BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!

FOLLOW NATIONAL, STATE AND LOCAL CODES.

READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION.

The Model 460-VBM MotorSaver

®

 is an auto-ranging voltage monitor designed to protect 3-phase

motors—regardless of size. It can be used on 190–480VAC, 50/60Hz motors to protect from

damage caused by single-phasing, low voltage, high voltage, phase reversal, and voltage
unbalance.

The Model 460-VBM (Voltage Band Monitor) has low and high voltage adjustment knobs and will

only permit motor operation if the voltage is within these limits.

CONNECTIONS

1.

Mount the MotorSaver

®

 in a convenient location in or near the motor control panel. If the

location is wet or dusty, the MotorSaver

®

 should be mounted in a NEMA 4 or 12 enclosure. The

MotorSaver

®

 can be mounted to a back panel using two #6 or #8 x 5/8 screws or can be

snapped onto DIN rail.

2.

Connect L1, L2 and L3 on the MotorSaver’s terminal strip to the LINE SIDE of the motor starter

(see Figure 1).

3.

Connect the output relay to the circuitry to be controlled. For motor control, connect the

normally open contact in series  with the magnetic coil of the motor starter as shown in Figure 1.

For alarm operation, connect the normally closed contact in series with the control circuit as in

Figure 2.

  INSTALLATION INSTRUCTIONS FOR

   SYMCOM’S MOTORSAVER

®

  MODEL 460-VBM

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Summary of Contents for SymCom 460-VBM

Page 1: ...in a convenient location in or near the motor control panel If the location is wet or dusty the MotorSaver should be mounted in a NEMA 4 or 12 enclosure The MotorSaver can be mounted to a back panel...

Page 2: ...460 Figure 1 Motor Control Wiring Diagram LIGHT 460 Figure 2 Alarm Control Wiring Diagram Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 3: ...ceptable voltage and the MotorSaver closing its output contacts For compressor applications the restart delay should be set for the approximate time it takes for the head pressure to bleed off of the...

Page 4: ...light will illuminate If the contacts do not energize and the RUN light does not illuminate see the TROUBLESHOOTING section CONGRATULATIONS YOU HAVE JUST INSTALLED THE FINEST MOTOR PROTECTION AVAILAB...

Page 5: ...tages and calculate the unbalance according to the formula on page 3 If the voltage unbalance does not exceed 5 call SymCom at 800 843 8848 or 605 348 5580 Red light is on steady RED The voltage is ou...

Page 6: ...ht 14 oz Enclosure Polycarbonate Terminal Torque 6 in lbs max Wire AWG 12 20 AWG Safety Marks UL UL508 File E68520 CE IEC 60947 6 2 Standards Passed Electrostatic Discharge ESD IEC 1000 4 2 Level 3 6k...

Page 7: ...l other products manufactured by SymCom shall be warranted against defects in material or workmanship for a period of two 2 years from the date of manufacture For complete information on warranty liab...

Reviews: