64
MCTC manual
9
Outputs
MCBalance, MCPowder, MCHigh Output, MCLiquid
For the location of the output connections, see Electrical connections
Alarm / Warning Output
Connection
27
and
28
.
Warning event:
this output is on (24V), the system continues running).
Alarm event:
this output is on (24V), the system
stops
running.
Free programmable events can be programmed to an
Alarm
or
Warning
. See chapter: Events. For alarm light
connection in multicomponent systems see paragraph: Alarm/warning output in the Multicomponent sector.
Valve Output
Connection
29
and
30
. This output is on (24V) to start the hopper loader or open the knife gate.
Alarm Output (OUT-1)
Normally open contact, connection
32
and
33.
Normally closed contact, connection
32
and
34.
Alarm event:
this output is activated, the systems stops running.
Run Output (OUT-2)
Normally open contact, connection
35
and
36.
The “RUN signal” can be used as a
Start/Stop condition for the molding machine.
For example: Molding machine can only start in case dosing unit is also started.
Default the Run output 2 (OUT-2) is always on in production mode (status Dosing or Standby)
Production status = STANDBY or DOSING
→
output
35
and
36
is CLOSED.
Production status = OFF
→
output
35
and
36
is OPEN.
In case of alarm, the alarm output (OUT-1) is switched and the system is stopped. This also switches output OUT-2.
AUX Output (OUT-3)
Normally open contact, connection
41
and
42
.
Function of OUT-3 depends on loader configuration.
Loader Function
Action
ME
No action
No Action
MV
No action (can be used for 3
rd
party loader)
41
–
42 output CLOSED during fill time
EX
No action
No Action
3PH
Activation of blower loading sequence
41
–
42 output CLOSED during filling
MFD
Activation of compressed air filter cleaning
41
–
42 output CLOSED during blowback time