background image

ENOWd – Gateway EnOcean ®

Hardware: V1.31

Firmware: V1.3

1. 

   GENERAL FEATURES

 

 :

Reading points:

  60 wireless input devices and 60 wireless

output devices.

Control:

 Via MD BUS e EnOcean®;

Applications:

  Interface   between   wireless   devices   and

EnOcean® Mordomus;

Installation:

 DIN Rail.

2. 

   GENERAL SPECIFICATIONS

 

 :

Voltage:

 12VDC;

Consumption

: 70mA @ 12VDC;

Storage Temperature:

 -10ºC to 60ºC;

Operating Temperature:

 10ºC to 50ºC;

Maximum Humidity

: 80%, non-condensing;

Physical Specifications:

 

Dimensions:

 105mm X 90mm X 70mm, DIN rail mounting (6

modules); Box Plastic, self-extinguishing UL-94 V0;

Level Protection:

 IP20, for indoor use.

3. 

   COMPATIBILITY

 

 :

PCCWd Compatibility:

 Firmware 3.42 or higher.

Mordomus   Software   Compatibility:

  Mordomus   Software

v2015.2 or higher;

4. 

   SECURITY

 

 :

Before   making   any   connections,   please   read   these
instructions carefully. 

Never remove the plastic base from DIN rail.

5. 

   CONNECTIONS

 

 :

Thickness of conductors:

Bus Circuit:

CAT6 Cable F/UTP shielded, twisted;

Power circuit:

Mono-wire or multi-wire at least 0.75 mm²

Table of Connections:

Number

Function

1

GND

2

MD BUS Inputs A

3

MD BUS Inputs B

4

GND

5

MD BUS Outputs A

6

MD BUS Outputs B

14

GND

15

+12VDC

16

GND

17

+12VDC

Connect the 12VDC:

The use of 

Mean-Well

DR60-12 

or 

DR30-12 

power supplies

is recommended.

Connect the Bus:

To   connect   the   BUS,   must   be   used   a   pair-Interlace   CAT6
cable. For example, Green for 

and Green/White for 

B

,

The shield should be connected to GND.

If   the   module   is   the   last   module   at   Mordomus   Bus,   the
jumpers must be placed according to Fig 1 b) to close the
BUS chain. In other situations it should remain as in Fig 1 a).

Manual: ENO-1642-EN

www.mordomus.com

Page 

1

/

2

Reviews: