 1 8 638 26 3 4 679 21 5 8 549 27 1 2 699 14 1 2 369 9 ...

Page 7: ...tends beyond both interior and exterior wall Note For all positions outside face must be positioned on OPEN non obstructed patio Outdoor Indoor 10 Min from grade 10 Min from grade 10 Min from grade X Y Unit must be 10 above grade on exterior side MODEL Sides Floor Indoor Floor Outdoor Top R324 STIO 1 2 0 10 3 Step 2 You may position the unit in framed opening to be flush to the interior wall Fig 3...

Page 8: ...intotheintendedlocationfromtheoutsideof thebuildinguntiltheflashingisflushwiththebuildingexterior SeeFig 4a Nail the flashing to the exterior sheathing of the building STEP 5 Cover the flashing with approved waterproofing membrane brought to the 1 2 edge of the unit See Fig 4b STEP 6 Install steel stud construction or other non combustible to create1 2 clearanceonsidesand3 clearanceontopbeforeinst...

Page 9: ...2 clearance all sides Figure 4c Install Steel studs for 1 2 clearance on sides and top Figure 4d Clearance above grade Non combustible Facing Combustible side IF 1 2 clearance is maintained Min 10 above grade 10 254 Minimum from Grade 1 2 13 3 73 5 Clearance to Combustible Non Combustible Flashing Combustible Header Combustible Sheathing Non Combustible Sheathing Indoor Side Outdoor Side Figure 4e...

Page 10: ... 250 degrees Fahrenheit STEP3 Installnon combustiblefacingmaterialsuchascementboard or tile on the front inside face of the unit See Fig 4b STEP 4 Install drywall or other finishing material Figure 5 Interior framing Figure 5b Finished interior installation Figure 5a Interior face of unit non combustible Min Clearance 1 2 to combustibles Min Clearance 3 to combustible from top of unit from sides o...

Page 11: ...vailable leak check solution DO NOT USE A FLAME OF ANY KIND TO TEST FOR LEAKS Pressure Requirements Gas Pressure Natural Gas Propane Minimum Inlet Pressure 5 5 W C 11 W C Manifold Presure 3 5 W C 10 W C After gas line is connected each appliance connection valve and valve train MUST be checked while under normal operating pressure with either a Liquid Solution or Leak Detection Device to locate an...

Page 12: ...ttom fireplace door frame Figure 7c NOTE Read ALL the instructions supplied with the tool and follow the associated operating procedures Step 4 Still holding the Glass Removal Tool firmly remove the door outward and away from the Fireplace Figure 7d Step5 Placethedoorinasafelocationwhile maintenance cleaning or other operation are in progress NOTE Read ALL the instructions supplied with the tool a...

Page 13: ...d out Figure 7f Lifting screen frame off fireplace Step 3 Removethescrewsthatsecurethescreentotheunit Makesuretoholdthe screensecurleyasyouremovethelastfewscrewstopreventthescreenfromfalling Figure 7g Removing screws that secure screen Figure 7h Removing screws that secure door REVISIONS REV DESCRIPTION DATE CHANGED BY 1 16 DWG NO WEIGHT R3 Finish MATERIAL DIMENSIONS ARE IN INCHES TOLERANCES FRACT...

Page 14: ...the glass door or with a broken glass door NOTICE TheC ViewResidentialR324STIOfireplacehastheoptionofinstallingthesupplied glass Firestones other colored glass media or cultured rocks Firestones The C View Residential R324 STIO fireplace is supplied with Glass Firestones To installtheFirestonesremovetheDoorandtrimasshowninthepreviousInstruction Followtheseinstructionstoensureallpartsareremovedorre...

Page 15: ...ndoor Outdoor Ventless Gas Fireplace Page 15 XG0775 150204 1 Operation Section 8 Start up Sequence TO TURN OFF GAS TO APPLIANCE LIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING Heat Sensor Conmustion Air ...

Page 16: ...ormal condition and is the result of burning of protective coatings on new metal Glass must be cleaned periodically to remove any film which is a normal by product of combustion which may be visible Film can easily be removed by removing the door as shown on Page 11 Handle the door carefully and clean it with non abrasive glass cleaners One of the most effective products is Kel Kem Use a vacuum cl...

Page 17: ...Gas Valve Flue Gas Switch R3 R1 R2 R1 Wht Grn Blk Wht Brn Blk Blu Wht BLK BLK Wht Wht Red Red Q R T S U V W X Wht Blk Blu Blu 3 1 Brown Blu Red Blu Blk Black Black White Blu Grey X W V U T S R Q WS NC R3 R2 24V 110V Grey PV Blu Brn Red 0 2in WC Post Purge Timer Prepurge Timer Main Power NO Flue Temp Limit Switch 300 F C Grn Fuse 5A 25OVAC ...

Page 18: ...p 4 Lift control panel cover out to expose controls Figure 11e Exposing controls under control panel Figure 11f Control box controls Figure 11g Control box controls Vacuum Switch Fuse Fan Speed Controller Prepurge Timer Transformer Vacuum Switch Relay Power Relay Thermal Switch Relay Capacitor Gas Valve Figure 11b Note placement of rating plate Figure 11c Removing screws from each side of the cont...

Page 19: ... RPA003 30 LP Pilot Assembly RPA004 30 Power Vent Control Box RESCB2 Replacement Screen RSCR320 Fuse AGC 5Amp EC1122 275 deg F Manual Reset Switch EC1073 Vacuum Switch REC1226 Outdoor Glass for fireplace without screen RD324ST01 Outdoor Glass for fireplace with screen RDT324OD Indoor Glass RD324ST02 Outdoor Screen RSCR324OD Indoor Screen RSCR324ID Replacement Parts ...

Page 20: ...d by The Companies 2 The Montigo Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and understood that The Companies sol...

Page 21: ...inimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall no...

Page 22: ...XG0775 150204 1 R324 ST Indoor Outdoor Gas Fireplace USA ...

Reviews: