3
Morley-IAS
996-203-000-2, Rev. 02
1.4
National Approvals
-
This equipment must be installed and operated in accordance with these instructions and the
appropriate national, regional and local regulations specific to the country and location of the
installation. Consult with the appropriate Authority Having Jurisdiction (AHJ) for confirmation of the
requirements.
-
This equipment must be installed in accordance with these instructions and the appropriate national,
regional and local wiring regulations.
All equipment is to be installed in accordance with the appropriate standards for the country and
area of installation.
1.5
EN54 Information
-
This Fire Alarm Control Panel complies with the requirements of EN54-2/4. In addition
to the basic requirements of EN54, the panel conforms to the following optional functions.
EN54
3
Option
EN54-2 Clause
Indication:
Alarm counter
7.13
Fault signals from points
8.3
Controls:
Delays to outputs
7.11.1
Manual or automatic switching of delays to outputs
7.11.2
Dependency on more than one alarm signal: Type C
7.12.3
Disablement of each address point
9.5
Test condition
10
Outputs
:
Outputs to fire alarm device(s)
7.8
EN54
3
-
The power supplies for the Connexion Series of panels comply with the following
clauses of EN54-4.
DXc1/2/4 Power Supply Functions
EN54-4 Clause
Derive power supply from main power source
5.1
Derive power supply from a standby battery source
5.2
Charge and monitor the standby battery source
5.3
Detect & signal power supply faults
5.4