On completion, a summary of the differences is shown with a total figure. In this example, 23 new
devices have been found (added), there are no devices found to be missing (removed) and there
are no devices that have been found to change type (changed). Check that the numbers listed
against each type of device match the expected physical installation of devices.
-
Enter the appropriate loop number and press the
key. Confirmation is requested to learn all
devices on the loop.
-
Press the
key once more to start the learn process. To cancel, press the
key.
-
The lower half of the LCD provides a summary of the number of sensor and module device types
found after performing the learn operation; a sub-total of each device type is displayed in two rows:
the sensor types in the upper row with the module types in the lower row.
-
The main types of devices have their own columns – for other devices, these are summed in the
‘Others’ column –
the actual type of device will be shown in the user access Level 2 ‘View Mode/
Devices’ for the devices learnt.
-
If the panel has more than one loop, use the
/
keys to view the other loop(s).
-
Refer to
Table 4
for a list of the device type abbreviations used.
-
Press the
key to exit the summary screen and return to the ‘Loop’ menu screen.
5.3.6 Local Inputs
-
The local inputs comprise the optional keyswitch, monitored inputs and function keys. The Input
Action, Zone and Disablement Group assigned to each input can be programmed.
-
With ‘Keyswitch’ selected, press the
key if a change is required to its assigned Input Action,
Zone or Group (disablement action).