[P.17]
Alarm Output Timing [ 1']
[inh.] 1-59 secs 1-15 mins and [cont]. Time-out of the alarm output. The code [cont]
disables the time-out, and the alarm remains energized until the OFF operating mode
is selected. The [inh.] mode enables the use of the external contactor
[P.18]
Temperature Switch [n.o.]
Selection: [n.o.] or [n.c.]
[n.o.]
the engine shuts down if the contact closes
[n.c.]
the engine shuts down if the contact opens
[P.19]
ALARM Control [n.c.]
Selection: [n.o.] or [n.c.]
[n.o.]
the engine shuts down if the contact closes
[n.c.]
the engine shuts down if the contact opens
[P.20]
Remote Start [n.o.]
Selection: [n.o.] or [n.c.]
[n.o.]
the engine starts if the contact closes
[n.c.]
the engine starts if the contact opens
[P.21]
Under Speed
setting [1200]
[Inh.] or 100-4000 r.p.m. The [Inh.] code disables the Under Speed shut down.
[P.22]
Over Speed setting [1700]
100-4000 rpm or [Inh.]. The EP6 provides one second bypass delay. The [Inh.] code
(>4000 r.p.m.) disables the Over Speed shut down.
[P.23]
Number of Teeth of the Flywheel [Inh.]
[Inh.] or 1-500 teeth.
The [Inh.] code disables the reading of the Speed (section 3.0), the Over/Under
Speed alarms, and the Crank termination (see [P.24]).
[P.24]
Crank OFF [Inh.]
Crank Termination setting: 100-800 rpm
If the speed rises above the setting, the EP6 terminates the crank cycle. One sec-
onddelay avoids false termination.The code [Inh.] inhibits the crank termination
[P.25]
Low Oil Pressure Alarm By-Pass [ 6"]
Range: 0-99 secs. By-Pass Delay to ignore the Oil Pressure (input #3) during the
engine starting cycle. This input requires normally closed contact
[P.26]
Automatic Periodic Test Cycle [inh.]
Range: [inh.], 1-99 days
This is the interval time between the automatic periodic tests of the engine. The code
[inh.] disables the Automatic Periodic Test (see section 19.0)
[P.27]
Automatic Engine Test Duration [ 10']
Range: 1-99 minutes.
This is the duration of the automatic engine test.
[P.28]
Generator warm-up timing [ 20"]
Range [inh.] 1-59 secs or 1-15 mins ([inh.]=No warm-up)
Active only when [P17]= [inh.] and the ALARM output is used to drive the contactor
[P.29]
Generator cooling timing [ 30"]
Range [inh.] 1-59 secs or 1-15 mins ([inh.]=No cooling)
Active only when [P28]= [inh.] and the ALARM output is used to drive the GEN-SET
contactor
[P.30]
N° poles of the alternator [...]
Range [inh.] - [2] = 2 pole alternator - [4] = 4 pole alternator
[P.31]
Engine shut-down delay for low fuel [5']
Range [inh.] = provides only optical - acoustical warning - 1 - 99 min.
PROTECTIONS
EP6 ENGINE PROTECTION
M
39.12.
3
REV.1-03/11
12/10/05 M39GB