Part Number: 000016427 Rev 00 08/2020 115
CLEANUP PROCEDURE
Mild System Contamination
1. Replace any failed components.
2. If the compressor is good, change the oil.
3. Replace the liquid line drier.
NOTE: If the contamination is from moisture, use heat lamps during evacuation. Position
them at the compressor, condenser and evaporator prior to evacuation. Do not position
heat lamps too close to plastic components, or they may melt or warp.
4. Follow the normal evacuation procedure, except replace the evacuation step with the
following:
A. Pull vacuum to 1000 microns. Break the vacuum with dry nitrogen and sweep the
system. Pressurize to a minimum of 5 psig.
B. Pull vacuum to 500 microns. Break the vacuum with dry nitrogen and sweep the
system. Pressurize to a minimum of 5 psig.
C. Change the vacuum pump oil.
D. Pull vacuum to 500 microns. Run the vacuum pump for 1/2 hour on self-contained
models, 1 hour on remotes.
NOTE: You may perform a pressure test as a preliminary leak check. You should use an
electronic leak detector after system charging to be sure there are no leaks.
5. Charge the system with the proper refrigerant to the nameplate charge.
6. Operate the ice machine.
Summary of Contents for PKM0335
Page 2: ......
Page 8: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 64: ...64 Part Number 000016427 Rev 00 08 2020 Troubleshooting THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 98: ...98 Part Number 000016427 Rev 00 08 2020 Troubleshooting THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 130: ...130 Part Number 000016427 Rev 00 08 2020 Specifications THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 131: ......
Page 132: ...Katom 305 Katom Drive Kodak Tennessee 37764 Part Number 000016427 Rev 00 08 2020 ...