07. REQUIREMENTS
RESET TO FACTORY VALUES
Control code 99
. Remove all memory registers including card numbers, system settings, master code
and resets all parameters to default settings.
Do this only when you detect a abnormal operation and if you want to clear all card numbers and pins.
OPERATIONS
INSTRUCTIONS
01 •
Enter programming mode
Master Code
*
#
(The default master code is 30191000)
02 •
Enter control code 99
99
03 •
Exit programming mode
#
CONNECTING CABLES
CABLE MODEL
CABLE SPECIFICATION
MAXIMUM LENGTH
FOR CONNECTION
Power cable
18~22 AWG
30m
Alarm relay
connection cable
18~22 AWG
50m
Exit button
connection cable
18~22 AWG
50m
RS-232 cable
4-Turn Shielded Twisted Pair Wire 20~22 AWG
25m
RS-485 cable
4-Turn Shielded Twisted Pair Wire 20~22 AWG
800m
It is recommended that:
•
Update cable specification according to transmission distance.
•
Update cable specification according to environmental interference factors.
•
Use larger cable strands for future use.
•
The use of shielded twisted pair wire for readers and communication cable to increase transmission
distance and resistance to interference.
1 2
3
4 5
6
7 8
9
*
0
#
Welcome!
1 2
3
4 5
6
7 8
9
*
0
#
Welcome!
08. COMPONENT TEST
DEVICE TEST
To avoid the touch sensor auto-detect interference, please do not touch the sensor when turning on
the device power.
1 •
Turn on the power.
2 •
The reader will emit a beep after 1 second, indicating that initialization is complete.
3 •
The green LED will blink.
4 •
Press the Exit Button to activate the door relay and the electronic lock will activate for 4 seconds.
5 •
Reader emits two short beeps for valid card and three long beeps for invalid card.
6 •
Test is complete.
06. STANDALONE PROGRAMMING