background image

DB15

 INSTALLATION AND OPERATING INSTRUCTIONS

10

11

DB15

 INSTALLATION AND OPERATING INSTRUCTIONS

 WATER SYSTEM CONNECTIONS

Outlines of some possible installation schemes are
shown here. In both of them: 

●Possible   boiling   is   safely   accommodated   by   a

vent   pipe   leading   directly   to   an   open   feed   and
expansion tank.

●A c50°C low-level thermostat brings the pumped

system 'on' only when the fire is hot. It prevents
stored   hot   water   from   being   depleted   and   cold
water chilling the boiler. Vital to prevent corrosion.

●A   c90°C   thermostat   can   close   to   override   all

other   controls   and   operate   the   central   heating
pump to dissipate heat if there is a risk of boiling.

●There   are   time   and   room-temperature   controls

controlling the central-heating pump.

●Hot water for taps is not separately controlled, it

may   become   scalding   hot   -   consider   fitting   a
thermostatic mixing valve.

●An   electric   immersion   heater   is   provided   for

summer hot water.

Temperatures are approximate and will vary.

 Scheme 1: TRADITIONAL 2-SIDE 

Compact   and   quick   to   heat.   Stores   hot   water
for   taps,   but   radiators   will   go   cold   if   the   fire
goes out. Recommended for occasional use or
where long-burning mineral fuels are used.

One side of the boiler feeds, by gravity circulation
alone, an indirect coil to heat a hot-water storage
cylinder  and has feed and vent  connections to a
small   open   expansion   tank.   (Gravity   piping
requires careful calculation but will generally be 

at

least

  28mm diameter, rise continually and have a

horizontal distance from the boiler of no more than
its vertical distance above it.)
The   other   side   of   the   boiler   connects   to   the
pumped   central   heating   circuit,   which   activates
only   when   a   time-clock,   room   thermostat   and
c50°C pipe thermostat (on the domestic hot-water
side flow pipe near to the boiler), are all 'closed'. 
A second electrical supply feeds a pipe thermostat
on the flow pipe to domestic water very near to the
boiler and set to close above c90°C, such that if
there is risk of boiling the central-heating pump will
always operate to dissipate heat.

 Scheme 2: THERMAL STORE

A   large   body   of   water   is   stored   at   a   high
temperature,   to   supply   both   taps   and   central
heating   when   needed.   High   and   low   output
phases   are   evened-out;   heating   can   operate
even   if   the   fire   is   out,   eg,   next   morning.
Recommended for all uses, and always where wood is the main fuel.

In one system, a 'combined' thermal store or 'heat bank' of about 300 litre capacity is directly heated by the boiler and has an indirect
coil [1] in its highest (hottest) part to supply tap water, below which the central-heating flow is taken-off as needed.
Pump (P1) circulates hot water from the boiler to the store only when a pipe thermostat on the boiler flow pipe is above c50°C. The,
separate,   central   heating   pump   (P2)   operates   only   when   the   time-clock,   room
thermostat and a second c50°C thermostat responsive to temperature in the store, are
all   'closed'.   A   second   thermostat   towards   the   top   of   the   store   closes   at   c90°C   to
dissipate heat if there is risk of boiling.
Extra indirect coils may be provided at [2] to accommodate a supply from a second
central-heating boiler, and at [3] to receive relatively low-grade heat from solar panels. 

 LINK-UP TO ANOTHER BOILER

Your   stove   can   be   linked   into   an   oil   or   gas   central   heating   system   and   operate
completely automatically. One method is to use a thermal store system, like Scheme 2
above,  with  a separate coil (for pressurised  boilers) or extra direct connections  (for
open-vent boilers).
Another method uses a 'neutral point manifold' where both boilers are connected to the
manifold, which   is in  turn  connected  to the  hot water  and  radiator  circuits. Suitable
devices come from 

www.esse.com

 and 

www.systemlink.ie

.

 2

 Scheme 1: 

Traditional 2-side system with gravity hot water.

Recommended where mineral fuels are mainly to be used

 Scheme 2:  

 Thermal store system.

Recommended for all uses, and always where wood is the main fuel.

Outline of multiple boiler Link-Up using a neutral-point

manifold

 WATER SYSTEM CONNECTIONS

Outlines of some possible installation schemes are
shown here. In both of them: 

●Possible   boiling   is   safely   accommodated   by   a

vent   pipe   leading   directly   to   an   open   feed   and
expansion tank.

●A c50°C low-level thermostat brings the pumped

system 'on' only when the fire is hot. It prevents
stored   hot   water   from   being   depleted   and   cold
water chilling the boiler. Vital to prevent corrosion.

●A   c90°C   thermostat   can   close   to   override   all

other   controls   and   operate   the   central   heating
pump to dissipate heat if there is a risk of boiling.

●There   are   time   and   room-temperature   controls

controlling the central-heating pump.

●Hot water for taps is not separately controlled, it

may   become   scalding   hot   -   consider   fitting   a
thermostatic mixing valve.

●An   electric   immersion   heater   is   provided   for

summer hot water.

Temperatures are approximate and will vary.

 Scheme 1: TRADITIONAL 2-SIDE 

Compact   and   quick   to   heat.   Stores   hot   water
for   taps,   but   radiators   will   go   cold   if   the   fire
goes out. Recommended for occasional use or
where long-burning mineral fuels are used.

One side of the boiler feeds, by gravity circulation
alone, an indirect coil to heat a hot-water storage
cylinder  and has feed and vent  connections to a
small   open   expansion   tank.   (Gravity   piping
requires careful calculation but will generally be 

at

least

  28mm diameter, rise continually and have a

horizontal distance from the boiler of no more than
its vertical distance above it.)
The   other   side   of   the   boiler   connects   to   the
pumped   central   heating   circuit,   which   activates
only   when   a   time-clock,   room   thermostat   and
c50°C pipe thermostat (on the domestic hot-water
side flow pipe near to the boiler), are all 'closed'. 
A second electrical supply feeds a pipe thermostat
on the flow pipe to domestic water very near to the
boiler and set to close above c90°C, such that if
there is risk of boiling the central-heating pump will
always operate to dissipate heat.

 Scheme 2: THERMAL STORE

A   large   body   of   water   is   stored   at   a   high
temperature,   to   supply   both   taps   and   central
heating   when   needed.   High   and   low   output
phases   are   evened-out;   heating   can   operate
even   if   the   fire   is   out,   eg,   next   morning.
Recommended for all uses, and always where wood is the main fuel.

In one system, a 'combined' thermal store or 'heat bank' of about 300 litre capacity is directly heated by the boiler and has an indirect
coil [1] in its highest (hottest) part to supply tap water, below which the central-heating flow is taken-off as needed.
Pump (P1) circulates hot water from the boiler to the store only when a pipe thermostat on the boiler flow pipe is above c50°C. The,
separate,   central   heating   pump   (P2)   operates   only   when   the   time-clock,   room
thermostat and a second c50°C thermostat responsive to temperature in the store, are
all   'closed'.   A   second   thermostat   towards   the   top   of   the   store   closes   at   c90°C   to
dissipate heat if there is risk of boiling.
Extra indirect coils may be provided at [2] to accommodate a supply from a second
central-heating boiler, and at [3] to receive relatively low-grade heat from solar panels. 

 LINK-UP TO ANOTHER BOILER

Your   stove   can   be   linked   into   an   oil   or   gas   central   heating   system   and   operate
completely automatically. One method is to use a thermal store system, like Scheme 2
above,  with  a separate coil (for pressurised  boilers) or extra direct connections  (for
open-vent boilers).
Another method uses a 'neutral point manifold' where both boilers are connected to the
manifold, which   is in  turn  connected  to the  hot water  and  radiator  circuits. Suitable
devices come from 

www.esse.com

 and 

www.systemlink.ie

.

 2

 Scheme 1: 

Traditional 2-side system with gravity hot water.

Recommended where mineral fuels are mainly to be used

 Scheme 2:  

 Thermal store system.

Recommended for all uses, and always where wood is the main fuel.

Outline of multiple boiler Link-Up using a neutral-point

manifold

 WATER SYSTEM CONNECTIONS

Outlines of some possible installation schemes are
shown here. In both of them: 

●Possible   boiling   is   safely   accommodated   by   a

vent   pipe   leading   directly   to   an   open   feed   and
expansion tank.

●A c50°C low-level thermostat brings the pumped

system 'on' only when the fire is hot. It prevents
stored   hot   water   from   being   depleted   and   cold
water chilling the boiler. Vital to prevent corrosion.

●A   c90°C   thermostat   can   close   to   override   all

other   controls   and   operate   the   central   heating
pump to dissipate heat if there is a risk of boiling.

●There   are   time   and   room-temperature   controls

controlling the central-heating pump.

●Hot water for taps is not separately controlled, it

may   become   scalding   hot   -   consider   fitting   a
thermostatic mixing valve.

●An   electric   immersion   heater   is   provided   for

summer hot water.

Temperatures are approximate and will vary.

 Scheme 1: TRADITIONAL 2-SIDE 

Compact   and   quick   to   heat.   Stores   hot   water
for   taps,   but   radiators   will   go   cold   if   the   fire
goes out. Recommended for occasional use or
where long-burning mineral fuels are used.

One side of the boiler feeds, by gravity circulation
alone, an indirect coil to heat a hot-water storage
cylinder  and has feed and vent  connections to a
small   open   expansion   tank.   (Gravity   piping
requires careful calculation but will generally be 

at

least

  28mm diameter, rise continually and have a

horizontal distance from the boiler of no more than
its vertical distance above it.)
The   other   side   of   the   boiler   connects   to   the
pumped   central   heating   circuit,   which   activates
only   when   a   time-clock,   room   thermostat   and
c50°C pipe thermostat (on the domestic hot-water
side flow pipe near to the boiler), are all 'closed'. 
A second electrical supply feeds a pipe thermostat
on the flow pipe to domestic water very near to the
boiler and set to close above c90°C, such that if
there is risk of boiling the central-heating pump will
always operate to dissipate heat.

 Scheme 2: THERMAL STORE

A   large   body   of   water   is   stored   at   a   high
temperature,   to   supply   both   taps   and   central
heating   when   needed.   High   and   low   output
phases   are   evened-out;   heating   can   operate
even   if   the   fire   is   out,   eg,   next   morning.
Recommended for all uses, and always where wood is the main fuel.

In one system, a 'combined' thermal store or 'heat bank' of about 300 litre capacity is directly heated by the boiler and has an indirect
coil [1] in its highest (hottest) part to supply tap water, below which the central-heating flow is taken-off as needed.
Pump (P1) circulates hot water from the boiler to the store only when a pipe thermostat on the boiler flow pipe is above c50°C. The,
separate,   central   heating   pump   (P2)   operates   only   when   the   time-clock,   room
thermostat and a second c50°C thermostat responsive to temperature in the store, are
all   'closed'.   A   second   thermostat   towards   the   top   of   the   store   closes   at   c90°C   to
dissipate heat if there is risk of boiling.
Extra indirect coils may be provided at [2] to accommodate a supply from a second
central-heating boiler, and at [3] to receive relatively low-grade heat from solar panels. 

 LINK-UP TO ANOTHER BOILER

Your   stove   can   be   linked   into   an   oil   or   gas   central   heating   system   and   operate
completely automatically. One method is to use a thermal store system, like Scheme 2
above,  with  a separate coil (for pressurised  boilers) or extra direct connections  (for
open-vent boilers).
Another method uses a 'neutral point manifold' where both boilers are connected to the
manifold, which   is in  turn  connected  to the  hot water  and  radiator  circuits. Suitable
devices come from 

www.esse.com

 and 

www.systemlink.ie

.

 2

 Scheme 1: 

Traditional 2-side system with gravity hot water.

Recommended where mineral fuels are mainly to be used

 Scheme 2:  

 Thermal store system.

Recommended for all uses, and always where wood is the main fuel.

Outline of multiple boiler Link-Up using a neutral-point

manifold

WATER SYSTEM CONNECTIONS  

Outlines of some possible installation 
schemes are shown here.  
In both of them:  
-  Possible boiling is safely accommodated  

by a vent pipe leading directly to an open  
feed and expansion tank.

-  A c50°C low-level thermostat brings the 

pumped system ‘on’ only when the fire  
is hot. It prevents stored hot water from  
being depleted and cold water chilling  
the boiler. Vital to prevent corrosion.

-  A c90°C thermostat can close to override 

allother controls and operate the central 
heating pump to dissipate heat if there is  
a risk of boiling.

-  There are time and room-temperature 

controls controlling the central-heating pump.

-  Hot water for taps is not separately 

controlled, it may become scalding hot - 
consider fitting a thermostatic mixing valve.

-  An electric immersion heater is provided 

for summer hot water. Temperatures are 
approximate and will vary.

 SCHEME 1: TRADITIONAL 2-SIDE

 LINK-UP TO ANOTHER BOILER

Compact and quick to heat. 
Stores hot water for taps, but 
radiators will go cold if the fire 
goes out. Recommended for 
occasional use or where long-
burning mineral fuels are 
used. One side of the boiler 
feeds, by gravity circulation 
alone, an indirect coil to heat a 
hot-water storage cylinder and 
has feed and vent connections 
to a small open expansion 
tank. (Gravity piping requires 
careful calculation but will 
generally be at least 28mm 
diameter, rise continually and 
have a horizontal distance from 
the boiler of no more than its 
vertical distance above it.)  
The other side of the boiler 

Your stove can be linked  
into an oil or gas central 
heating system and operate 
completely automatically. 
One method is to use a 
thermal store system, 
like Scheme 2 above, 
with a separate coil (for 
pressurised boilers) or  
extra direct connections  
(for open-vent boilers).
Another method uses a 
‘neutral point manifold’ where 
both boilers are connected 
to the manifold, which is in 
turn connected to the hot 
water and radiator circuits. 
Suitable devices come from 
www.esse.com and  
www.systemlink.ie.

connects to the pumped 
central heating circuit, which 
activates only when a time-
clock, room thermostat and 
c50°C pipe thermostat (on the 
domestic hot-waterside flow 
pipe near to the boiler), are all 
‘closed’. A second electrical 

supply feeds a pipe thermostat 
on the flow pipe to domestic 
water very near to the boiler 
and set to close above c90°C, 
such that if there is risk of 
boiling the central-heating 
pump will always operate to 
dissipate heat.

 WATER SYSTEM CONNECTIONS

Outlines of some possible installation schemes are
shown here. In both of them: 

●Possible   boiling   is   safely   accommodated   by   a

vent   pipe   leading   directly   to   an   open   feed   and
expansion tank.

●A c50°C low-level thermostat brings the pumped

system 'on' only when the fire is hot. It prevents
stored   hot   water   from   being   depleted   and   cold
water chilling the boiler. Vital to prevent corrosion.

●A   c90°C   thermostat   can   close   to   override   all

other   controls   and   operate   the   central   heating
pump to dissipate heat if there is a risk of boiling.

●There   are   time   and   room-temperature   controls

controlling the central-heating pump.

●Hot water for taps is not separately controlled, it

may   become   scalding   hot   -   consider   fitting   a
thermostatic mixing valve.

●An   electric   immersion   heater   is   provided   for

summer hot water.

Temperatures are approximate and will vary.

 Scheme 1: TRADITIONAL 2-SIDE 

Compact   and   quick   to   heat.   Stores   hot   water
for   taps,   but   radiators   will   go   cold   if   the   fire
goes out. Recommended for occasional use or
where long-burning mineral fuels are used.

One side of the boiler feeds, by gravity circulation
alone, an indirect coil to heat a hot-water storage
cylinder  and has feed and vent  connections to a
small   open   expansion   tank.   (Gravity   piping
requires careful calculation but will generally be 

at

least

  28mm diameter, rise continually and have a

horizontal distance from the boiler of no more than
its vertical distance above it.)
The   other   side   of   the   boiler   connects   to   the
pumped   central   heating   circuit,   which   activates
only   when   a   time-clock,   room   thermostat   and
c50°C pipe thermostat (on the domestic hot-water
side flow pipe near to the boiler), are all 'closed'. 
A second electrical supply feeds a pipe thermostat
on the flow pipe to domestic water very near to the
boiler and set to close above c90°C, such that if
there is risk of boiling the central-heating pump will
always operate to dissipate heat.

 Scheme 2: THERMAL STORE

A   large   body   of   water   is   stored   at   a   high
temperature,   to   supply   both   taps   and   central
heating   when   needed.   High   and   low   output
phases   are   evened-out;   heating   can   operate
even   if   the   fire   is   out,   eg,   next   morning.
Recommended for all uses, and always where wood is the main fuel.

In one system, a 'combined' thermal store or 'heat bank' of about 300 litre capacity is directly heated by the boiler and has an indirect
coil [1] in its highest (hottest) part to supply tap water, below which the central-heating flow is taken-off as needed.
Pump (P1) circulates hot water from the boiler to the store only when a pipe thermostat on the boiler flow pipe is above c50°C. The,
separate,   central   heating   pump   (P2)   operates   only   when   the   time-clock,   room
thermostat and a second c50°C thermostat responsive to temperature in the store, are
all   'closed'.   A   second   thermostat   towards   the   top   of   the   store   closes   at   c90°C   to
dissipate heat if there is risk of boiling.
Extra indirect coils may be provided at [2] to accommodate a supply from a second
central-heating boiler, and at [3] to receive relatively low-grade heat from solar panels. 

 LINK-UP TO ANOTHER BOILER

Your   stove   can   be   linked   into   an   oil   or   gas   central   heating   system   and   operate
completely automatically. One method is to use a thermal store system, like Scheme 2
above,  with  a separate coil (for pressurised  boilers) or extra direct connections  (for
open-vent boilers).
Another method uses a 'neutral point manifold' where both boilers are connected to the
manifold, which   is in  turn  connected  to the  hot water  and  radiator  circuits. Suitable
devices come from 

www.esse.com

 and 

www.systemlink.ie

.

 2

 Scheme 1: 

Traditional 2-side system with gravity hot water.

Recommended where mineral fuels are mainly to be used

 Scheme 2:  

 Thermal store system.

Recommended for all uses, and always where wood is the main fuel.

Outline of multiple boiler Link-Up using a neutral-point

manifold

 SCHEME 2: THERMAL STORE

A large body of water is 

stored at a high temperature, 

to supply both taps and 

central heating when needed. 

High and low output phases 

are evened-out; heating 

can operate even if the fire 

is out, eg, next morning.

Recommended for all uses, 

and always where wood is 

the main fuel. In one system, 

a ‘combined’ thermal store 

or ‘heat bank’ of about 300 

litre capacity is directly 

heated by the boiler and 

has an indirect coil [1] in 

its highest (hottest) part 

to supply tap water, below 

which the central-heating 

flow is taken-off as needed.

Pump (P1) circulates hot 

water from the boiler to 

the store only when a pipe 

thermostat on the boiler 

flow pipe is above c50°C. 

The separate, central 

heating pump (P2) operates 

only when the time-clock, 

room thermostat and a 

second c50°C thermostat 

responsive to temperature in 

the store, areall ‘closed’.  

A second thermostat towards 

the top of the store closes 

at c90°C to dissipate heat 

if there is risk of boiling.

Extra indirect coils may 

be provided at [2] to 

accommodate a supply from 

a second central-heating 

boiler, and at [3] to receive 

relatively low-grade heat 

from solar panels.

(about 90°C) to override 

controls and run the 

heating circuit to dissipate 

heat if there is a risk of 

boiling. Stored hot water 

for taps is not controlled, 

but accumulates during 

normal operation, especially 

during periods while central 

heating is not required.

 

BOILER STOVE CENTRAL HEATING SYSTEMS

This is a rough guide to specifying and fitting central heating using a solid fuel boiler stove with thermostatic control. It doesn't cover
every detail, which will need to be determined on-site by a skilled heating engineer.
'Wet' solid fuel central heating systems use the same types of pipework (including microbore, plastic) and heat emitters (radiators,
underfloor, etc), as other fuels and they can likewise come on in the morning, go off at night and regulate themselves. Systems must...

1: CONTROL THE HEATING SYSTEM.  

Stove boilers control their own water temperature by an internal thermostat, so controls

such as time clocks and thermostats regulate flow through the heating circuit, not the boiler.

2: GUARD AGAINST CONDENSATION! 

Solid fuels contain water which can condense on cool boiler faces to cause VERY rapid corrosion

and failure. Use 

very

 dry fuel and 

always

 fit a device such as a low-level thermostat to minimise cool water circulating through the boiler.

2:   ALLOW   FOR   EXCESS   HEAT.  

The   fire   can   close  down   automatically,   but   it   can't  

completely  

stop  combustion   and   output   will   vary

considerably during a fuelling cycle. There must be some infallible means of dissipating, and preferably storing, surplus heat, for instance a
hot water cylinder or a thermal store and always a system to run the central-heating pump if there is risk of boiling. Should thermostat and
pump fail together, there must be infallible provision to cool the system, or allow it to boil, for instance through an open vent. (The old-
fashioned idea of deliberately wasting heat through a permanent "heat leak" radiator not only throws heat away, it just will not suffice with
powerful modern stoves.)

 HEAT REQUIREMENT

GET   THE   RIGHT   SIZE   HEATERS.  

Guesswork   won't   do.   A   preliminary  estimate   of   heat

requirement for each room can be got from the table here. 

Example

: A room 6m x 5m x 2.8m

has volume of 84m³. If it was a ground floor room in the corner of a two-storey house, in
which the adjacent rooms and the one above were also heated, then 2 unheated outside
walls + 1 outside floor = 3 unheated faces. If moderately insulated then the factor in the table
is 40 Watts per m³, so 84m³ x 40 = 3360 Watts, or 3.36kW. A radiator, or radiators, emitting
at least 3.36kW should be specified.
Don't   forget   that,   with   boiler   stoves,   the   room   output   and   water   output   go   up   and   down
together - turn the central heating down, and the whole stove goes cooler. It is usually wise to
fit a radiator (with thermostatic valve) in the fireplace room.
The actual value varies with the shape, exposure, draughtiness and temperatures. For larger
installations or whole-house heating, use the more accurate 'U-Value method - an online
heat-need calculator is available at 

www.soliftec.com

APPROXIMATE HEAT REQUIREMENT OF ROOMS

Watts 

per

 Cubic Metre

Number of unheated faces

1

2

3

4

5

6

 

No effective insulation 

eg: all-glass rooms with single glazing, barns, workshops, tents

120

132

145 158 170 183

Poor insulation 

eg; single glazing, little loft insulation, uninsulated cavity walls, draughts

62

70

78

86

94 102

Moderate insulation 

eg: thick solid walls, some loft insulation, some draught-proofing

31

35

40

44

48

53

Good Insulation 

eg: some wall insulation, thick loft insulation, double glazing, draught-proofing

21

24

27

31

34

37

Best insulation 

eg: properties built to 2008 UK standards

16

18

20

22

24

26

Watts (W) per cubic metre 

 CONTROLS 

Your   stove   has   a   built-in
mechanical   thermostat   to
regulate

 

its

 

water

temperature. A tiny vial of oil
is  fitted  in  the  boiler.  As  the
boiler   water   gets   hotter,   the
oil expands along a fine tube,
moves   a   bellow   outward,
moving an arm, which closes
off   air   to   the   fuel   and   so
slows combustion. So, if the timeclock or room thermostat determines
that no heat is needed, it stops the circulating pump; without water
circulation the boiler begins to get too hot, the oil expands, shuts off
air and the fire dies down. If there is demand for heat, for instance in
the morning, the pump comes on, colder water enters the boiler, the
air-flap opens and the fire blazes up.  

The control dial on the stove does not directly turn the stove up and
down, it sets the water temperature at which the thermostat will begin
to shut the fire down.

We recommend a control system regulating the central-heating pump through (1) a single-channel time clock, (2) a centrally-located
room thermostat (not in the stove room) and (3) thermostatic radiator valves on all but one radiator. A low-level (about 50°C) pipe
thermostat to prevent pumped circulation of cool water (which can cause condensation, rust, and deplete stored hot water) and a high
level one (about 90°C) to override controls and run the heating circuit to dissipate heat if there is a risk of boiling. Stored hot water for
taps is not controlled, but accumulates during normal operation, especially during periods while central heating is not required.

 1

Copyright © and UK Design Right, Glyn Hughes 2006-2013. 

'Teddington' thermostat

(Normal cold '0' setting -  about 7mm open)

Typical wiring layout through connector block (return dotted)

Room and boiler outputs vary together

 

BOILER STOVE CENTRAL HEATING SYSTEMS

This is a rough guide to specifying and fitting central heating using a solid fuel boiler stove with thermostatic control. It doesn't cover
every detail, which will need to be determined on-site by a skilled heating engineer.
'Wet' solid fuel central heating systems use the same types of pipework (including microbore, plastic) and heat emitters (radiators,
underfloor, etc), as other fuels and they can likewise come on in the morning, go off at night and regulate themselves. Systems must...

1: CONTROL THE HEATING SYSTEM.  

Stove boilers control their own water temperature by an internal thermostat, so controls

such as time clocks and thermostats regulate flow through the heating circuit, not the boiler.

2: GUARD AGAINST CONDENSATION! 

Solid fuels contain water which can condense on cool boiler faces to cause VERY rapid corrosion

and failure. Use 

very

 dry fuel and 

always

 fit a device such as a low-level thermostat to minimise cool water circulating through the boiler.

2:   ALLOW   FOR   EXCESS   HEAT.  

The   fire   can   close  down   automatically,   but   it   can't  

completely  

stop  combustion   and   output   will   vary

considerably during a fuelling cycle. There must be some infallible means of dissipating, and preferably storing, surplus heat, for instance a
hot water cylinder or a thermal store and always a system to run the central-heating pump if there is risk of boiling. Should thermostat and
pump fail together, there must be infallible provision to cool the system, or allow it to boil, for instance through an open vent. (The old-
fashioned idea of deliberately wasting heat through a permanent "heat leak" radiator not only throws heat away, it just will not suffice with
powerful modern stoves.)

 HEAT REQUIREMENT

GET   THE   RIGHT   SIZE   HEATERS.  

Guesswork   won't   do.   A   preliminary  estimate   of   heat

requirement for each room can be got from the table here. 

Example

: A room 6m x 5m x 2.8m

has volume of 84m³. If it was a ground floor room in the corner of a two-storey house, in
which the adjacent rooms and the one above were also heated, then 2 unheated outside
walls + 1 outside floor = 3 unheated faces. If moderately insulated then the factor in the table
is 40 Watts per m³, so 84m³ x 40 = 3360 Watts, or 3.36kW. A radiator, or radiators, emitting
at least 3.36kW should be specified.
Don't   forget   that,   with   boiler   stoves,   the   room   output   and   water   output   go   up   and   down
together - turn the central heating down, and the whole stove goes cooler. It is 

usually wise to

fit a radiator (with thermostatic valve) in the fireplace room.

The actual value varies with the shape, exposure, draughtiness and temperatures. For larger
installations or whole-house heating, use the more accurate 'U-Value method - an online
heat-need calculator is available at 

www.soliftec.com

APPROXIMATE HEAT REQUIREMENT OF ROOMS

Watts 

per

 Cubic Metre

Number of unheated faces

1

2

3

4

5

6

 

No effective insulation 

eg: all-glass rooms with single glazing, barns, workshops, tents

120

132

145 158 170 183

Poor insulation 

eg; single glazing, little loft insulation, uninsulated cavity walls, draughts

62

70

78

86

94 102

Moderate insulation 

eg: thick solid walls, some loft insulation, some draught-proofing

31

35

40

44

48

53

Good Insulation 

eg: some wall insulation, thick loft insulation, double glazing, draught-proofing

21

24

27

31

34

37

Best insulation 

eg: properties built to 2008 UK standards

16

18

20

22

24

26

Watts (W) per cubic metre 

 CONTROLS 

Your   stove   has   a   built-in
mechanical   thermostat   to
regulate

 

its

 

water

temperature. A tiny vial of oil
is  fitted  in  the  boiler.  As  the
boiler   water   gets   hotter,   the
oil expands along a fine tube,
moves   a   bellow   outward,
moving an arm, which closes
off   air   to   the   fuel   and   so
slows combustion. So, if the timeclock or room thermostat determines
that no heat is needed, it stops the circulating pump; without water
circulation the boiler begins to get too hot, the oil expands, shuts off
air and the fire dies down. If there is demand for heat, for instance in
the morning, the pump comes on, colder water enters the boiler, the
air-flap opens and the fire blazes up.  

The control dial on the stove does not directly turn the stove up and
down, it sets the water temperature at which the thermostat will begin
to shut the fire down.

We recommend a control system regulating the central-heating pump through (1) a single-channel time clock, (2) a centrally-located
room thermostat (not in the stove room) and (3) thermostatic radiator valves on all but one radiator. A low-level (about 50°C) pipe
thermostat to prevent pumped circulation of cool water (which can cause condensation, rust, and deplete stored hot water) and a high
level one (about 90°C) to override controls and run the heating circuit to dissipate heat if there is a risk of boiling. Stored hot water for
taps is not controlled, but accumulates during normal operation, especially during periods while central heating is not required.

 1

Copyright © and UK Design Right, Glyn Hughes 2006-2013. 

'Teddington' thermostat

(Normal cold '0' setting -  about 7mm open)

Typical wiring layout through connector block (return dotted)

Room and boiler outputs vary together

Typical wiring layout through 
connector block (return dotted)

‘Teddington’ thermostat (Normal 
cold ‘0’ setting - about 7mm open)

Scheme 1: Traditional 2-side system with gravity hot water.

Recommended where mineral fuels are mainly to be used

 Scheme 2:  Thermal store system. Recommended for  

all uses, and always where wood is the main fuel.

Outline of multiple boiler Link-Up using  

a neutral-point manifold

Summary of Contents for DB15

Page 1: ...HIGH EFFICIENCY MULTI SOLID FUEL CENTRAL HEATING STOVE WITH AUTOMATIC CONTROL Issued 10 09 2013 456 PLEASE LEAVE THIS DOCUMENT WITH THE HOUSEHOLDER DB15 INSTALLATION AND OPERATING INSTRUCTIONS ...

Page 2: ...h timber thatch or other vulnerable materials take specialist advice It is not possible to access the chimney for cleaning through the stove inspection and sweeping access must be provided The chimney must Generate a draught in use of at least 12Pa 0 05ins wg Be capable of withstanding the temperatures generated Be absolutely incapable of leaking fumes into the dwelling Several different forms of ...

Page 3: ...r manufactured smokeless fuels then empty the ash regularly if it builds up it will severely damage the grates If you mainly use wood then do the opposite let the ash and charcoal build up To empty the ash agitate the firebed by using the tool to operate the riddling mechanism on the right hand side Use the ashpan tool to lift out the ashpan Remember to let ash cool before disposing in plastic sac...

Page 4: ...himney Checktherequirementsearlier in this document and in any case of doubt engage a professional sweep or chimney engineer POOR AIR SUPPLY Lack of air to the fire is a common cause of smoking and poor performance Air supply problemsmaybe worseincertain wind conditions often incorrectly ascribed to downdraught which is in fact very rare where air can be sucked out of the room The answer is to fit...

Page 5: ...hemselves Systems must 1 CONTROL THE HEATING SYSTEM Stove boilers control their own water temperature by an internal thermostat so controls such as time clocks and thermostats regulate flow through the heating circuit not the boiler 2 GUARD AGAINST CONDENSATION Solid fuels contain water which can condense on cool boiler faces to cause VERY rapid corrosion and failure Use very dry fuel and always f...

Page 6: ...ratures are approximate and will vary Scheme 1 TRADITIONAL 2 SIDE Compact and quick to heat Stores hot water for taps but radiators will go cold if the fire goes out Recommended for occasional use or where long burning mineral fuels are used One side of the boiler feeds by gravity circulation alone an indirect coil to heat a hot water storage cylinder and has feed and vent connections to a small o...

Page 7: ... 8 5 7 6 2 7 8 9 1 To water kW 6 3 8 8 7 9 7 7 7 6 Total Output kW 12 1 14 5 4 1 15 5 16 7 Mean Flue Gas Temp Rise ºC 200 C 263 C 251 C 276 C 241 C CO 13 o2 0 06 0 24 0 07 0 24 0 23 Minimum room air entry requirement 8000 mm Minimum Clearance to combustibles 100mm at sides and back Temperature underneath can exceed 100 C traditional hearth required These stoves exceed the safety and performance re...

Reviews: