Moog ACV with CANopen bus interface
7 Servo valve functions
Pressure controller
B99224-DV018-D-211, Rev. A, October 2018
171
7.5.8.1 Object 0x2350: Active parameter set number
This parameter is to select the active parameter set of the pressure controller.
The number of this parameter set is identical with the sub-index of the objects which are used for the pressure
controller. If, for example, the <ActiveParameterSetNumber> (0x2350) is set to 3 all pressure controller ob-
jects within the set use the parameter with the sub-index 3 as active parameter.
7.5.9 Demand pressure ramp function
The one-quadrant ramp function limits the rate the demand pressure value rises or falls. The slope will be de-
fined by the rising time <RampSlope> (0x2303[N]). The ramp is only active, if the parameter is greater zero.
Figure 80: Demand pressure ramp function
ValvePressureControl
Index
Sub-index
Parameter name
Data type
Access
Per-
sistence
Value
range
Default
0x2350
0
ActiveParameterSetNumber
INT8
rw
Y
1…16
1
t
input
+ 100 %
- 100 %
t
output
+ 100 %
- 100 %
<RampSlope>
(0x2303[N])
Pressure
ramp
input
output
<RampSlope>
(0x2303[N])