background image

R324-STIOIndoorOutdoorVentlessGasFireplace

Page 21

XG0775 - 150204.1

Appendix

Appendix B: State of Massachusetts

Amendment

(GasFireplace/EquipmentsoldintheStateofMassachusetts)

5.08:ModificationstoNFPA-54,Chapter10

(1)ReviseNFPA-54section10.5.4.2

 

by adding a second exception as follows:

Existing chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manually reset device 

that will automatically shut off the gas to the burner in the event of a sustained back-draft

.

(2)Revise10.8.3

 by 

adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, 

including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in 

the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 

1.INSTALLATIONOFCARBONMONOXIDEDETECTORS.

 

At the time of installation of the side wall horizontal vented gas fueled equip-

ment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor 

level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon 

monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled 

equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon 

monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with 

alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days 

to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm 

shall be installed.

2.APPROVEDCARBONMONOXIDEDETECTORS.

 

Each carbon monoxide detector as required in accordance with the above provisions 

shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified. 

3.SIGNAGE.

 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet 

above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print 

size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

4.INSPECTION.

 The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, 

upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. 

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 

 

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the 

Board; and 

 

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or struc-

ture used in whole or in part for residential purposes.  

 

(c)MANUFACTURERREQUIREMENTS-GASEQUIPMENTVENTINGSYSTEMPROVIDED

. When the manufacturer of Product 

Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions 

provided by the manufacturer for installation of the equipment and the venting system shall include:

 

1. Detailed instructions for the installation of the venting system design or the venting system components; and

 

2. A complete parts list for the venting system design or venting system. 

 

(d)MANUFACTURERREQUIREMENTS-GASEQUIPMENTVENTINGSYSTEMNOTPROVIDED

. When the manufacturer of a Prod

-

uct Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, 

the following requirements shall be satisfied by the manufacturer:

 

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and 

 

2.The“specialventingsystems”

 shall be Product Approved by the Board, and the instructions for that system shall include a parts list and 

detailed installation instructions. 

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for 

venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

(3)AfterNFPA-54section10.10.4.2

 add a new section 10.10.4.3 as follows:

When more than four gas appliances are to be vented through a common gas vent or common horizontal vent manifold, a plan of the proposed vent installation 

shall be submitted to the Inspector and the serving gas supplier for review and approval.

Extraction from: Massachusets Rules and Regulations

5.00:AmendmentsTo2002EditionOfANSIZ223.1-NFPA-54

Summary of Contents for R324-ST

Page 1: ...zard Danger of suffocation High voltage Toxic Flammable materials Corrosive Fork lift trucks Danger overhead crane Explosion risk Oxidising Danger of death Biohazard Laser Radiation Danger of entrapment Hot surface General Warning Blank Gas bottles Watch for falling objects Electricity Danger for cutter Entrapment hazard Battery hazard Rotating parts Low temperature Strong magnetic field Optical r...

Page 2: ...on 2 Framing 7 Section 3 Finishing 8 Section 4 Installing the Gas Line 11 Section 5 Electrical Connection 11 Section 6 a Removing Installing the Interior Screen and Door 12 Removing the Screen and Door 12 Section 6 b Removing Installing the Outside Screen and Door 13 Section 7 Installing the Firestones 14 Firestones 14 Optional River Rocks 14 Section 8 Start up Sequence 15 Section 9 Cleaning and M...

Page 3: ...l installation and service work should be performed by a qualified or licensed installer plumber or gas fitter as certified by the state province region or governing body where the fireplace is being installed This installation operation and maintenance manual is applicable to the models described below Refer to your rating plate to verify included options Warranty and Installation Information See...

Page 4: ...rrier removed for servicing an appliance must be replaced prior to operating the appliance Pre Installation Checklist Determine the desired install location of your fireplace See Section 1 Dimensions on Page 5 and refer to the Framing Section 2 for details Theelectricalpanelislocatedonthelowerrightsidewhenfacingtheinterior side of the fireplace Montigosupplies20 oflowvoltagewire whichcanbesplicedt...

Page 5: ...STIO Indoor Outdoor Ventless Gas Fireplace Page 5 XG0775 150204 1 Installation Rating Plate Sample Figure A Rating Plate for R324 ST LBL1207D V5 0 R P VIEW_HSI_WITH SCREEN _DEC 11 2014 Teklynx LabelView Demo ...

Page 6: ...ration mustbeconsideredwhen selecting the fireplace location Try to select a location that does not interfere with room traffic has adequate ventilation and offers an accessible pathway for Power Vent installation The fireplace dimensions are shown below Figure 1 Unit Dimensions 48 1219 39 1 8 994 39 3 8 999 35 3 4 906 23 3 8 594 23 1 4 590 25 1 8 638 26 3 4 679 21 5 8 549 27 1 2 699 14 1 2 369 9 ...

Page 7: ...tends beyond both interior and exterior wall Note For all positions outside face must be positioned on OPEN non obstructed patio Outdoor Indoor 10 Min from grade 10 Min from grade 10 Min from grade X Y Unit must be 10 above grade on exterior side MODEL Sides Floor Indoor Floor Outdoor Top R324 STIO 1 2 0 10 3 Step 2 You may position the unit in framed opening to be flush to the interior wall Fig 3...

Page 8: ...intotheintendedlocationfromtheoutsideof thebuildinguntiltheflashingisflushwiththebuildingexterior SeeFig 4a Nail the flashing to the exterior sheathing of the building STEP 5 Cover the flashing with approved waterproofing membrane brought to the 1 2 edge of the unit See Fig 4b STEP 6 Install steel stud construction or other non combustible to create1 2 clearanceonsidesand3 clearanceontopbeforeinst...

Page 9: ...2 clearance all sides Figure 4c Install Steel studs for 1 2 clearance on sides and top Figure 4d Clearance above grade Non combustible Facing Combustible side IF 1 2 clearance is maintained Min 10 above grade 10 254 Minimum from Grade 1 2 13 3 73 5 Clearance to Combustible Non Combustible Flashing Combustible Header Combustible Sheathing Non Combustible Sheathing Indoor Side Outdoor Side Figure 4e...

Page 10: ... 250 degrees Fahrenheit STEP3 Installnon combustiblefacingmaterialsuchascementboard or tile on the front inside face of the unit See Fig 4b STEP 4 Install drywall or other finishing material Figure 5 Interior framing Figure 5b Finished interior installation Figure 5a Interior face of unit non combustible Min Clearance 1 2 to combustibles Min Clearance 3 to combustible from top of unit from sides o...

Page 11: ...vailable leak check solution DO NOT USE A FLAME OF ANY KIND TO TEST FOR LEAKS Pressure Requirements Gas Pressure Natural Gas Propane Minimum Inlet Pressure 5 5 W C 11 W C Manifold Presure 3 5 W C 10 W C After gas line is connected each appliance connection valve and valve train MUST be checked while under normal operating pressure with either a Liquid Solution or Leak Detection Device to locate an...

Page 12: ...ttom fireplace door frame Figure 7c NOTE Read ALL the instructions supplied with the tool and follow the associated operating procedures Step 4 Still holding the Glass Removal Tool firmly remove the door outward and away from the Fireplace Figure 7d Step5 Placethedoorinasafelocationwhile maintenance cleaning or other operation are in progress NOTE Read ALL the instructions supplied with the tool a...

Page 13: ...d out Figure 7f Lifting screen frame off fireplace Step 3 Removethescrewsthatsecurethescreentotheunit Makesuretoholdthe screensecurleyasyouremovethelastfewscrewstopreventthescreenfromfalling Figure 7g Removing screws that secure screen Figure 7h Removing screws that secure door REVISIONS REV DESCRIPTION DATE CHANGED BY 1 16 DWG NO WEIGHT R3 Finish MATERIAL DIMENSIONS ARE IN INCHES TOLERANCES FRACT...

Page 14: ...the glass door or with a broken glass door NOTICE TheC ViewResidentialR324STIOfireplacehastheoptionofinstallingthesupplied glass Firestones other colored glass media or cultured rocks Firestones The C View Residential R324 STIO fireplace is supplied with Glass Firestones To installtheFirestonesremovetheDoorandtrimasshowninthepreviousInstruction Followtheseinstructionstoensureallpartsareremovedorre...

Page 15: ...ndoor Outdoor Ventless Gas Fireplace Page 15 XG0775 150204 1 Operation Section 8 Start up Sequence TO TURN OFF GAS TO APPLIANCE LIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING Heat Sensor Conmustion Air ...

Page 16: ...ormal condition and is the result of burning of protective coatings on new metal Glass must be cleaned periodically to remove any film which is a normal by product of combustion which may be visible Film can easily be removed by removing the door as shown on Page 11 Handle the door carefully and clean it with non abrasive glass cleaners One of the most effective products is Kel Kem Use a vacuum cl...

Page 17: ...Gas Valve Flue Gas Switch R3 R1 R2 R1 Wht Grn Blk Wht Brn Blk Blu Wht BLK BLK Wht Wht Red Red Q R T S U V W X Wht Blk Blu Blu 3 1 Brown Blu Red Blu Blk Black Black White Blu Grey X W V U T S R Q WS NC R3 R2 24V 110V Grey PV Blu Brn Red 0 2in WC Post Purge Timer Prepurge Timer Main Power NO Flue Temp Limit Switch 300 F C Grn Fuse 5A 25OVAC ...

Page 18: ...p 4 Lift control panel cover out to expose controls Figure 11e Exposing controls under control panel Figure 11f Control box controls Figure 11g Control box controls Vacuum Switch Fuse Fan Speed Controller Prepurge Timer Transformer Vacuum Switch Relay Power Relay Thermal Switch Relay Capacitor Gas Valve Figure 11b Note placement of rating plate Figure 11c Removing screws from each side of the cont...

Page 19: ... RPA003 30 LP Pilot Assembly RPA004 30 Power Vent Control Box RESCB2 Replacement Screen RSCR320 Fuse AGC 5Amp EC1122 275 deg F Manual Reset Switch EC1073 Vacuum Switch REC1226 Outdoor Glass for fireplace without screen RD324ST01 Outdoor Glass for fireplace with screen RDT324OD Indoor Glass RD324ST02 Outdoor Screen RSCR324OD Indoor Screen RSCR324ID Replacement Parts ...

Page 20: ...d by The Companies 2 The Montigo Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and understood that The Companies sol...

Page 21: ...inimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall no...

Page 22: ...XG0775 150204 1 R324 ST Indoor Outdoor Gas Fireplace USA ...

Reviews: