background image

DB15

 INSTALLATION AND OPERATING INSTRUCTIONS

8

9

DB15

 INSTALLATION AND OPERATING INSTRUCTIONS

PARTS AND ACCESSORIES

 Standard Spare Parts for Morso DB15 Central Heating Stove

to be emitted from the chimney, especially when the fire is cold.
Use only VERY dry wood or smokeless fuels. Is the chimney high
enough and hot enough to generate the necessary 12Pa draught?

POOR HEAT OUTPUT:  

This appliance is  

very easily

  capable of

producing   the   quoted   heat   outputs   given   suitable   fuels   and   a
chimney capable of developing sufficient draught. Is the chimney
too short or becoming cool or damp? Is the fuel completely dry?
Have   the   central   controls   been   set   correctly?   Is   the   building
sufficiently well insulated?

CONDENSATION  

onto   cool   surfaces   inside   the   stove   can   be

severe if fuel is in any way damp. 

Use only very dry fuel. 

It is vital

that the heating circuit is fitted with a device, such as a low-limit
thermostat, to minimise cold water circulating through the boiler.

SMOKE   COMING   INTO   ROOM  

A   little   smoke   leaking   into   the

room   during   refuelling   is   normal,   but   fumes   are   poisonous   and
recurrent   smoke   emission   must   NEVER   be   tolerated,   causes
might be:
NEW STOVE: There is often a smell and sometimes visible fumes
as the paint cures. This normally stops after an hour or so.
INADEQUATE   SEALS:   Are   all   flue   pipes   and   connectors

absolutely

  gas-tight? Even the tiniest crack or gap can spoil the

draught. Does an inset appliances fully seal against the fireplace? 
BLOCKED   FLUEWAYS:   Has   soot   and   ash   collected   above   the
inner back part of the firebox? 
UNSUITABLE,   BLOCKED   OR   UN-SWEPT   CHIMNEY:   The   first
requirement for correct operation is a sound chimney. Check the
requirements  earlier   in   this  document  and   in  any  case   of   doubt
engage a professional sweep or chimney engineer.
POOR AIR SUPPLY: Lack of air to the fire is a common cause of
smoking   and   poor   performance.   Air   supply   problems   may   be
worse   in   certain   wind   conditions   (often   incorrectly   ascribed   to
'downdraught', which is in fact very rare), where air can be sucked
out of the room. The answer is to fit an air vent, as near to the fire
as possible, facing into the usual wind direction.

DOWNDRAUGHT:   Wind   can   blow  

down

  a   chimney   if   there   is

something   higher   nearby   such   as   a   tree,   hill   or   high   building.
Fitting an anti-downdraught cowl to the chimney top can cure this.
Types which cannot be swept through are not recommended.
POOR CHIMNEY DRAUGHT- Chimney draught in use MUST be
at least 12Pa. 

CHIMNEY FIRE: 

In the rare event of deposits inside the chimney

igniting   (roaring   sound   +   dense   smoke   and   sparks   from   the
chimney) immediately close the door, shut all air controls and call
the fire brigade. Prevent fires by using  

very dry fuel 

and having

your chimney swept regularly.

 MAINTENANCE

MONTHLY

- Open the fire door and inspect the top flue passages.

Gain access for cleaning by using the tool to lift off the lid (B on the
diagram).

ANNUALLY-   SWEEP   THE   CHIMNEY

  The   entire   length   of   the

chimney from stove to outlet should be swept annually, more often
if smoky fuels are used.

NEW PARTS  

Your stove has been extensively tested for safety -

please don't try to modify it and always obtain genuine spare parts

.

SURFACE FINISH

 Wipe the stove body with a slightly damp cloth

when cool. NEVER use aerosol spray or wax near the hot fire –
they   can   ignite.   Painted   steel   parts   can   be   refurbished   using
special spray paint. 

Your   stove   generates  

VERY

  high   temperatures.   Eventually   the

internal parts will require replacement . Help parts to last by:

●Using only recommend, very dry, fuels.
●Emptying the ash very regularly when using mineral fuel -never

allow it to touch the underside of the grate.

●Cleaning the flueways regularly.
●Avoiding 'over-firing'

 

PARTS AND ACCESSORIES

 Standard Spare Parts for Morso DB15 Central Heating Stove

Part Number

a

Window

MOR0029

b

Front firebar

MOR0030

c

Riddling bar

MOR0031

d

Thermostat assembly

MOR0032

e

Roof brick, pair, with seals

MOR0033

f

Side Brick, pair, with seals

MOR0034

g

Mid Brick, with seals

MOR0035

h

Firebar, upper

MOR0036

k

Firebar, lower

MOR0037

m

Ashpan

MOR0038

Touch-up paint

MOR0039

Operating tool

MOR0040

Rope Seal kit

MOR0041

Mineral fibre seals between bricks

MOR0042

Morso UK Ltd, Unit 7, The I O Centre, Valley Drive, Rugby, Warwickshire, CV21 1TW   UK

 4

These stove designs are registered at the UK Patent Office, Design No 4030575 and others, and are protected by Copyright © and UK Design Right, Glyn Hughes 2006-2013. 
Certain parts are UK Patent Applied For. This document printed 10/09/2013. We are always striving to improve these products and may change their specification without notice.

KEY

SPARE PART

PART NUMBER

A

WINDOW

MOR0029

B

FRONT FIREBAR

MOR0032

C

RIDDLING BAR

MOR0031

D

THERMOSTAT ASSEMBLY

MOR0032

E

ROOF BRICK, PAIR, WITH SEALS

MOR0033

F

SIDE BRICK, PAIR, WITH SEALS

MOR0034

G

MID BRICK, WITH SEALS

MOR0035

H

FIREBAR, UPPER

MOR0036

K

FIREBAR, LOWER

MOR0037

M

ASHPAN

MOR0038

TOUCH-UP PAINT

MOR0039

OPERATING TOOL

MOR0040

ROPE SEAL KIT

MOR0041

MINERAL FIBRE SEALS BETWEEN BRICKS

MOR0042

1. CONTROL THE  

HEATING SYSTEM

 

Stove boilers control their 

own water temperature  

by an internal thermostat,  

so controls such as time 

clocks and thermostats 

regulate flow through the 

heating circuit, not  

the boiler. 

2. GUARD AGAINST 

CONDENSATION!

 

Solid fuels contain water 

which can condense on  

cool boiler faces to cause 

VERY rapid corrosion and 

failure. Use very dry fuel 

and always fit a device such 

BOILER STOVE CENTRAL HEATING SYSTEMS  

This is a rough guide to specifying and fitting central heating using a solid fuel boiler stove with 
thermostatic control. It doesn’t cover every detail, which will need to be determined on-site by  
a skilled heating engineer.
‘Wet’ solid fuel central heating systems use the same types of pipework (including microbore, 
plastic) and heat emitters (radiators, underfloor, etc), as other fuels and they can likewise  
come on in the morning, go off at night and regulate themselves. Systems must...

HEAT REQUIREMENT

CONTROLS

GET THE RIGHT SIZE HEATERS 

Guesswork won’t do.  

A preliminary estimate of heat 

requirement for each room 

can be got from the table here. 

Example: A room 6m x 5m x 

2.8m has volume of 84m³.  

If it was a ground floor room 

in the corner of a two-storey 

house, in which the adjacent 

rooms and the one above were 

also heated, then 2 unheated 

outsid 1 outside floor = 

3 unheated faces.  

If moderately insulated then 

Your stove has a built-in 
mechanical thermostat 
to regulate its water 
temperature. A tiny vial of 
oil is fitted in the boiler. 
As the boiler water gets 
hotter, the oil expands 
along a fine tube, moves 
a bellow outward,moving 
an arm, which closes off 
air to the fuel and so slows 
combustion. So, if the time 
clock or room thermostat 
determines that no heat 
is needed, it stops the 
circulating pump; without 

 

BOILER STOVE CENTRAL HEATING SYSTEMS

This is a rough guide to specifying and fitting central heating using a solid fuel boiler stove with thermostatic control. It doesn't cover
every detail, which will need to be determined on-site by a skilled heating engineer.
'Wet' solid fuel central heating systems use the same types of pipework (including microbore, plastic) and heat emitters (radiators,
underfloor, etc), as other fuels and they can likewise come on in the morning, go off at night and regulate themselves. Systems must...

1: CONTROL THE HEATING SYSTEM.  

Stove boilers control their own water temperature by an internal thermostat, so controls

such as time clocks and thermostats regulate flow through the heating circuit, not the boiler.

2: GUARD AGAINST CONDENSATION! 

Solid fuels contain water which can condense on cool boiler faces to cause VERY rapid corrosion

and failure. Use 

very

 dry fuel and 

always

 fit a device such as a low-level thermostat to minimise cool water circulating through the boiler.

2:   ALLOW   FOR   EXCESS   HEAT.  

The   fire   can   close  down   automatically,   but   it   can't  

completely  

stop  combustion   and   output   will   vary

considerably during a fuelling cycle. There must be some infallible means of dissipating, and preferably storing, surplus heat, for instance a
hot water cylinder or a thermal store and always a system to run the central-heating pump if there is risk of boiling. Should thermostat and
pump fail together, there must be infallible provision to cool the system, or allow it to boil, for instance through an open vent. (The old-
fashioned idea of deliberately wasting heat through a permanent "heat leak" radiator not only throws heat away, it just will not suffice with
powerful modern stoves.)

 HEAT REQUIREMENT

GET   THE   RIGHT   SIZE   HEATERS.  

Guesswork   won't   do.   A   preliminary  estimate   of   heat

requirement for each room can be got from the table here. 

Example

: A room 6m x 5m x 2.8m

has volume of 84m³. If it was a ground floor room in the corner of a two-storey house, in
which the adjacent rooms and the one above were also heated, then 2 unheated outside
walls + 1 outside floor = 3 unheated faces. If moderately insulated then the factor in the table
is 40 Watts per m³, so 84m³ x 40 = 3360 Watts, or 3.36kW. A radiator, or radiators, emitting
at least 3.36kW should be specified.
Don't   forget   that,   with   boiler   stoves,   the   room   output   and   water   output   go   up   and   down
together - turn the central heating down, and the whole stove goes cooler. It is usually wise to
fit a radiator (with thermostatic valve) in the fireplace room.
The actual value varies with the shape, exposure, draughtiness and temperatures. For larger
installations or whole-house heating, use the more accurate 'U-Value method - an online
heat-need calculator is available at 

www.soliftec.com

APPROXIMATE HEAT REQUIREMENT OF ROOMS

Watts 

per

 Cubic Metre

Number of unheated faces

1

2

3

4

5

6

 

No effective insulation 

eg: all-glass rooms with single glazing, barns, workshops, tents

120

132

145 158 170 183

Poor insulation 

eg; single glazing, little loft insulation, uninsulated cavity walls, draughts

62

70

78

86

94 102

Moderate insulation 

eg: thick solid walls, some loft insulation, some draught-proofing

31

35

40

44

48

53

Good Insulation 

eg: some wall insulation, thick loft insulation, double glazing, draught-proofing

21

24

27

31

34

37

Best insulation 

eg: properties built to 2008 UK standards

16

18

20

22

24

26

Watts (W) per cubic metre 

 CONTROLS 

Your   stove   has   a   built-in
mechanical   thermostat   to
regulate

 

its

 

water

temperature. A tiny vial of oil
is  fitted  in  the  boiler.  As  the
boiler   water   gets   hotter,   the
oil expands along a fine tube,
moves   a   bellow   outward,
moving an arm, which closes
off   air   to   the   fuel   and   so
slows combustion. So, if the timeclock or room thermostat determines
that no heat is needed, it stops the circulating pump; without water
circulation the boiler begins to get too hot, the oil expands, shuts off
air and the fire dies down. If there is demand for heat, for instance in
the morning, the pump comes on, colder water enters the boiler, the
air-flap opens and the fire blazes up.  

The control dial on the stove does not directly turn the stove up and
down, it sets the water temperature at which the thermostat will begin
to shut the fire down.

We recommend a control system regulating the central-heating pump through (1) a single-channel time clock, (2) a centrally-located
room thermostat (not in the stove room) and (3) thermostatic radiator valves on all but one radiator. A low-level (about 50°C) pipe
thermostat to prevent pumped circulation of cool water (which can cause condensation, rust, and deplete stored hot water) and a high
level one (about 90°C) to override controls and run the heating circuit to dissipate heat if there is a risk of boiling. Stored hot water for
taps is not controlled, but accumulates during normal operation, especially during periods while central heating is not required.

 1

Copyright © and UK Design Right, Glyn Hughes 2006-2013. 

'Teddington' thermostat

(Normal cold '0' setting -  about 7mm open)

Typical wiring layout through connector block (return dotted)

Room and boiler outputs vary together

the factor in the table is 40 Watts  

per m³, so 84m³ x 40 = 3360 Watts,  

or 3.36kW. A radiator, or 

radiators, emitting at least 

3.36kW should be specified. 

Don’t forget that, with boiler 

stoves, the room output and 

water output go up and down 

together - turn the central 

heating down, and the whole 

stove goes cooler.  

It is usually wise to fit a 

radiator (with thermostatic 

valve) in the fireplace room.  

The actual value varies 

as a low-level thermostat 

to minimise cool water 

circulating through the boiler.

3. ALLOW FOR  

EXCESS HEAT

 

The fire can close down 

automatically, but it can’t  

completely stop combustion 

and output will vary considerably 

during a fuelling cycle. 

There must be some infallible 

means of dissipating, and 

preferably storing, surplus 

heat, for instance a hot 

water cylinder or a thermal 

store and always a system 

to run the central-heating 

pump if there is risk of 

boiling. Should thermostat 

and pump fail together, 

there must be infallible 

provision to cool the system, 

or allow it to boil, for 

instance through an open 

vent.  

(The old-fashioned idea of 

deliberately wasting heat 

through a permanent “heat 

leak” radiator not only 

throws heat away, it just  

will not suffice with powerful 

modern stoves.)

APPROXIMATE HEAT REQUIREMENT OF ROOMS  

Watts per Cubic Metre

NUMBER OF UNHEATED FACES

1

2

3

4

5

6

INSULA

TION

No effective insulation eg: all-glass rooms with single  

glazing, barns, workshops, tents

120

132

145

158

170

183

Poor insulation eg; single glazing, little loft insulation,  

uninsulated cavity walls, draughts

62

70

78

86

94

102

Moderate insulation eg: thick solid walls, some loft insulation, 

some draught-proofing

31

35

40

44

48

53

Good Insulation eg: some wall insulation, thick loft insulation, 

double glazing, draught-proofing

21

24

27

31

34

37

Best insulation eg: properties built to 2008 UK standards

16

18

20

22

24

26

WATTS (W) PER CUBIC METRE

water circulation the boiler 
begins to get too hot, the oil 
expands, shuts off air and 
the fire dies down. If there  
is demand for heat, for instance 
in the morning, the pump 
comes on, colder water 
enters the boiler, the air-flap 
opens and the fire blazes up.
The control dial on the stove 
does not directly turn the 
stove up and down, it sets 
the water temperature at 
which the thermostat will 
begin to shut the fire down.

We recommend a control 
system regulating the 
central-heating pump 
through (1) a single-channel 
time clock, (2) a centrally-
located room thermostat 
(not in the stove room) and 
(3) thermostatic radiator 
valves on all but one 
radiator. A low-level (about 
50°C) pipe thermostat to 
prevent pumped circulation 
of cool water (which can 
cause condensation, rust, 
and deplete stored hot 
water) and a high level one 

with the shape, exposure, 

draughtiness and temperatures. 

For larger installations or 

whole-house heating, use 

the more accurate ‘U-Value 

method - an online heat-need 

calculator is available at  

www.soliftec.com. 

Summary of Contents for DB15

Page 1: ...HIGH EFFICIENCY MULTI SOLID FUEL CENTRAL HEATING STOVE WITH AUTOMATIC CONTROL Issued 10 09 2013 456 PLEASE LEAVE THIS DOCUMENT WITH THE HOUSEHOLDER DB15 INSTALLATION AND OPERATING INSTRUCTIONS ...

Page 2: ...h timber thatch or other vulnerable materials take specialist advice It is not possible to access the chimney for cleaning through the stove inspection and sweeping access must be provided The chimney must Generate a draught in use of at least 12Pa 0 05ins wg Be capable of withstanding the temperatures generated Be absolutely incapable of leaking fumes into the dwelling Several different forms of ...

Page 3: ...r manufactured smokeless fuels then empty the ash regularly if it builds up it will severely damage the grates If you mainly use wood then do the opposite let the ash and charcoal build up To empty the ash agitate the firebed by using the tool to operate the riddling mechanism on the right hand side Use the ashpan tool to lift out the ashpan Remember to let ash cool before disposing in plastic sac...

Page 4: ...himney Checktherequirementsearlier in this document and in any case of doubt engage a professional sweep or chimney engineer POOR AIR SUPPLY Lack of air to the fire is a common cause of smoking and poor performance Air supply problemsmaybe worseincertain wind conditions often incorrectly ascribed to downdraught which is in fact very rare where air can be sucked out of the room The answer is to fit...

Page 5: ...hemselves Systems must 1 CONTROL THE HEATING SYSTEM Stove boilers control their own water temperature by an internal thermostat so controls such as time clocks and thermostats regulate flow through the heating circuit not the boiler 2 GUARD AGAINST CONDENSATION Solid fuels contain water which can condense on cool boiler faces to cause VERY rapid corrosion and failure Use very dry fuel and always f...

Page 6: ...ratures are approximate and will vary Scheme 1 TRADITIONAL 2 SIDE Compact and quick to heat Stores hot water for taps but radiators will go cold if the fire goes out Recommended for occasional use or where long burning mineral fuels are used One side of the boiler feeds by gravity circulation alone an indirect coil to heat a hot water storage cylinder and has feed and vent connections to a small o...

Page 7: ... 8 5 7 6 2 7 8 9 1 To water kW 6 3 8 8 7 9 7 7 7 6 Total Output kW 12 1 14 5 4 1 15 5 16 7 Mean Flue Gas Temp Rise ºC 200 C 263 C 251 C 276 C 241 C CO 13 o2 0 06 0 24 0 07 0 24 0 23 Minimum room air entry requirement 8000 mm Minimum Clearance to combustibles 100mm at sides and back Temperature underneath can exceed 100 C traditional hearth required These stoves exceed the safety and performance re...

Reviews: