Moog ACV with CANopen bus interface
6 Signal routing and scaling
Setpoint value path
B99224-DV018-D-211, Rev. A, October 2018
62
6.2.4.2 Object 0x3310: Setpoint parameter
The pressure setpoint value parameter <PrsSetpointParameter> (0x3310) points to the input where the pres-
sure setpoint value <PrsSetpoint> (0x6380) comes from.
The pressure setpoint value <PrsSetpoint> (0x6380) is only effective in case the <StatusWord> (0x6041) is
1111
b
('ACTIVE') and the <DeviceMode> (0x6042) is set to 1 (setpoint input via bus).
Value description
This pointer contains a combination of index, sub-index and length of the parameter to be used. It may only
refer to parameters with a bit length of 0x10.
The default value is 0x63800110, which refers to the <PrsSetpoint> (0x6380), sub-index 0x01 with the length
of 16 bit (16 = 0x10).
6.2.4.3 Object 0x6394: Prs hold setpoint
This parameter defines the pressure hold setpoint value. It is effective for the following
<ControlMode> (0x6043):
Chapter "7.1.1 Object 0x6043: Control mode", page 128
The <PrsHoldSetpoint> (0x6394) acts as setpoint value in case of <StatusWord> (0x6041) equals 'HOLD' or
'FAULT_HOLD'.
Chapter "5.2.3 Object 0x6041: Status word", page 52
Chapter "2.4.3 Units and prefix parameter", page 12
ValvePressureControl
Index
Sub-index
Parameter name
Data type
Access
Persis-
tence
Value
range
Default
0x3310
0x00
PrsSetpointParameter
INT32
rw
Y
INT32
0x63800110
<SetpointParameter>
Byte
3
2
1
0
Description
Index MSB
Index LSB
Sub-index
Parameter bit length: 0x10
Default
0x63
0x80
0x01
0x10
Table 34: Possible values of parameter <PrsSetpointParameter> (0x3310)
3
Pressure control open loop
4
Pressure control closed loop
5
p/Q control
8
Force control
14 p/flow control
ValvePressureControl_DemandValueGenerator
Index
Sub-index
Parameter name
Data type
Access
Persis-
tence
Value
range
Default
0x6394
1
PrsHoldSetPoint
INT16
rw
Y
INT16
0
0x6394
2
Unit
UINT8
ro
-
UINT8
0
0x6394
3
Prefix
INT8
ro
-
INT8
0