background image

MORTEX

 

PRODUCTS

 

INC

 

FORT

 

WORTH,

 

TX

 

76106

 

Page

 

10

 

white thermostat wire to the W” terminal on the furnace 
terminal strip. This signal energizes the heater contactor(s) 
closing the contacts to the heaters. The blower heating speed 
wire is connected to the “W” terminal on the terminal block so 
the blower is energized at the after the ON delay has expired. 
The blower will continue to operate until the thermostat call 
for heat has been satisfied. When the call for heat has been 
satisfied the “W” terminal is de-energized and the heater 
contactor opens turning off the heater. The blower motor will 
continue to operate until the OFF delay has expired. The 
furnace is now in standby mode waiting for the next heating 
cycle.  

 

The 12 kW, 15 kW and 20 kW models have a black wire that 
is connected to the “W” terminal on the terminal block. For 
two stage operation the black wire needs to be removed from 
the “W” terminal and connected to the W2 wire from the 
thermostat. Connect the wires using a wire nut. The other end 
of the black wire is connected to the 24 VAC coil on the 
second heater contactor. You must have a thermostat that has 
the second stage heating feature “W2”. The second stage heat 
cycle is enabled when the room temperature typically falls 
more than 3 degrees below the thermostat set point. The 
thermostat energizes the second heater to aid in heating the 
room back to the thermostat set point. Once the room is within 
1 degree of the thermostat set point the second stage heater is 
de-energized until the thermostat calls for second stage heat 
“W2” again. 

 

 

 

 
 
 
 
 
 
 
 
 

SECTION V: TROUBLE SHOOTING  

 

The following checks should be made before trouble shooting 
the furnace controls for a no heat issue. 
1.

 

Check all of the circuit breakers. Make sure they are 
turned to the “ON” position and have not tripped. 

2.

 

Check all fuses, especially the 3 amp fuse on the top right 
side of the control box. If the fuse is blown, check the 
wiring with an OHM meter for a short to ground. If 
shorted, repair the short, and then replace the fuse. 

3.

 

Check any electrical switches that are external to the 
furnace to make sure they are turned on. 

4.

 

Check all wiring connections, especially on any of the 
components, to ensure they are securely fastened. 

 

If you have 240 VAC coming out of the control box circuit 
breakers and you have 24 VAC between the load side if the 3 

amp fuse and ground, then continue on through the rest of the 
checks. 

 

CONSTANT TORQUE Motor Check – Heating Mode 

1.

 

If the motor is not running, check for 240 VAC on the L1 
and L2 terminals. Check 24 VAC at the motor terminals 
connected to the “W” and “C” terminal on the terminal 
block. If the 240 VAC and 24 VAC is present continue to 
the steps below. Refer to Figure 10 and Table 1 for 
terminal locations and definitions. 

A.

 

If 240 VAC is not present at the motor check for a 
broken wire between the circuit breaker and the 
motor.  

B.

 

If 240 VAC is present at the motor terminals continue 
to the next check. 

C.

 

If 24 VAC is not present at the motor check the fuse 
or transformer. 

D.

 

If 24 VAC is present at the terminal block “W” and 
“C” terminals then check the motor connections. 

E.

 

If the motor connections are ok then the motor is bad 
and needs to be replaced.  

 

CONSTANT TORQUE Motor Check – Cooling Mode 

1. If the motor is not running, check for 240 VAC on the L1 

and L2 terminals. Check 24 VAC at the motor terminals on 
the “Y” and “C” terminals on the terminal block. If the 240 
VAC and 24 VAC is present continue to the steps below. 
Refer to Figure 10 and Table 1 for terminal locations and 
definitions. 
A. 

If 240 VAC is not present at the motor check for a 
broken wire between the circuit breaker and the 
motor.  

If 240 VAC is present at the motor terminals continue 
to the next check. 

C. 

If 24 VAC is not present at the motor check the fuse 
or transformer. 

D. 

If 24 VAC is present at the terminal block “Y” and 
“C” terminals then check the motor connections. 

E. 

If the motor connections are ok then the motor is bad 
and needs to be replaced.  

 

 

 

Figure 10: Constant Torque Motor Terminals 

 

 
 
 

 

For personal safety be sure to turn the electrical power 
“OFF” at the main circuit panel (Circuit Breaker Box) 
before attempting any service or maintenance operations. 
Home owners should never attempt to perform any 
maintenance which requires opening the furnace control box 
door.  

To avoid personal injury or property damage, make certain 
that the motor leads cannot come into contact with non-
insulated metal components of the unit. 

Summary of Contents for E30 SERIES

Page 1: ...Torque Motor 14 9 Replacement Parts List 3 4 HP Constant Torque Motor 19 5 Blower Performance 3 4 HP Constant Torque Motor 15 CONTACT INFORMATION Contact us by mail Manufactured and Distributed by Mo...

Page 2: ...block or obstruct air openings used for ventilation and cooling of the furnace electrical components 8 Refer to the furnace rating plate for the furnace model number for the operating specifications...

Page 3: ...an The furnace s best friend is a qualified service technician If the unit gives any indication of improper operation call the service technician The service technician is allowed to perform the norma...

Page 4: ...of the furnace to make sure there are no flammable materials in the area If you smell vapors of any kind DO NOT turn on the power to the furnace until vapors have been ventilated and removed from the...

Page 5: ...s on the center shelf Refer to Figure 6 10 Push the upper door forward and tighten with the thumb screw until the door is secured to the cabinet Refer to Figure 6 11 Follow the instructions to Turn On...

Page 6: ...ted as to how to clean and reinstall filters washable or replaceable filters for good preventive maintenance Care must be taken that the edges of the washable or replaceable filter are resting on the...

Page 7: ...cause serious injury if clothing or body parts get caught in the moving part The manufacturer or distributer will not be responsible for any repairs due to improper parts changes improper maintenance...

Page 8: ...trol Box Cover Figure 8 Blower Assembly and Mounting Screw Location 8 Check the blower wheel for dust and debris Use the brush and the vacuum cleaner to remove any dust or debris from the wheel Be car...

Page 9: ...heating or cooling operation 9 Thermostat Y Circuit The thermostat Y circuit is used for cooling or high speed indoor fan operation When 24 VAC is placed on the thermostat Y circuit the 24 vac is sen...

Page 10: ...heck all wiring connections especially on any of the components to ensure they are securely fastened If you have 240 VAC coming out of the control box circuit breakers and you have 24 VAC between the...

Page 11: ...tactor check for 24 VAC between the A1 and A2 terminals If 24 VAC is present then replace the heater contactor L1 L2 T1 T2 A 1 A 2 Figure 11 Heater Contactor Terminal Designations Blower Motor FLA 1 3...

Page 12: ...2 741 615 466 LO 764 689 586 507 460 399 332 MED LO 855 807 733 632 571 521 478 416 367 MEDIUM 990 923 878 825 741 672 628 574 520 440 MED HI 1085 1031 988 929 878 789 725 663 603 474 HI 1291 1247 120...

Page 13: ...56 630 494 with Cabinet MEDIUM 1251 1216 1170 1134 1079 1045 1009 860 685 570 97 FLSB 27 MED HI 1450 1410 1380 1335 1303 1221 1139 1056 737 580 or 97 FLSF 27 HI 1549 1506 1457 1410 1335 1246 1165 1056...

Page 14: ...1245 1137 1012 679 551 or 97 FLSF 39 HI 1570 1531 1488 1415 1344 1279 1170 1070 736 562 CFMwith Coil LO 851 813 759 708 618 555 523 458 394 362 98 8Z12W OP MED LO 1021 982 934 884 837 740 684 636 573...

Page 15: ...4 1065 874 711 561 with Cabinet MEDIUM 1404 1350 1327 1294 1251 1211 1145 1005 718 535 97 FSOB 39 MED HI 1601 1538 1468 1400 1327 1241 1148 888 719 541 HI 1725 1613 1530 1442 1360 1283 1190 1088 739 5...

Page 16: ...TON ACCESSORY BLOWER 86MH0025 3 4 HP PSC 5 TON ACCESSORY BLOWER 86MH0026 3 4 HP CONSTANT TORQUE 5 TON ACCESSORY BLOWER 86MH0027 21 1200 CFM BROKE DOWN COOLING COIL CABINET 97 FLSB 21 21 1600 CFM BROK...

Page 17: ...019P R68AB0019P 6 HEATER CONTACTOR 2 R68AB0019P R68AB0019P R68AB0019P 7 TRANSFORMER R68AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 8 CIRCUIT BREAKER 1 R68BAD014 R68BAD016 R68BAD018 R68BAD...

Page 18: ...HEATER CONTACTOR 2 R68AB0019P R68AB0019P R68AB0019P 7 TRANSFORMER R68AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 8 CIRCUIT BREAKER 1 R68BAD015 R68BAD017 R68BAD018 R68BAD015 R68BAD018 R68B...

Page 19: ...AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 8 CIRCUIT BREAKER 1 R68BAD015 R68BAD017 R68BAD018 R68BAD015 R68BAD018 R68BAD018 9 CIRCUIT BREAKER 2 R68BAD014 R68BAD013 R68BAD017 10 LOW VOLTAGE TERMINAL...

Reviews: