7
Symptom
Possible fault
The fan has stopped Fault in the power supply.
Check the power supply.
Short circuit in connection.
Check for moisture in the safety
switch and motor connection.
Locked impellar
Check that there are no
foreign objects in the fan
housing.
Locked impellar
Check that no ice has formed
in the fan housing.
Locked impellar
Check that the bearing in
the motor is working.
Loss of performance
Mo
t
or winding
Check for resistance between
windings.
Debris
Check that there are no
foreign objects in the fan
housing.
Incorrect direction of rotation
Check the direction of
rotation.
Connections
Check that connections and
duct routing are correct.
In order to satisfy applicable standards, the
FB fan must be fitted with a contactor and
overcurrent protection.
To choose the correct contactor, see page 6.
If technical regulating apparatus (e.g.
frequency converter) is used, the
manufacturer's recommendations for avoiding
interference must be observed. E.g. EMC,
protective earth, cable length, cable shielding,
etc.
.
The one phase motor is equipped with double
capacitors. When the fan is not operating in full
running speed, i.e. during the start-up and shut down
process, the motor produces a mechanical sound,
deriving from the switch between the two capacitors.
This is a normal sound and it is not harmful for the
motor.
Troubleshooting
Always go through the troubleshooting schedule
before contacting Movex. This schedule contains
information that makes it easy to identify faults that
are simple to rectify.
Set external safety switch in the off position.
The fan can start up without warning following
a power outage
Only qualified personnel may perform servicing
work on the fan.