37
MCTC manual
4
Events
General
In case of an error, the MCTC can generate events. When an error occurs using the MCTC, an event display
will pop up indicating the event type, code, source and description.
Together with the displayed event an output contact will be switched (Warning/Alarm output), this event
screen can be confirmed with the acknowledge button:
The controller itself gives a beeping signal and the red alarm LED will lighten up.
The MCTC keeps track of all active events (multiple simultaneous events are possible).
Movacolor distinguishes 3 different events:
Warning
:
Alarm/warning output is ON, but the system continues running and dosing.
Soft Alarm*:
Alarm/warning output is ON, the inline dosing units continue dosing, MCHybrid is in pause.
Alarm
:
Alarm/warning output and the Alarm relay output are ON and the system
stops running (no
dosing).
* A soft Alarm is only applicable for a MCHybrid
We distinguish 4 different event source levels:
System:
events like aux module events, production settings errors.
Group:
events like main material events.
Unit:
events like motor connection failures, load cell connection errors, CAN bus errors.
Component:
events like low hopper event, deviation errors.
Configuration
(When working with multiple components, some configurations can be made on group level, other event
configurations have to be made for each unit or component separately).
For setting the free programmable events into Alarm Soft Alarm, Warning or off, enter the event
configuration menu. The event configuration menu can be accessed in the advanced settings menu.
By default the unit event configuration list is displayed
Here you can select if the error will act as an alarm, soft alarm, warning or OFF. When OFF selected, no
events will be displayed of this event.
1 Unit/Component navigation buttons
2 Event identifier
3 Event description
4 Event configuration
5 Event level selection buttons
2
3
4
5
1