62
Morley-IAS
996-203-000-2, Rev. 02
5.4
Programming Using the PC Configuration Tool
-
The DX Connexion Series of Fire Control Panels allows the programming of ALL configuration
parameters including, for some markets, an option to select the SLC device manufacturer’s protocol.
-
If using the Isolated USB to Serial
Adapter Kit lead (PN: 020-891) and
4-way target cable (PN: 082-298),
connect to the 4-way connector on the
left-hand edge of the Base PCB (see
illustration at right). The MIAS
communications lead (PN: 795-080)
may also be used for this purpose.
-
The panel needs to be at user access
Level 3 to upload the configuration file
to the panel. However, downloading
the configuration to the PC does not
require this user access level.
-
Instructions on how to use the PC
Configuration Tool are not given here
- refer to the user documentation
supplied via the tool’s Help menu.
Figure 31 - Position of PC Tool Cable Connector
5.4.1 Retrieving Configuration Data
-
To carry out this operation the panel does not require entry of user access passcodes.
-
The LCD shows the progress of the data transfer between the panel and the PC. During this operation
the LCD displays messages about the data currently being sent to the PC, i.e settings and text
information. The user is still able to view panel operating conditions by pressing the
key.
-
Following completion the panel will return to the normal status display or the previously-displayed
screen.
5.4.2 Sending Configuration Data
-
To carry out this operation requires the panel to be at user access Level 3. Refer to the Help
documentation supplied with the tool.