30
Installation
Connect the Power Wires
WARNING: Shock Hazard
The solar PV array can produce open-circuit voltages in excess of 500 Vdc when
in sunlight. Verify that the solar input breaker or disconnect has been opened
(disconnected) before installing the system wires.
AVERTISSEMENT : Risque de décharge électrique
Le réseau PV solaire peut produire des tensions de circuit ouvert supérieures à 500 V cc
à la lumière du soleil. Vérifiez que le coupe-circuit ou l’interrupteur d’entrée solaire a été
ouvert (déconnexion) avant d’installer les câbles du système.
Using the following steps, connect the power conductors corresponding to the lettered
references shown in Figures 3-10 and 3-11 on pages 28-29
:
NOTE:
Refer to GFPD-600V manual for all product details and specifications.
A. Open the main solar and battery disconnects, and GFPD breaker (down). Open all solar
disconnect switches and battery breakers / switches before connecting the power wires to the
controller.
B. Pull the PV and battery wires into the TS-MPPT-600V-TR. The Remote Temperature
Sensor (RTS) and Battery Sense wires can be routed inside conduit along with the battery
power conductors if required. The RTS and Battery Sense wires CANNOT be routed in the same
conduit with the high voltage solar conductors. It is easier to pull the RTS and Sense wires before
the power cables.
C. Only route high voltage solar circuit conductors in the high voltage wiring zone and low
voltage battery and network conductors within the low voltage zone. Refer to section 3.2 for more
information.
WARNING: Risk of Damage
The grid-tie inveter should be OFF during the next step. Be very certain that the grid-tie
connections are made with correct polarity.
AVERTISSEMENT : Risque d’endommagement
La grille-cravate inveter devrait être OFF au cours de cette étape. Être très certain que les
connexions réseau sont faites en respectant la polarité.
D. Connect the grid-tie inverter (+) and (-) wires to the solar (+) and (-) output terminals going to
the grid-tie inverter solar input.
WARNING: Risk of Damage
Be very certain that the solar connections are made with correct polarity. Turn on the solar array breaker /
disconnect and measure the voltage on the open wires BEFORE connecting to the TS-MPPT-600V-TR.
Disconnect the solar breaker/disconnect before wiring to the controller.
AVERTISSEMENT : Risque d’endommagement
Assurez-vous que les connexions solaire sont effectuée avec la polarité correcte. Activez le coupe-circuit/
interrupteur de réseau solaire et mesure la tension sur les câbles ouverts AVANT la connexion au
TS-MPPT-600V-TR. Déconnectez le coupe-circuit/interrupteur solaire avant le câblage sur le contrôleur.