6

Electrical installation

 

The equipment is supplied with high voltage and 

 

must always be fitted with a safety switch for carrying

 

out servicing work in connection with the fan.

The choice of cable and cable cross-section must comply 

with the national requirements that apply to fixed 

installations.

Z2

U1

Z1

U2

115V 1N~

Z2

U1

Z1

U2

115V 1N~

Clockwise

Counterclockwise

W2

V2

U1

V1

W1

U2

U2

V2

W2

U1+U3

V1+V3

W1+W3

YY

208/230V 3~

W2

V2

U1

V1

W1

U2

U2+U3

V2+V3

W2+W3

U1

V1

W1

Y

460V 3~

1U2

1W2

2U1

2V1

2W1

1V2

YY

208/230V 3~

1U1

1V1

1W1

1U2

1W2

2U1

2V1

2W1

1V2

Y

460V 3~

1U1

1V1

1W1

Single phase fans are supplied with the motor

connected for clockwise rotation. The speed of the

single phase motors CANNOT be regulated.

Three phase fans are supplied with the motor

connected for 460V (Y-connection).

6-Terminal motor for FB 206 and 406:

9-Terminal motor for FB 076 and 106:

W2

V2

U1

V1

W1

U2

U3+W2

V3+U2

V2+W3

U1+W4

V1+U4

W1+V4

YY

208/230V 3~

W2

V2

U1

V1

W1

U2

U2+U3

V2+V3

W2+W3

U1+W4

V1+U4

W1+V4

Y

460V 3~

6-Terminal motor for FB 706 and 1506:

Summary of Contents for 106-3

Page 1: ...INSTALLATION INSTRUCTIONS F18W09_MFB_MUS_EN ...

Page 2: ... User instructions 3 5 General 3 Fan installation 3 5 Maintenance 4 Electrical installation 6 Troubleshooting 7 Technical description 8 General 8 Classification 8 Technical specification 8 Exploded view 9 Accessories 10 ...

Page 3: ...to pressure drop and sound levels In order to achieve optimum performance we recommend that the inlet connection is a straight duct that is 5 times the diameter of the duct If an outlet duct is used the same applies to this If the system requires a 90 bend in the outlet it should deviate in the impeller s direction of rotation see below There is always a risk of clothes or loose items being sucked...

Page 4: ...hieve optimum function Movex recommends the following maintenance schedule Component Interval 6 months Motor Check function Replace motor if necessary Impeller Check for any damage and clear away foreign objects if necessary Replace impeller in the event of damage Fan housing Check that connections are secure and clear away foreign objects Check the drainage hole and clear if necessary ...

Page 5: ...n site An installation that is used when low noise levels are prioritised The disadvantage of this arrangement is that the fan is located high up if the extract air duct is high Note The fan housing needs to be drained for drainage see page 3 A low level sideways outlet direction is suitable in the event of condensation problems Note The base must be made on site due to possible snow Upwards outle...

Page 6: ...208 230V 3 W2 V2 U1 V1 W1 U2 U2 U3 V2 V3 W2 W3 U1 V1 W1 Y 460V 3 1U2 1W2 2U1 2V1 2W1 1V2 YY 208 230V 3 1U1 1V1 1W1 1U2 1W2 2U1 2V1 2W1 1V2 Y 460V 3 1U1 1V1 1W1 Single phase fans are supplied with the motor connected for clockwise rotation The speed of the single phase motors CANNOT be regulated Three phase fans are supplied with the motor connected for 460V Y connection 6 Terminal motor for FB 206...

Page 7: ...or and overcurrent protection To choose the correct contactor see page 6 If technical regulating apparatus e g frequency converter is used the manufacturer s recommendations for avoiding interference must be observed E g EMC protective earth cable length cable shielding etc The one phase motor is equipped with double capacitors When the fan is not operating in full running speed i e during the sta...

Page 8: ...B 406 3 4 0 hp 230 V 3 60 Hz 10 6 A 3530 rpm 0 81 150lb SKO 130 10 115 SMB 140 FB 706 3 7 0 hp 230 V 3 60 Hz 17 6 A 3535 rpm 0 88 227lb SKO 240 15 115 SMB 230 FB 1506 3 15 hp 230 V 3 60 Hz 35 2 A 3550 rpm 0 86 377lb FB 076 3 0 7 hp 460 V 3 60 Hz 1 10 A 3440 rpm 0 81 49lb SKO 16 5 115 SMB 16 FB 106 3 1 0 hp 460 V 3 60 Hz 1 85 A 3360 rpm 0 66 66lb SKO 25 5 115 SMB 25 FB 206 3 2 0 hp 460 V 3 60 Hz 2 ...

Page 9: ... a b 9 1 Bracket 1 a Bolt 4 a Bolt 2 Motor 1 b Washer 4 b Washer 3 Motor plate 1 c Nut 6 a Bolt 4 Impeller 2 a Bolt 6 b Washer 5 Fan housing 2 b Washer 6 c Rivet nut 6 Inlet 2 c Nut 7 a Carriage bolt 7 Outlet grating 3 a Bolt 7 b Washer 3 b Washer 7 c Nut ...

Page 10: ...20 FBD 400 Fits FB 400 FBD 750 Fits FB 750 Vibration damper FBV Intended to be used to prevent the spread of vibrations which can result in increased noise levels Designation FBV 110 is compatible with FB 076 FB 206 FBV 750 is compatible with FB 406 FB 1506 Technical information Material EPDM rubber with mounting components made of chromated steel Weight 0 55 lb Outer dimensions FBV Ø115 16 x 13 1...

Page 11: ......

Page 12: ...104 Commerce Drive Northampton PA 18067 USA Phone 610 440 0478 Fax 610 440 0480 www movexinc com info movexinc com ...