IX34208a_e.doc / Aug-09
Page 20 / 40
The following Operational Parameters provide configuration of the serial interface:
Menu
Setting Range
Default
Serial Timer:
Setting 0,000 allows manual activation of a serial data
transmission at any time. All other settings specify the cycle
time for automatic transmission, when the interface is set to
"Printer Mode"
0,000
0,010 sec
…
9.999 sec
0,100 sec
Between two transmission cycles the unit will allow a pause
depending on the baud rate. The minimum cycle times for
timer transmissions are shown in the table.
Baud
Rate
Minimum Cycle Time [ms]
600 384
1200 192
2400 96
4800 48
9600 24
19200 12
38400 6
Serial Mode:
PC:
Operation according to communication profile
(see 4.4.1)
Print1:
Transmission of string type 1 (see 4.4.2)
Print2:
Transmission of string type 2 (see 4.4.2)
Serial Register-Code:
101
Specifies the register code of the data to be transmitted.
The most important register codes are:
Register
S-Code
ASCII
Description
Original SSI
Value
111
;; 1
Direct encoder data
SSI Value
113
;; 3
Encoder data after
Bit Blanking
Display
value
101
:: 1
Value with full scaling
as it appears in the
display
100
...