background image

5

Mortex Products, Inc. / FT. WORTH, TX 76106  

G17 / G18 Installation Instructions  

Printed 04/04

4

Mortex Products, Inc. / FT. WORTH, TX 76106  

G17 / G18 Installation Instructions  

Printed 04/04

INSTALLATION INSTRUCTIONS

RETURN AIR

ALCOVE INSTALLATION 

The furnace may be installed free standing or in an alcove
with a free flow of air back to the furnace. A minimum of
18” shall be provided at the front for return air and service
access.

CLOSET INSTALLATION - 6 in. 

NOTE: If return air is through a side wall, there must be a
minimum of 6-in. clearance from side wall to furnace in
addition to 6-in. minimum clearance from inside of closet
door to front of furnace.

If a louvered door complying with the minimum air require-
ments is used, the front clearance may be reduced to 1”.

CLOSET INSTALLATIONS
Additional Requirements

Concerning under floor or ceiling return air systems, the 
following items (1-10) must be adhered to:

1. The return-air opening into the closet, regardless of 
location, is to be sized not less than specified on the 
appliance rating plate.

2. If the return-air opening is located in the floor of the
closet (versus the vertical front or side wall),  the 
opening is to be provided with means to prevent its 
inadvertent closure by a flat object placed over the 
opening.

3. The cross-sectional area of the return duct system 
(when located in the floor or ceiling of the 
manufactured home) leading into the closet is to be not
less than that of the opening specified on the appli-
ances rating plate. 

4. The total free area of openings in the floor or ceiling
registers serving the return-air duct system is to be not 
less than 150% of the size opening specified on the 
appliance rating plate.  At least one such register is to
be located where the likelihood of its being covered by
carpeting, boxes, and other objects is minimized.

5. Materials located in the return duct system have a
flame spread classification of 200 or less.

6. Non-combustible pans having one-inch upturned
flanges are located beneath openings in the floor
return duct system.

7. Wiring materials located in the return duct system
conform to Article 300-22 (B&C) of the National
Electric Code, ANSI / NFPA-70.

8. Gas piping is not run in or through the return duct
system.

9. The negative pressure in the closet, as determined
by test with the air-circulating fan operating at high 
heating speed and the closet door closed, is to be not
more negative than minus 0.05-inch water column.

10. For floor return systems, the manufactured home
manufacturer or installer shall affix a prominent 
warning where it is easily read when the closet door is
open. 

The marking shall read:

HAZARD OF ASPHYXIATION

DO NOT COVER OR RESTRICT FLOOR

OPENING, or equivalent

WARNING

RETURN AIR

ALCOVE

A minimum of 18” front clearance to a facing
wall or partition is needed for service access
and return air. 

Provide a removable panel above the furnace
for access to roof jack and  pipe connections on
top of the furnace.

CLOSET - 6” CLEARANCE

A minimum of 250 sq. in free open area return
opening is required to the closet.  The return
opening may be anywhere on or above the
closet door.  If the return is through a side wall,
and the opening is below the top of the furnace,
a minimum of 6-in. clearance from side wall to
furnace must be provided in addition to 6-in
minimum clearance from inside of closet door to
furnace.  

If a 5T A/C will be installed, the return shall be
increased to 390-sq. in. open area. 

SPECIAL-CLOSET, 1” CLEARANCE

For closet installations with less than 6-in. 
clearance from inside of closet door to furnace,
a louvered closet door must be used with a min.
of 250 sq. in open area directly in line with the
furnace top louver panel as shown. A fully 
louvered closet door may be used.

If a 5T A/C will be installed, the return shall be
increased to 390 sq. in open area directly in
line with the furnace louver panel.

ALCOVE INSTALLATION

CLOSET INSTALLATION

*SPECIAL - 1”- 6” CLOSET INSTALLATION

Summary of Contents for G17D

Page 1: ...th a cooling unit the furnace shall be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the heat exchanger For installations with a parallel flow arrangement the furnace must be equipped with a damper or other means to prevent cold air from being discharged up around the heat exchanger GAS VALVE CONVERSION INSTRUCTIONS 1 Follow instructions TO TURN OFF G...

Page 2: ...n 6 PART NO DESCRIPTION NOTES 90 RJF1729 AL Body Roof Jack Gas FLAT Height A 73 in 85 in 90 RJF2551 AL Body Roof Jack Gas FLAT Height A 81 in 107 in 90 RJS1729 AL Body Roof Jack Gas SLOPE 3 12 Height B 81 in 101 in 90 RJS2551 AL Body Roof Jack Gas SLOPE 3 12 Height B 97 in 123 in 90 RJS3868 AL Body Roof Jack Gas SLOPE 3 12 Height B 110 in 140 in 90 RJS6399 AL Body Roof Jack Gas SLOPE 3 12 Height B...

Page 3: ...stem have a flame spread classification of 200 or less 6 Non combustible pans having one inch upturned flanges are located beneath openings in the floor return duct system 7 Wiring materials located in the return duct system conform to Article 300 22 B C of the National Electric Code ANSI NFPA 70 8 Gas piping is not run in or through the return duct system 9 The negative pressure in the closet as ...

Page 4: ...ng above the floor Bend sides over onto the floor surface Fig F 8 Install floor base over floor opening with 13x13 flanges down Nail to floor thru 4 holes Fig G INSTALL FURNACE Prior to installing furnace fuel and A C line openings may be cut in See FIG D 1 Remove upper and lower furnace doors 2 Slide furnace onto floor base and push back until cabinet is against rear flange of floor base 3 Secure...

Page 5: ...es gas line connection point To furnace gas control valve To furnace wall thermostat 4 Upper crown in original carton must be stored in a prominent location inside the home until crown installation is made at site location AT MANUFACTURED HOME SITE 5 The transit weather cap is removed and 6 90 RJCRWN AL crown installed per these instructions See FIG K Make sure crown engages RJ body pipes above th...

Page 6: ...ator on the gas control valve must also be converted See label on lower furnace compartment for full instructions If the gas input to the furnace is too high due to excessive gas pressure wrong size burner orifice no orifice high altitude etc the burner flame will be sooty especially with Propane gas This type of furnace operation can produce carbon monoxide which could result in unsafe operation ...

Page 7: ...ADY MODELS G17D060 G17D070 P N 61GFC004 Mortex Products Inc FT WORTH TX 76016 H 2 10 1 4 HP 2 SPD BLOWER HEATING SPEED SELECTION G17D060 G17D070 LO OR HI SPEED TAP FIG N G17D060 G17D070 W PILOT HEATING FIG O G17D060B G17D070B W PILOT A C READY FIG Q G17D090B W PILOT A C READY FIG P G17D090 W PILOT HEATING WARNING ELECTRIC SHOCK HAZARD Disconnect all electric power before servicing 1 Incoming wire ...

Page 8: ... R68CA0005 R86GF0050 R86GF0050 R68GF0001 R68GF0006 R68GF0007 R68BKN007 R86GF0051 R86GF0052 R68GF0004 R68DD0009 R68DD0009 R68DD0008 R68GF0002 R68CA0004 R86GF0053 R86GF0054 R86GF0054 R68GF0005 R76AA0002 R86GF0055 R86GF0123 R86GF0119 R65GF0001 R65GF0002 R65GF0003 R86GF0056 R68DE0001 R68DE0002 R68DE0003 R69AB0001 R68AB0002 R68AB0002 R68CA0007 R68CA0006 R68GF0009 R68GF0008 R86GF0057 R86GF0058 R87NBF007...

Reviews: