7.4  Under normal conditions, the current and voltage values generated by the  modules may be higher than the standard test 

conditions  of  the  component.  Therefore,  when  designing  PV  power  system  components,  such  as  rated  voltage,  wire 
capacity, fuse capacity or component power output related parameters, the corresponding short-circuit current and open 
circuit voltage should be amplified by 1.25 times. 
 

7.5  Use  limit:  Do  not  install  or  use  modules  in  corrosive  areas,  under  abnormal  environment  conditions,  or  on  mobile  units 

(except solar tracking mounting systems are allowed). Should connect  the negative pole (of the array) to ground , cause it 
can reduce the risk of PID. Doing so will void the product warranty. 

8. Electrical and Physical Ratings  

The electrical and physical properties of the Motech modules are detailed in the table below. 

8.1 Module Electrical Ratings 

 

Model Number 

Pmpp (W) 

Voc(V) 

Isc(A) 

Vmpp(V) 

Impp(A) 

 

XS60GB-315 

315 

39.33 

9.56 

33.55 

9.39 

 

XS60GB-310 

310 

39.19 

9.53 

33.26 

9.32 

 

XS60GB-305 

305 

39.05 

9.50 

32.97 

9.25 

 

XS60GB-315-S 

315 

39.33 

9.56 

33.55 

9.39 

 

XS60GB-310-S 

310 

39.19 

9.53 

33.26 

9.32 

 

XS60GB-305-S 

305 

39.05 

9.50 

32.97 

9.25 

 

 

8.2 Module Physical Properties 

Model Number

 

No. Cells 

(PCS) 

Dimension (mm)  

Length * Width * Frame Height

 

Weight (kg

)

 

 

XS60GB 

60 

1664 

998 

40 

22.5±5% 

 

 
The current and voltage characteristics of Motech modules are within -5%/+10% percent of the indicated values of Isc and Voc 
under standard test conditions (irradiance of 1000 W/m

2

, AM 1.5 spectrum, cell temperature of 25°C).  The maximum power of 

each  Motech  module  is  within  -0%  /  +3%  of  the  indicated  values  of  rated  power  under  standard  test  conditions.  Other 
tolerances may be available upon special request. 

9. Bypass diode 

9.1  Bypass  diodes  are  pre-installed  in  the  junction  box  of  each  Motech  PV  module.    Depending  on  junction  box  type,  each 

junction box model provides 3 Schottky diodes with a maximum current of SB3050DY of 30  Amps. Each bypass diode is 
rated at 50 Vdc reverse voltage.   
 

9.2 Each bypass diode is connected to 1/3

rd

 the total number of cells for a given module type.  Bypass diodes are NOT user-

serviceable components.  DO NOT remove bypass diodes or operate a module without bypass diodes. 
 

Summary of Contents for XS60GB-315

Page 1: ...otech com tw Page Content 1 Disclaimer of Liability 2 2 Rules and regulations 2 3 Important Safety Information 2 4 Safe Work Practices 2 5 Fire installation needs 3 6 Unpacking and storage 3 7 Array D...

Page 2: ...ndling Do not apply bending or twisting forces to the module Do not step on the module or strike the front or back these actions may result in cracked solar cells Do not lift or carry the module by th...

Page 3: ...n be used in series or in parallel to produce the desired output voltage and output current When the modules are connected in series the output voltage of the entire string is the sum of the voltages...

Page 4: ...Vmpp V Impp A XS60GB 315 315 39 33 9 56 33 55 9 39 XS60GB 310 310 39 19 9 53 33 26 9 32 XS60GB 305 305 39 05 9 50 32 97 9 25 XS60GB 315 S 315 39 33 9 56 33 55 9 39 XS60GB 310 S 310 39 19 9 53 33 26 9...

Page 5: ...d to be between 20 C and 46 C Celsius Maximum operating temperature range 40 C Celsius to 85 C 11 3 The minimum safe distance between the module and the module is recommended for 1 cm when the solar p...

Page 6: ...ring Each Motech module is factory equipped with two lengths of 4 0mm 2 UL Recognized PV Wire 90 C rated sunlight resistant Factory cables are terminated with UL TUV Recognized electrical connectors A...

Page 7: ...If hand cleaning is not possible pressure washer cleaning of module glass is permitted only when complying with all of the following restrictions 1 Cleaning fluid water at normal ambient temperature 2...

Reviews: