Moog ACV with CANopen bus interface
7 Servo valve functions
Data logger
B99224-DV018-D-211, Rev. A, October 2018
256
7.17.3.1 Object 0x3182: Divider
This parameter contains an integer number to reduce the sampling frequency.
Value description
7.17.4 Trigger settings
The trigger settings can be set like on a real oscilloscope.
• Trigger parameter (integer parameter for the trigger).
• Trigger type (FREE, NORMAL, SINGLE).
• Trigger level or bitmask (trigger level).
• Trigger coupling (AC, DC, BITMASK).
• Trigger slope (rising, falling, both).
• Trigger position (pre trigger, post trigger).
7.17.4.1 Object 0x3189: Trigger parameter
The <TriggerParameter> (0x3189) defines the parameter which is used as trigger signal.
Value description
This pointer contains a combination of index, sub-index and length of the parameter to be used. It may only
refer to parameters with a bit length of 0x10.
The default value is 0x63100110, which refers to the <SplDemandValue> (0x6310), sub-index 0x01 with a
length of 16 bit (16=0x10).
DataLogger
Index
Sub-index
Parameter name
Data type
Access
Persistence
Value range
Default
0x3182
0
Divider
UINT16
rw
Y
1…65535
1
<Divider>
Description
1
10000 samples per second (10 kHz).
2…65534
10000/2…10000/65534 samples per second.
65535
10000/65535 = 0.1526 samples per second.
Table 105: Possible values of parameter <Divider> (0x3182)
DataLogger
Index
Sub-index
Parameter name
Data type
Access
Persistence
Value range
Default
0x3189
0
TriggerParameter
UINT32
rw
Y
UINT32
0x63100110
<TriggerParameter>
Byte
3
2
1
0
Description
Index MSB
Index LSB
Sub-index
Parameter bit length
Default
0x63
0x10
0x01
0x10