Appendix 6 Event Text Explained
-
The table below provides a description of the meaning/ cause behind each possible event log entry.
Event Text (English)
Description/ Meaning
Control Actions
EVACUATE
A 'Sound Alarms' button or digital loop input associated with the 'Evacuate'
action has been activated.
SILENCE SOUNDERS
A 'Silence/ Resound' button or digital loop input associated with the 'Silence'
action has been activated.
RESOUND SOUNDERS
With sounders already 'silenced', the 'Silence/ Resound' button or digital
loop input associated with the 'Silence' action has been activated.
MUTE INTERNAL BUZZER
A panel or repeater 'Mute Buzzer' button has been activated.
RESET PANEL
A 'Reset' button or digital loop input associated with the 'Reset' action has
been activated.
EXTEND DELAY
A panel EXTEND DELAY or repeater 'Accept' button has been activated.
Device Actions
FIRE ALARM
An input device associated with a Fire action has activated
TEST FIRE ALARM
An input device, from a zone currently in test mode, associated with a
Fire action has activated.
PLANT ALARM
An input device associated with a 'Plant Warning' action has activated
TEST PLANT ALARM
An input device, from a zone currently in test mode, associated with a
'Plant Warning' action has activated.
PRE-ALARM
A detection device has registered a pre-alarm level - based on it's
programmed pre-alarm threshold.
PLANT ALARM RETURN
An input device associated with the 'Plant Warning' action has returned
from its activated state back to normal.
FIRE ALARM RETURN
An input device associated with the 'Fire' action has returned from its
activated state back to normal.
BOMB ALERT
An input device associated with the 'Bomb Alert' action has been activated
BOMB ALERT RETURN
An input device associated with the 'Bomb Alert' action has returned from
its activated state back to normal.
INTRUDER ALERT
An input device associated with the 'Security' action has been activated
INTRUDER ALERT RET'N
An input device associated with the 'Security' action has returned from its
activated state back to normal.
TRANSPARENT ACTION
An input device associated with the 'Transparent' action has been activated
TRANS ACTION RETURN
An input device associated with the 'Transparent' action has returned from
its activated state back to normal.
CLASS CHANGE START
An input device associated with the 'Class Change' action has been activated
CLASS CHANGE FINISH
An input device associated with the 'Class Change' action has returned
from its activated state back to normal.
DETECTION MODE START An input device associated with the 'Det Mode' action has been activated.
Overrides the timer to instigate the detection mode manually.
DETECTION MODE END
An input device associated with the 'Det Mode' action has returned from
its activated state back to normal.