Part Number: 000016427 Rev 00 08/2020 111
RECOVERY AND RECHARGING PROCEDURES
Do not purge refrigerant to the atmosphere. Capture refrigerant using recovery
equipment. Follow the manufacturer’s recommendations.
Important
No responsibility is assumed for the use of contaminated refrigerant. Damage resulting
from the use of contaminated refrigerant is the sole responsibility of the servicing
company.
Important
Replace the liquid line drier before evacuating and recharging. Use only an O.E.M. liquid
line filter drier to prevent voiding the warranty.
CONNECTIONS
1. Suction side of the compressor through the suction service valve.
2. Discharge side of the compressor through the discharge service valve.
3. Liquid side through the liquid line drier.
SELF-CONTAINED RECOVERY/EVACUATION
1. Cycle the toggle switch Off.
2. Install manifold gauge, scale and recovery unit or two-stage vacuum pump and open
high, low and charging ports.
3. Perform recovery or evacuation:
A. Recovery: Operate the recovery unit as directed by the manufacturer’s
instructions.
B. Evacuation prior to recharging: Pull the system down to 500 microns. Then, allow
the pump to run for an additional half hour. Turn off the pump and perform a
standing vacuum leak check.
4. Follow the Charging Procedures.
Summary of Contents for PKM0335
Page 2: ......
Page 8: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 64: ...64 Part Number 000016427 Rev 00 08 2020 Troubleshooting THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 98: ...98 Part Number 000016427 Rev 00 08 2020 Troubleshooting THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 130: ...130 Part Number 000016427 Rev 00 08 2020 Specifications THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 131: ......
Page 132: ...Katom 305 Katom Drive Kodak Tennessee 37764 Part Number 000016427 Rev 00 08 2020 ...