background image

- 6 - 

Auto backup to the ABC-02 when configurations change 
The ABC-02 is capable of backing up switch configuration files 
automatically. This function is found under “System/System Files/ 
Configuration Backup and Restore”. While the ABC-02 is plugged into 
the switch, enable the “Auto backup to ABC-02 when configuration 
change” option. Then click “Apply”. Once this configuration is modified, 
the switch will back up the current configuration under the “/His_ini” 
folder in the ABC-02. The file name will be the system date/time 
(MMDDHHmm.ini). 
Auto backup of the earliest 100 log entries to prevent 
overwriting 
This function is designed to maintain a long-term record the switch log 
files. Moxa Ethernet switches are capable of saving 1000 entries of 
event logs. When the 1000-entry storage limit is reached, the switch 
will delete the oldest saved event log. The ABC-02 can help to backup 
these event logs. When switch log entries reach 1000, the ABC-02 will 
back up the earliest 100 entries of the switch. 
The function is found under “System/System Files/ Log File Backup”. 
Enable the “Auto backup the earliest 100 log entries to prevent 
overwriting”. Then click “Apply”. After that, when the ABC-02 is 
plugged into the switch, the event logs will always be saved to the ABC-
02 automatically. 

NOTE  For further details on the ABC-02 operation through the switch 

web console, please refer to the switch user manual. 

 

 

 

WARNING 

DO NOT remove the ABC-02 when the STATE LED is blinking or 
when the web console is showing WORKING status. 

 

 

NOTE  The status of the ABC-02 may be checked on the switch web 

console or by observing the switch front panel LEDs. 

Operation 

Switch LED status 

The switch detects 
ABC-02-USB plugged 
in 

STATE blinking slowly (1 time/ 2 
seconds), 

Import/Export in 
progress* 

FAULT, MASTER, COUPLER LEDs   
Blink sequentially and circularly   

Import/Export 
successful 

FAULT, MASTER, COUPLER LEDs light 
off 

Save/Load failed 

FAULT LED light on until ABC-02 is 
removed or system reboot 

 

Operation 

ABC-02 LED status 

Power on 

ABC-02 STATE LED green light on 

Reading /Writing 

ABC-02 STATE LED blinking 

*Does not include “Auto backup to the ABC-02 when 
configuration change” and ”Auto backup the earliest 100 log 
entries to prevent overwriting 

 

Summary of Contents for ABC-02-USB

Page 1: ...port Moxa Americas Toll free 1 888 669 2872 Tel 1 714 528 6777 Fax 1 714 528 6778 Moxa China Shanghai office Toll free 800 820 5036 Tel 86 21 5258 9955 Fax 86 21 5258 5505 Moxa Europe Tel 49 89 3 70 0...

Page 2: ...from the ABC 02 USB and backup event logs to the ABC 02 USB It is also an easy and fast diagnostics tool for automation engineers to retrieve configuration files and event logs in the field immediate...

Page 3: ...USB is designed for use with an USB 2 0 port Plug the ABC 02 into the USB port of your Moxa managed switch Securing the ABC 02 on the wall with an M4 screw is suggested Avoid hanging the ABC 02 config...

Page 4: ...load configuration files from the ABC 02 to the switch This function is found under System System Files Configuration Backup and Restore Then select Auto Backup Configurator ABC 02 in the web console...

Page 5: ...tch web console to save the configuration file to the ABC 02 This function is found under System System Files Log File Backup Then select Auto Backup Configurator ABC 02 in the web console Click Backu...

Page 6: ...n is found under System System Files Log File Backup Enable the Auto backup the earliest 100 log entries to prevent overwriting Then click Apply After that when the ABC 02 is plugged into the switch t...

Page 7: ...ing PVC molding IP40 Weight 50 g Installation M4 screw 4 mm Dimension W D H 32 5 97 12 mm Cable Length 35 cm including connectors Operating Temperature 0 to 60 C 32 to 140 F Storage Temperature 20 to...

Reviews: