7.10 External Wiring Connections
Refer to the following sections of this manual for information regarding the connection of
detection loop cables, sounder circuits and other site installation wiring and cabling:
1. Detection Loops – Section 3.4.3
2. Sounder Circuits - Section 3.4.4
3. Auxiliary Relay Outputs – Section 3.4.5
4. Auxiliary Supply Outputs - Section 3.4.6
5. Panel Networking / Graphics PC Interface – Section 3.4.7
6. Peripheral Loop – Section 3.4.8
7. RS485 Wiring Arrangements – Section 3.4.9
8. High Integrity Loop – Section 3.4.10
9. Recommended Cables – Section 3.4.13
7.11 Cable Routing
Cables should be routed within the enclosure in accordance with the diagram below.
AC Mains
Cables
RS485/RS232
Power-Limited
SLC Circuits
Power-Limited
Sounder and
AUX Power
Power-Limited
Relay Outputs
Non
Power-Limited
Relay Outputs
Non
Power-Limited
Inter-panel
Network wiring
RS485
Figure 37 – Recommended Cable Routing Arrangement – ZX10Se