ZX Fire Alarm Control Panels
Page 48
Document No. 996-174-000-1, Revision: 01
Installation Manual
7.12 Installing Additional Equipment
Refer to Section 3.5 Installing Additional Equipment for relevant instructions on fitting loop driver
cards, RS485 / RS232 interface cards, printer module (top panel only) or key switch option.
7.13 Maintenance
Refer to Section 5 Maintenance for details relating to all ZX10Se FACP maintenance issues.
7.14 Specification
7.14.1 Functional Specifications
Specification Item
Values
Enclosure
500mm wide, 1000mm high, 185mm deep.
Sealed to IP30.
Weight
38kg without batteries.
76.8 kg with 24Ah batteries fitted.
Operating Temperature
0ºC to +40ºC
Relative Humidity
85% (non-condensing).
Knockouts (20mm)
24 (top), 24 (bottom).
Sounder Output
4 programmable outputs (x2)
Open- and short-circuit monitored.
6k8, EOL resistors (P/N 170-073-682).
1A maximum output current.
Minimum switched current – 1mA.
Auxiliary Relay
2 volt-free, changeover outputs. Relay 1 configured as
Fault output. Relay 2 configured as Fire output. (x2).
Contacts rated at 30V AC/DC, 1A maximum.
Sensor Circuit
1 to 5 plug-in loop driver modules per ZX5Se FACP.
Supports Analogue Addressable devices over a 2-wire
combined power and digital data transmission loop.
Loop output voltage and signalling depends on the loop
driver installed – refer to documentation supplied with the
loop driver.
Maximum loop loading is 460mA.
Monitoring Zones
Up to 20 zones with individual LED indicators,
Expandable to 40/80 zones with optional LED indicator
boards per (x2).
Maximum 120 zones – up to 200 software zones (no LED
indicators) – x2.
Table 13 – ZX10Se Functional Specification